Toshiba RBC-MTSC1 Скачать руководство пользователя страница 1

RBC-MTSC1 
Installation Manual

Mini Touch Screen Controller

RBC-MTSC1 v0,12 2019

Содержание RBC-MTSC1

Страница 1: ...RBC MTSC1 Installation Manual Mini Touch Screen Controller RBC MTSC1 v0 12 2019 ...

Страница 2: ...1 Fixing Frame 7 6 User Interface 8 6 1 Start Up 8 6 2 Ready 8 6 3 Default View 9 6 4 Configuration 9 6 4 1 Configuration Menu Icons 10 6 4 2 General R C Setup 10 6 4 3 User interface setup 11 6 4 4 DN code editing 11 6 4 5 Appearance 13 6 4 6 Occupancy Strategy 13 6 4 7 Diagnostics 17 6 4 8 Model information 18 6 4 9 Reboot button 18 6 4 10 Back button 18 6 5 Version History and New Features Guid...

Страница 3: ...servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burned when removing this panel CAUTION High temperature parts You might get burned when removing this panel CAUTION Do not touch the aluminium fins of the unit Doing so may result in injury CAUTION Do not touch the aluminium fins of the unit Doing ...

Страница 4: ...REQUIREMENT For power supply wiring strictly conform to the Local Regulation in each country For wiring of power supply of the outdoor units follow the Installation Manual of each outdoor unit Perform the electric wiring so that it does not come to contact with the high temperature part of the pipe The coating may melt resulting in an accident After connecting wires to the terminal blocks provide ...

Страница 5: ... codes Set central addresses Leak detection warning symbols to complement the current Toshiba solution Text inputs for instructions example Error contact reception tel 1234 Use CN61 connection to set back for energy saving for un occupied space MAIN FUNCTIONS FUNCTION COMMAND INPUT STATUS OUTPUT ON OFF Status Operation Mode Auto Heat Cool Dry Fan Only Fan Speed Stop Auto Ultra low Low Medium High ...

Страница 6: ... Mini Touch Screen Controller is powered on connection to the indoor unit A B terminals 4 2 USB The USB interface located behind the cover plate is used for configuration via a PC and for upgrading the firmware Ensure that the correct USB driver has been installed prior to connecting the Mini Touch Screen Controller to a PC 4 3 Firmware Updates IMPORTANT NOTICE Please check our website on a regula...

Страница 7: ...RBC MTSC1 Mini Touch Screen Controller Installation Owners Manual 7 5 Dimensions 5 1 Fixing Frame 15 mm 74 mm 141 mm Fixing holes Cable entry ...

Страница 8: ...RBC MTSC1 Mini Touch Screen Controller Installation Owners Manual 8 6 User Interface 6 1 Start Up Initialising start up display screen 6 2 Ready After initialisation the controller is ready to switch on ...

Страница 9: ...ing two fingers Press and hold the bottom right hand corner of the screen keeping your finger in place do not remove and then press and hold the bottom left hand corner of the screen Now keeping your finger on the left hand corner of the screen do not remove release your right hand finger and tap the bottom right hand corner of the screen four times with your finger Executed correctly will reveal ...

Страница 10: ...on Menu Icons 1 General R C setup 2 User interface setup 3 DN code editing 4 Appearance 5 Occupancy strategy 6 Not assigned or used 7 Diagnostics 8 Model information 9 Reboot button 10 Back button 6 4 2 General R C Setup Enable or disable header unit show setpoint to 0 or 1 decimal place ...

Страница 11: ...perating mode temperature change fan speed louvre operation Tap button to change setting 6 4 4 DN code editing To change DN code settings use up down arrow to move between DN codes To change data settings use up down arrow to change value To enable changes press green Send button To exit DN code use blue Back button ...

Страница 12: ...ller Installation Owners Manual 12 Reboot button is visible when configuration setting has changed and requires the indoor unit to be restarted to accept the command To save settings press Reboot button displayed on Configuration screen ...

Страница 13: ...ouch paint board to reveal RGB colour sliders 6 4 6 Occupancy Strategy Enable or disable temperature setting limits for cooling and heating Tap button to change setting Use slider to set minimum and maximum temperature conditions Enable or disable on off mode temperature adjustment fan speed louvre operation Tap button to change setting ...

Страница 14: ... Mini Touch Screen Controller Installation Owners Manual 14 Enable or disable on off button Enable or disable to fix mode Enable or disable temperature change To change setpoint use up down arrow to change value ...

Страница 15: ...RBC MTSC1 Mini Touch Screen Controller Installation Owners Manual 15 Enable or disable to fix fan speed Enable or disable louvre operation Tap to select fixed louvre position or set auto swing ...

Страница 16: ...g Enable or disable activity mode settings Disable prevents selection of activity mode Low fan speed Cooling mode Auto mode Medium fan speed Heating mode Temperature setting High fan speed Fan only mode Louvre operation Auto fan speed Dry mode On Off Minimum and maximum temperature setting Disable activity ...

Страница 17: ...n Controller Installation Owners Manual 17 6 4 7 Diagnostics Warning symbol on display indicates fault code To access diagnostics refer to 6 4 Configuration page 9 Displays error message Tap air conditioner to reveal error codes ...

Страница 18: ...tion Owners Manual 18 6 4 8 Model information 6 4 9 Reboot button Tap to save and update settings 6 4 10 Back button Tap to exit and return to previous screen 6 5 Version History and New Features Guide 6 5 1 Version Information v0 12 initial release ...

Страница 19: ...ion error between indoor header and follower units E19 Outdoor header units quantity error E20 Other line connected during automatic address E23 Sending error in communication between outdoor units E25 Duplicated follower outdoor address E26 Decrease of No of connected outdoor units E28 Follower outdoor unit error E31 IPDU communication error F01 Indoor TCJ sensor error F02 Indoor TC2 sensor error...

Страница 20: ...sses L28 Maximum number of outdoor units exceeded L29 No of IPDU error L30 Auxiliary interlock in indoor unit L31 IC error P01 Indoor fan motor error P03 Discharge temp TD1 error P04 High pressure switch detection error P05 Phase missing detection Phase order error P07 Heat sink overheat error P10 Indoor overflow error P12 Indoor fan motor error P13 Outdoor liquid back detection error P15 Gas leak...

Страница 21: ...RBC MTSC1 Mini Touch Screen Controller Installation Owners Manual 21 ...

Страница 22: ...port toshiba ac com Plymouth Toshiba Carrier UK Limited Porsham Close Belliver Industrial Estate Plymouth Devon PL6 7DB Tel 0870 843 0333 sales support toshiba ac com Departmental Contact Details Sales 0845 850 8924 sales support toshiba ac com Projects 01372 220 266 projects uk toshiba ac com Spares 0870 843 0333 opt 3 spares toshiba ac com Warranty 0870 843 0333 opt 6 warranty toshiba ac com Tra...

Отзывы: