DK424 Installation
Reserve Power Installation
5-36
Strata DK I&M 6/00
CAB 2
CAB 3
CAB 4
CAB 5
CAB 6
CAB 1
RPSB1A
RPSB1A
RPSU280A
RPSU280A
AC IN
AC IN
RPSU280A
AC IN
RPSU280A
AC IN
RPSU280A
AC IN
RPSU280A
MBJU
(see Note below)
Jumper Unit
AC IN
FG
FG
FG
FG
FG
FG
2043
Frame Ground
Screw (FG)
Data Cables
115VAC ± 10VAC (50/60 Hz)
(11.5 Amp max)
Insulated
Ground
Wire “B”
Earth Ground:
Cold Water Pipe
Or Ground Rod
AWG #6 Wire
Maximum
Length: 60 Feet
Per General Rules of Article 250 Of
The National Electric Code,
NFPA70
ONEAC 6-AP
or 6-DP
Solid State
Secondary
Protectors
Third Wire
AC Ground
Building Main Power
Panel Electrical Ground
“A”
115VAC ±10VAC (50/60 Hz)
Dedicated 15 Amp
Branch Circuit
Third Wire Ground
to AC Power
AC Cable
Intercabinet Power
Supply Ground Wire
Figure 5-21 AC Power Distribution for Six Cabinets
Important!
Remove MBJU only when RCTUE/F is installed.
Содержание Strata AirLink DK40i
Страница 22: ...Introduction Related Documents Media xx Strata DK I M 6 00 ...
Страница 48: ...DK14 Installation DK14 Wiring Diagrams 1 26 Strata DK I M 6 00 ...
Страница 220: ...DK424 Installation Remote Cabinet Installation Instructions 5 68 Strata DK I M 6 00 ...
Страница 262: ...DK424i Configuration Primary Reserve Power Cabinet Hardware 6 42 Strata DK I M 6 00 ...
Страница 450: ...Universal Slot PCB Wiring Option Interface PCB Wiring Diagrams 10 42 Strata DK I M 6 00 ...
Страница 592: ...Peripheral Installation Enhanced 911 Service E911 12 84 Strata DK I M 6 00 ...
Страница 616: ...ACD Installation Spectrum Electronic Wall Boards 13 24 Strata DK I M 6 00 ...
Страница 634: ...Fault Finding Fault Isolation Flowcharts 14 18 Strata DK I M 6 00 ...
Страница 704: ...ISDN Interfaces ISDN Disconnect Cause Code 16 54 Strata DK I M 6 00 ...