background image

 

1 (EN)

 

 

 

Owners Manual 

Touch Screen Controller 

 
 

 
Owners Manual 

 
 

Touch Screen Controller

 

 
 
 

Model Name:  

 

TCB-TSC640-PY 

 
 
 
 
 
 
 
 
 
 

 

Thank you for purchasing this 

TOSHIBA

 Carrier UK Ltd. TCB-TSC640-PY Touch Screen Controller. 

 

  Please read this manual carefully before using to ensure the correct setup and operation of the TCB-

TSC640-PY and related equipment. 

 
 
 
 

Contents:  

 

 

1.  Precautions for Safety ………………………………………………………………………………..…... 
2. Introduction 

…………………………………………………………………………………………........... 

3.  Part names and functions…………………………………………………………………………………. 
4. Commissioning 

…………....…………………………………………………………………………........ 

5. Operation 

…………………………………………………………………………………….................... 

6. Control 

Items.………………………………………………………………………………….................. 

7. Maintenance………………………………………………………………………………………………... 
8.  Trouble shooting ……..….………………………………………………………………………………… 
 
 
 
 

1402113201 

 

 




13 
26 
35 
36 

 

ENGLISH 

Version 1.2 

Содержание TCB-TSC640-PY

Страница 1: ...C640 PY Touch Screen Controller Please read this manual carefully before using to ensure the correct setup and operation of the TCB TSC640 PY and related equipment Contents 1 Precautions for Safety 2 Introduction 3 Part names and functions 4 Commissioning 5 Operation 6 Control Items 7 Maintenance 8 Trouble shooting 1402113201 2 5 8 9 13 26 35 36 ENGLISH Version 1 2 ...

Страница 2: ... or qualified professional fails to do so we shall not be responsible for the conformity of this product When you wish to use this product for any of the following purposes be sure to consult our sales staff and use this product with a margin of rating and performance as well as take appropriate safety measures for safety circuit mechanism etc that will minimize danger in case of failure Use this ...

Страница 3: ...tallation checks are performed by personnel in charge who possesses a thorough understanding pf the machinery to be installed Do not use the input functions of the touch switch etc of the TCB TSC640 PY unit in applications that involve human life in applications that may result in serious injury or for emergency stop switches Do not attempt to disassemble repair or modify the TCB TSC640 PY Otherwi...

Страница 4: ...munication cables correctly The maximum tensile load for connections is 30 N Do not apply loads greater than this Confirm the safety of the system before pressing the touch panel Signals from the touch switches may not be input if the switches are pressed consecutively at high speed Confirm that the touch screen has detected the input of a touch before pressing another switch Input signals from th...

Страница 5: ...ol building structure control all unit control and provides advanced schedule features external device integration via the TCB IFCG1TLE and extensive alarm list and alarm history Specifications TCUK IFMB641 0 OTR PY Interface Power Supply 220 240 VAC 50 60 Hz Power consumption 3 W Operating Temperature 0 to 40 C 10 to 90 RH No Condensation Storage Temperature 20 to 60 C Chassis material Galvanized...

Страница 6: ...xternal View TCUK IFMB641 0 OTR PY Interface Part Name Specification 1 Case Galvanized sheet metal 2 Case Lid Galvanized sheet metal 3 Grommet C30 SG20A 4 Grommet C30 SG20A 5 Grommet for Power Supply C30 SG20A Mounting Holes Top Side Bottom Side ...

Страница 7: ...7 EN Owners Manual Touch Screen Controller Touch Screen Controller ...

Страница 8: ...window weekly or daily schedule up to 12 events per day Fire alarm indication and fault alarms will be shown in the two boxes circled Settings tab used for commissioning and setup Active fault display and fault code history list Overview screen shows overall status of the building and summary view of the indoor units Return to main menu Home Screen ...

Страница 9: ...hod is used when more advanced building control is required Quick Start The quick start commissioning option reduces the amount of time required to commissions the TCB TSC640 PY Touch screen The quick start uses an Autoscan feature that will scan the network and address all of the connected IDU s The quick start commissioning method is explained below Commissioning Quick start 1 Power on unit ente...

