INSTALLATION MANUAL

SUPER MODULAR MULTI SYSTEM AIR CONDITIONER
T-shape branching joints (For R410A)

Model name: RBM-BT14UL, RBM-BT24UL

EH98605001-2

Please read and follow the "PRECAUTIONS FOR SAFETY" in the installation manual for the air conditioner. 
• Make sure all the parts listed in the table are included in the package. 
• Read the installation manual for the air conditioner regarding the selection of the size and material of the refrigerant pipes. 
• Ask an authorized dealer or qualified installation professional to install this product. 
• Installation work must be carried out by following this installation manual and using exclusive tools and pipes for the refrigerant R410A. 

1

English

Thank you for purchasing the “Branching 

Joint” for TOSHIBA Carrier Air 

Conditioner. Before starting the 

installation work, please read this manual 

carefully and install the product properly.

Parts Table

NOTE

1 ( ): indicates outer diameter.
2 For the sockets, the side with a notch is the one to connect a pipe. (

,

,

 : without notch)

Unit: inch

[Unit: mm]

 

Gas side joint 

Liquid side joint 

Balance pipe joint 

RBM-

BT14UL

Socket 

No. Specifications 

No. Specifications 

No. Specifications 

No. Specifications 

Ø1 3/8"×(Ø1 1/4")
[Ø 34.9×(Ø31.8)]

1 pc 

(Ø1 1/8")×Ø7/8"
[(Ø 28.6)×Ø22.2]

2 pcs 

Ø5/8"×(Ø3/4")
[Ø 15.9×(Ø19.1)]

1 pc 

(Ø3/4")×Ø1/2"
[(Ø19.1)×Ø12.7]

2 pcs 

Ø1 1/8"×(Ø1 1/4") 
[Ø 28.6×(Ø31.8)]

1 pc 

Joint Joint 

pc 

L-pipe (Ø1")×Ø1 1/8"

[(Ø 25.4)×Ø28.6]

1 pc 

T-joint 3-Ø3/4" 

[3-Ø19.1]

1 pc 

Heat 
insulator

Heat insulator for joint 

1 pc  Heat insulator for L-pipe 

1 pc  Locally procured 

RBM-

BT24UL

Socket 

No. Specifications 

No. Specifications 

No. Specifications 

No. Specifications 

Ø1 5/8"×(Ø1 1/2")
[Ø41.3×(Ø38.1)]

1 pc 

(Ø1 1/2")×Ø1 5/8"
[(Ø38.1)×Ø41.3]

1 pc 

Ø3/4"×(Ø7/8")
[Ø19.1×(Ø22.2)]

1 pc 

(Ø7/8")×Ø3/4"
[(Ø22.2)×Ø19.1]

1 pc 

Ø1 3/8"×(Ø1 1/2")
[Ø34.9×(Ø38.1)]

1 pc 

(Ø1 1/2")×Ø1 3/8"
[(Ø38.1)×Ø34.9]

1 pc 

(Ø7/8")×Ø5/8"
[(Ø22.2)×Ø15.9]

2 pcs 

(Ø1 1/2")×Ø1 1/8" 
[(Ø38.1)×Ø28.6]

1 pc 

(Ø7/8")×Ø1/2"
[(Ø22.2)×Ø12.7]

1 pc 

(Ø1 1/2")×Ø7/8"
[(Ø38.1)×Ø22.2]

1 pc 

(Ø1 1/8")×Ø7/8"
[(Ø28.6)×Ø22.2]

1 pc 

Joint Joint 

pc 

L-pipe (Ø1 1/4")×Ø1 1/8"

[(Ø31.8)×Ø28.6]

1 pc 

T-joint 3-Ø7/8" 

[3-Ø22.2]

1 pc 

T-joint 3-Ø3/8"

[3-Ø9.5]

1 pc 

Heat 
insulator 

Heat insulator for joint 

1 pc  Heat insulator for L-pipe 

1 pc  Locally procured 

Locally procured 

59 61

62

Diameter of the 

connecting pipe

External 

diameter of 

socket

Socket

Notch

Ø1 1/8"

Ø7/8"

L-pipe 

(Ø1 1/4")

(Ø1 1/8")

Ø1 1/8"

(Ø1 1/8")

Ø7/8"

(Ø1 1/4")

Ø1 3/8"

Ø1 1/4"

Ø1 1/8"

(Brazed locally) (Ø1")

27

59

43

43

(Ø3/4")

Ø1/2"

Ø1/2"

Ø5/8"

(Ø3/4")

3-Ø3/4"

(Ø3/4")

13

10

10

59

43

13

10

27

(Ø1 1/2")

L-pipe 

Ø7/8"

(Ø1 1/8")

Ø1 1/2"

Ø1 5/8"

Ø1 1/8"

73

Ø1 3/8"

(Ø1 1/2")

Ø1 1/2"

(Brazed locally) (Ø1 1/8")

(Ø1 1/2")

Ø1 5/8" Ø1 3/8" Ø1 1/8"

Ø7/8"

71

61

62

43

61

62

(Ø1 1/2") (Ø1 1/2") (Ø1 1/2")

Ø3/4"

Ø5/8"

Ø3/4"

3-Ø7/8"

(Ø7/8")

18

14

Ø1/2"

(Ø7/8")

(Ø7/8")

(Ø7/8")

(Ø7/8")

18

85

14

Ø5/8"

3-Ø3/8"

62

62

18

18

61

61

14

71

85

73

43

Installation and connection

Select the model and the number of outdoor unit connection piping kits that you need based on the sales catalog, design engineering, and the 
data book and installation manual of outdoor unit. 

CAUTION

• When brazing the refrigerant pipes, be sure to put the nitrogen first to prevent from oxidizing the inner pipe. If not, the oxidization scale 

brings the refrigerant cycle clogging and result in malfunction.

• Use clean new pipes for the refrigerant pipes, and do not let water, moisture or dust get into the pipes during installation. 

1

Installation mode

<Gas joint>

Install them horizontally with a maximum gradient of ±15° for even distribution. 

(Do not install them perpendicularly or upright.) 

(Figure 4, Figure 5, Figure 6, Figure 7)

 

<Liquid/balance pipe joint> 

No restrictions on the installation orientation by the direction of refrigerant flow. However, on the liquid joint the installation cannot have the 
refrigerant from the main pipe flow directly into the header unit. (

Figure 2

). 

Liquid pipes 

Figure 1 

Figure 2 

Gas pipes 

Figure 3 

<Gas joint reverse orientation installation> 

Figure 4 

<Gas joint upright orientation installation> 

Figure 5 

<Vertical installation> 

Figure 6 

<Vertical installation> 

Figure 7 

A

B

Horizontal line

Within ±15°

A view

Horizontal line

B view

Within ±15°

A

Horizontal line

Horizontal line

A view

A view

Header unit A 

Follower unit B 

Follower unit C 

Main pipe 

To indoor unit 

Liquid joint

Extension valve installation site

(For planned system expansion)

Correct

Header unit A 

Follower unit B 

Follower unit C 

To indoor unit 

Main pipe 

Incorrect

Header unit A  Follower unit B  Follower unit C 

Main pipe 

Gas joint 

To indoor unit 

Extension valve installation site

(For planned system expansion)

Correct

Header unit A  Follower unit B  Follower unit C 

Main pipe 

Gas joint 

To indoor unit 

Incorrect

Gas joint 

Header unit A 

Follower unit B 

Main pipe 

Gas joint 

To indoor unit 

A view

Gas joint 

Incorrect

Unit 

Vartical line

Header unit A 

Gas joint

Incorrect

Header unit A 

Gas joint

Incorrect