29
GROUP:UTILITY PARAMETERS (Cont.)
Reg.
Function / Title
Bank
Address
Mask
Adjustment Range
Multiplier
23E
INDUSTRIAL APPL: TEXTILES BLIND
0 / 1
0460
0008
0000: Blind
0001: Unblind
23F
INDUST APPL:MACHINE TOOLS BLIND
0 / 1
0460
0010
0000: Blind
0010: Unblind
240
AM/FM ADJUSTMENT PARAMS BLIND
0 / 1
0461
0001
0000: Blind
0001: Unblind
241
MOTOR PARAMETERS BLIND
0 / 1
0461
0004
0000: Blind
0001: Unblind
8.3.13
GROUP:MOTOR RATING PARAMETERS
Function / Title
Bank
Address
Mask
Adjustment Range
Multiplier
242
NUMBER OF MOTOR POLES
0 / 1
04C3
00FF
0001:
(2)
0002:
(4)
0003:
(6)
0004:
(8)
0005:
(10)
0006:
(12)
0007:
(14)
0008: (16)
2
243
MOTOR RATED CAPACITY
0 / 1
041E
FFFF
0001
∼
270F (0.1
∼
999.9)
0.1
244
MOTOR TYPE
0 / 1
04BF
0030
0000:Toshiba EQPIII motor
(0)
0001:Toshiba STD motor
(1)
0002:Other
(2)
245
2
MOTOR RATED VOLTAGE
(230 / 460v units)
0 / 1
04C6
00FF
0012
∼
0078 (90
∼
600)
5
246
(575v units)
042C
001A
∼
00AC (130
∼
860)
247
MOTOR RATED FREQUENCY
0 / 1
04C7
00FF
0000
∼
00C8 (0
∼
400)
2
248
MOTOR RATED RPM
0 / 1
040C
FFFF
0000
∼
270F (0
∼
9999)
1
249
AUTO-TUNING ENABLE
0
04BE
0008
0000: Auto-tuning disabled
(0)
0001: Auto-tuning enabled
(1)
24A
LOAD MOMENT OF INERTIA
0 / 1
04BF
00C0
0000: Small
(0)
0001: Medium
(1)
0002: Large
(2)
0003: Very large
(3)
8.4
Inverter Fault Codes
Fault codes which can be read at address 10h through 12h are listed below:
INVERTER FAULT CODE TABLE :
FAULT
DATA(Hex)
FAULT
DATA(Hex)
FAULT
DATA(Hex)
NONE
00
MOTOR OL
0E
OPTION ROM
1C
OC (ACCEL)
01
DBR OL
0F
LOW CURRENT
1D
OC (DECEL)
02
OH
10
UV
1E
OC (RUN)
03
E-STOP
11
UNUSED
1F
LOAD-END OC
04
EEPROM WRITE
12
OVER TORQUE
20
U PH. SHORT
05
EEPROM READ
13
EARTH (SOFT)
21
V PH. SHORT
06
UNUSED
14
EARTH (HARD)
22
W PH. SHORT
07
RAM
15
OPEN FUSE
23
LOST INPUT PH
08
ROM
16
DBR OC
24
LOST OUT PH
09
CPU
17
DC OC (ACC)
25
OV (ACCEL)
0A
COMM.
18
DC OC (DEC)
26
OV (DECEL)
0B
GATE ARRAY
19
DC OC (RUN)
27
OV (RUN)
0C
CUR DETECT
1A
AUTO TUNE
28
INV OL
0D
OPTION PCB
1B
INV TYPEFORM
29