Страница 10: ...10 EN Owners Manual Touch Screen Controller 2 Set date and time under the correct tab If used enabled also set the first and last day of Summertime 3 In the Settings tab select Administrator ...

Страница 11: ...matically addressed Please note that when completing an auto scan it will clear all existing addressing information 5 The pop up screen shown below will appear with the message Autoscan network This cannot be undone If ready please select scan The Touch screen will then begin searching for indoor units Note Please ensure the outdoor and indoor units are fully powered and addressed before running t...

Страница 12: ...uring the scan will be displayed Select OK on pop up box displayed Please note the Autoscan only detects units on gateways 1 2 If more gateways are used please refer to section 5 Setup for remaining gateways Note Only one gateway is supplied with the TCB TSC640 PY 7 The Quick Start method is now complete ...

Страница 13: ...ures are as follows Time Date This tab allows you to set the current date and time It is also where you set up the first and last day of Summertime for schedule operations The Summertime can be enabled as shown in the image above When this is disabled the box will be blank The Green status light will illuminate if the Summertime operation is active ...

Страница 14: ...erarchy is used for the advanced setup procedure These screens are explained below Unit Config The Unit Config screen is required when commissioning the touch screen for a more advanced setup then the Autoscan Once you have selected the Unit Config button you will see the screen below As you can see the screen lists the ID Gateway Address Unit name Type and customise option ID is the order the ind...

Страница 15: ...pose interface GPIF this must also be selected in this screen You can also remove any units using this screen Once the Type is selected you must press the Customize button Once you have pressed this button you will see the screen as shown below As you can see this is where you set the Gateway address 1 4 and the address of the individual indoor unit This screen is also where you can apply the set ...

Страница 16: ...ns an indoor unit can control Factory restrictions are based on the type of indoor unit you selected please ensure you select the correct indoor unit in the type screen In the Names Zones Hierarchy tab this is where you enter a unit name If using the Autoscan the unit name is automatically set to match the ID number For example ID 1 is Unit 1 If entering the unit name for advanced setup the the ma...

Страница 17: ...is screen is where you apply indoor units to the levels you have created To enter a level select the blue box under level and scroll through names To enter the indoor units to this level select the far right column and the unit names entered in the Unit Config screen will be shown Once you have entered a unit in to a level it will no longer be available in the drop down menu for level 4 ...

Страница 18: ...terlock tab the screen below will be displayed This screen will list the Interlocks once they have been created The interlocks can be enabled and disabled in this screen using the section box beside the interlock name To create an interlock and to give it a name select one of the white boxes listed You can create up to 20 GPIF interlocks The purpose In this window you can create up to 10 separate ...

Страница 19: ...ntroller This Screen in the GPIF interlocks tab is the Interlock write setup for indoor units You have the same level as control as the master control screen The Screen below is the interlock write setup for Digital and analogue outputs ...

Страница 20: ... to be 0 5 C or 1 C 0 5 C will only work if the remote controller supports this The screen saver time is in minutes If you wish to have no screen saver timeout set to 0 to disable this feature Beep on key press As standard the beep on key press will be on from factory you can enable or disable the feature using this selection box on the touch screen The languages that are available for the TCB TSC...

Страница 21: ... the fire alarm input signal is normally closed the fire alarm panel will break this circuit to trigger the fire alarm input This will switch off all indoor units and apply a central on off lock Selecting the Firestop invert input signal option inverts this so the fire alarm input is normally open and closed when a fire alarm signal is received from the fire alarm panel Once selected a green tick ...

Страница 22: ...een Please be aware the Autoscan identities unit types and not specific models for example 1WC will be identified as 4WC If required you can correct model type after the Autoscan is complete Once you have initiated the Autoscan this cannot be undone and all previous addressing will be overwritten If there have been any changes on the TCC link network please reboot the PY gateway and wait 5 minutes...

Страница 23: ...or presses a Tab or Function that they do not have access to then a popup window or alternative screen will ask for the password PIN Correct password PIN entry allows then access but after inactivity delay of 5 minutes the current access level reverts back to User Once you have entered a user level this level will be displayed in the top left hand corner of the display screen To log out of any lev...

