Central Remote Controller
Installation Manual
20
-EN
Address Display
The indoor units registered in the unit are displayed.
Address Auto-setting
The Central control address of the connected indoor units is automatically set from 1 in ascending order of the line address-
indoor address.
IMPORTANT
All currently set Central control addresses are overwritten.
NOTE
• At initial startup or when "Zone Settings" is not set, when "Obtain Address" is performed, the connected indoor units are set
to "ZONE-1" up to 64 units in ascending order of line address. The 65th and subsequent units are not set. If you wish to
monitor and control 65 or more units, use another Central Remote Controller to perform "Zone Settings".
• If you change the address from the local remote controller or register the wrong Central control address in the Central
Remote Controller, normal operation will not be possible. Perform "Obtain Address" again.
• Devices that set the Central control address with DIPSW cannot change the Central control address from the Central
Remote Controller. Configure the settings beforehand so that they do not overlap with other devices.
1
Select "Address Display" on the "Address Settings"
screen and press [ ] (Confirm)
The "Address Display" confirmation screen appears.
2
Press [
˄
] and [
˅
] to select "Yes", then press [ ]
(Confirm)
The "Address Display" screen appears.
• Press [
˄
] and [
˅
] to switch pages.
1
Select "Address Auto-setting" on the "Address
Settings" screen and press [ ] (Confirm)
The "Address Auto-setting" confirmation screen appears.
2
Press [
˄
] and [
˅
] to select "Yes", then press [ ]
(Confirm)
The display shifts from "Registering the address...
" to "Address
Settings
", and the process is complete when the "Servicing Menu"
screen appears.
• This operation will take several minutes.
Содержание TCB-SC640U-E