Toshiba RBC-U33P-E Скачать руководство пользователя страница 6

- 6 -

Installation of air inlet grille

•  Install the air inlet grille in the reverse procedure of the removal.
•  Be sure not to pinch the louver motor wiring to install the air inlet grille.
•  Attach a Safety strap hook of the air inlet grille to the ceiling panel.

Hook hole of 
ceiling panel

Safety strap hook

3. Louver operation set up

REQUIREMENT

•  Use the wired remote controller to change the setting.
•  The setting cannot be changed using the wireless remote controller, sub remote controller, or remote-controller-less system 

(for central remote controller only). Therefore, installs the wired remote controller to change the settings.

 

CAUTION

Set only the CODE No. shown in the following table: DO NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible to operate the air conditioner or other trouble with the product may 
result.

1.  Turn the power on.
2.  Push and hold   +   +   buttons simultaneously for 4 seconds or more. After a while the display flashes.
 

Confirm that CODE No. is [10]. Also, the fan of the selected unit runs and the louvers start swing.

• 

If the CODE No. is not [10], push   button to clear the display content, and repeat the procedure from the beginning

3.  Select an indoor unit to be set by pushing 

 button (Left side of the button). Indoor unit No. changes each time the 

button is pushed.

4.  Change the CODE No. to [47] with 

 buttons.

5.  Set the (SET DATA) like as the following table with 

TIME

 buttons.

6. Push   button. The display state changes from flashing to lighting, and the setting is fixed.
7.  Continue set the CODE No. [48] ~ [4E] like as the table with repeat procedure (4) - (6).

• 

To change setting of another indoor unit, repeat from procedure (3)

8.  When settings have been complete, push   button to determine the settings.

• 

When   button is pushed, 

 

flashes and then the display content disappears and the air conditioner enters the 

normal stop mode. (While 

 

 

 is flashing, no operation of the remote controller is accepted.)

CODE No.

SET DATA

47

0024

48

0024

49

0030

4A

0035

4B

0040

4C

0043

4D

0046

4E

0060

4 8 6 2

5 3

<RBC-AMT32E>

Содержание RBC-U33P-E

Страница 1: ...injury Electrical work must be performed by a qualified electrician in accordance with the Installation Manual Make sure the air conditioner uses an exclusive power supply The capacity shortage of the power circuit or improper electrical work may result in electric shock or fire Connect the specified wires firmly and clamp them securely so that external force applied to the wires does not affect t...

Страница 2: ...t 12 mm to 17 mm Failure to do so cause the malfunction or other damages Indoor unit Ceiling opening size Ceiling board Installation gauge Indoor unit accessory 12 to 17 Unit mm Heat insulator CAUTION Do not remove the heat insulators A heat insulator on the corner of rear side of the panel are for dew protection Do not remove the heat insulators because removing them causes dew drop or water leak...

Страница 3: ...ew Ceiling panel Louver motor wires Tentative hanging hook Engraved mark REF PIPE Square hole of an indoor unit Push to remove Tentative hanging hook 2 Lift the corner of the frame in a panel Fig 5 slide the panel fixed implement bracket in the direction of the arrow so that the panel fixed screw head comes to the specified position on the bracket Fig 6 Do the same for all four corners Slide the b...

Страница 4: ... loosen the screw B Slide the cover inside so that the hook part can be removed The electrical control box cover remain being hooked on the hinge Screw A Screw B Hook part Hinge Electric control box cover 2 Pass the louver motor wire from the ceiling panel through the clamper as shown in figure then connect them to the 20P connector CN510 White on the PC board of the indoor unit Check the cables a...

Страница 5: ...ss remote controller kit or the Occupancy sensor The Wireless remote controller kit or the Occupancy sensor separate sold parts Only this position can be installed 4 direction free Electrical control box Indoor unit drain pipe side Position of hook for air inlet grill at factory default Indoor unit refrigerant pipe side Installation of adjust corner cap Push claw A two positions and claw B three p...

Страница 6: ... for 4 seconds or more After a while the display flashes Confirm that CODE No is 10 Also the fan of the selected unit runs and the louvers start swing If the CODE No is not 10 push button to clear the display content and repeat the procedure from the beginning 3 Select an indoor unit to be set by pushing button Left side of the button Indoor unit No changes each time the button is pushed 4 Change ...

Страница 7: ...hed to the wireless remote controller kit sold separately For Air purifier kit For details of installation refer to the Installation Manual attached to Air purifier kit sold separately For Occupancy sensor kit For details of installation refer to the Installation Manual attached to Occupancy sensor kit sold separately This product Occupancy sensor kit cannot be used together with the wireless remo...