Страница 24: ...he warning message that will appear once the factory rest has been selected Once selected it cannot be undone The factory reset default settings are as follows Factory Default Settings Passwords USER empty POWER USER empty ADMINISTRATOR 8888 Password mode 4 digit PIN Settings page 1 SUMMERTIME disabled Start of summertime 00 00 End of summertime 00 00 Settings page 2 Clear zones Clear level names ...

Страница 25: ...Disabled Firestop Invert signal OFF Firestop auto restart OFF Display AUTO modes OFF Screen brightness MAX 32 CLEAR MEMORY AREAS Schedules Alarm History MISCELLANEOUS Reset filter selections to none Clear filter selection display boxes Erase Alarm History Another option in the administrator tab is the possibility to erase alarm history This will clear all active past and present alarms Once the Al...

Страница 26: ...d once to enable the lock and twice to unlock When locked a padlock will be displayed in the selection box When unlocked the selection box will be clear but have a bold white border You can control units individually or in levels zones The QTY of units that are available to control is listed in the bottom left hand corner of touch screen Once you have created the command to send to indoor units pr...

Страница 27: ...tered selection on the screen Quantity of units QTY of units as displayed in the left hand side of the touch screen is to show the amount of indoor units available to control ID A unique ID is provided to each indoor unit The ID number is based on the information added in the settings unit config screen If Autoscan is used the ID number is the number given based on the order of units found Unit na...

Страница 28: ... in the direct control screen The set point can be in increments of 0 5 or 1 To set increments enter the settings display operation tab Room Temperature The Room Temperature is displayed on the direct control home screen Comms Envelope Each time a write command is sent to the touch screen a comms envelope with green sending arrow will be displayed on the top bar of the touch screen Once the comman...

Страница 29: ...e box next to the schedule name Once the schedule has been enabled a green tick will appear in the selection box Please allow sufficient time for the trigger schedule to be completed This may take several minutes depending on complexity of schedule and amount of indoor units If this is not obeyed the later schedule will overwrite any incomplete schedules Please allow sufficient time for trigger sc...

Страница 30: ...winter The dates made for summertime and winter are created in the settings date time tab 4 Summer Winter The bottom left hand side of the image above is also where you can set the schedule to operate in summer or winter The dates made for summertime and winter are created in the settings date time tab If not set the schedules will run all year 5 Trigger No The trigger No is where create each even...

Страница 31: ... take you to the screen displayed below 1 The overview screen will display the amount of units that are on or off the amount of indoor units that are in heat cool or fan only and how many units that are currently in alarm 2 As well as providing a general overview for all IDUs There is also the capability to send global control commands on the left hand side of the screen From here you can turn ALL...

Страница 32: ... units at one time The overview will show the unit ID Power status Mode status Fan status and Room temperature 2 The Indoor units can be filtered by Zone and levels this information will be based on the information entered in the settings menu 3 The detailed building overview screen has the capability to send global control commands If the indoor units have been filtered so you are looking at a ce...

Страница 33: ... touch screen will show the ID Address of gateway and IDU and also the unit name If you are aware of the fault you can acknowledge the alarm This will then stop the alarm signal from flashing in the control screen however this will stay in active alarm until the fault is cleared Once the fault has cleared it will only be displayed in the alarm history screen The active alarm screen can display up ...

Страница 34: ...When the Alarm History log is full it will begin to overwrite the oldest alarms The Alarm History screen will display the date and time that an alarm occurs and the data and time that it is cleared It will list the ID Address and unit name The Alarm Code and description of alarm will be displayed beneath the occurred date on the left hand side of the touch screen ...

Страница 35: ...y according to the following points 1 During the daily cleaning please use a dry soft cloth But if you use the dry soft cloth please take care if you are too forceful trying to remove the dirt the front panel may be damaged In this case use a wet cloth to clean in advance 2 When the dirt cannot be cleaned by dry cleaning please dip the cloth into the diluted neutral washing agents concentration of...

Страница 36: ...mmunication error exists in either the Active Alarm or Alarm History List of the Touch Screen Controller 2 Check correct communication with Indoor Units When there is communication trouble between the Touch Screen Controller and an Indoor Unit an error message will be created This message will be stored in Active alarm and if cleared will then be displayed in the Alarm History List To ensure corre...