– 20 –

EN

Installation Manual

6

Field setting menu

1. Test mode

Set for the test operation after installation.

Before the test mode

• Perform the followings before turning on the power:

1) By using 500 V-megger, check that resistance of 1 M

 or more exists between the terminal block of the 

power supply and the earth (earthing).
If resistance of less than 1 M

 is detected, do not run the unit.

2) Check all valve of the outdoor unit is opened fully.

• To protect the compressor at the time of startup, leave the power on for 12 hours or more before operation.
• Do not press the electromagnetic contactor to forcibly perform the test mode. (It is very dangerous because the 

protective device does not work.)

• Peel off the protective sheet affixed when the remote controller was shipped before performing a test run.

Performing the test mode

For the procedure of the operation, refer to the supplied Owner’s Manual. A forced test mode can be performed 
according to the following procedure when the room temperature rises / falls enough for the thermostat to turn off. 
In order to prevent a continuous operation, the forced test operation is released after 60 minutes have passed and 
returns to the normal operation.

1

Push the [

 

MENU] button to display the 

menu screen.

2

Push and hold the [

 

MENU] button and 

the [

 

] button at the same time to 

display the “Field setting menu”.

Push and hold the buttons for more than 4 
seconds.

3

Push the [

 

 CANCEL] button to return.

Item

Function

1. Test mode

Settings for when performing the test operation after installation

2. Register service info.

Registration of information about the contact number for service, model name and 

serial number of the indoor unit and outdoor unit

3. Alarm history

List of latest 10 alarm data: information of check code, date, time, and unit

4. Monitor function

Monitoring data of sensor temperature, rotating speed of the compressor or other 

factor.

5. Setting louver position

Change the louver indication setting to match the indoor unit type.

6. FC setting

Advanced settings using Function code

1.Test mode

2.Register service info.
3.Alarm history
4.Monitor function
5.Setting louver position

Field setting menu(1/2)

Return

Set

Содержание RB-RWS21-E

Страница 1: ... manual before using the RB RWS21 E remote controller Refer to the Installation Manual supplied with the indoor unit for any installation instructions other than operations of the remote controller Wired Remote Controller Installation Manual ...

Страница 2: ...for installing two remote controllers 7 Note 8 4 Part Names and Functions 9 Monitor screen 10 5 Initial setting 11 1 Clock 11 2 Name of room 12 3 Screen contrast 13 4 Backlight 14 5 Key lock 15 6 Header Follower 16 7 Language 17 8 Press hold 4sec 18 9 Clock display 19 6 Field setting menu 20 1 Test mode 20 2 Register service info 22 3 Alarm history 26 4 Monitor function 27 5 Setting louver positio...

Страница 3: ...burns electric shock and other injuries which do not require hospitalization or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indi...

Страница 4: ... 3 Installation Manual 2 Accessory Parts No Part name Quantity 1 Screws M4 x 20 2 2 Wood screws M3 8 x 16 2 3 Owner s Manual 1 4 Installation Manual This manual 1 5 CD ROM 1 ...

Страница 5: ...xposed to direct sunlight or direct outside air such as the side of a window Do not install the remote controller in a place behind something or to the rear side of an object where air flow is not sufficient Do not install the remote controller in a freezing box or refrigerator as the remote controller is not waterproof Install the remote controller vertically to the wall Installation dimension Ro...

Страница 6: ...llers To install two or more adjacent remote controllers follow the instructions in the Fig 1 and 2 Wiring type VCTF 0 5 mm2 to 2 0 mm2 x 2 Total length of remote control wiring and inter wiring between remote controllers L L1 1 remote controller 2 remote controllers Up to 500 m Up to 300 m Indoor unit Remote control wiring L Remote controller Remote controller L1 Wall 33 mm or more from a wall 20...

Страница 7: ... screws 2 pieces supplied with the remote controller to attach the rear case of the remote controller to the wall Do not use an electrical screwdriver Do not over tighten the screw Tightening torque is up to 2 kg f cm otherwise the rear case may be damaged 3 Connect the electrical wire from the indoor unit to the terminal block of remote controller Refer to Wire the remote controller Check the ter...

Страница 8: ...et from 6 Header Follower in Initial setting on the MENU screen For details refer to the page 16 Install the remote controllers For the dual remote controller system install the remote controllers as follows Set one remote controller as the Header remote controller The remote controllers are set as Header remote controller as factory default Remote control wiring procured locally Terminal block fo...

Страница 9: ...ttings of the test operation refer to the page 20 To diverge from the indoor unit To diverge from the Header remote controller Remote control wiring Locally procured 0 5 mm2 to 2 0 mm2 Remotecontroller Header Remote controller Follower Sold separately Terminal block for the remote control wiring Earth Indoor unit A B A B A B Remote control wiring Locally procured 0 5 mm2 to 2 0 mm2 Remotecontrolle...

Страница 10: ...On the menu screen selects a menu item 4 MENU button Displays the menu screen 5 F1 button Varies its function according to the setting screen 6 F2 button Varies its function according to the setting screen 7 CANCEL button Functions as indicated on the screen such as returning to the previous menu screen 8 MONITOR button Displays the monitoring screen 8 4 7 6 1 2 3 5 Room A 12 00 Mode Fan Speed Coo...

Страница 11: ...er of the indoor unit is not set 1 Push MONITOR button The monitor screen appears 2 Push CANCEL button to return 1 Displays the set temperature 2 Displays the temperature measured by the room temperature sensor of the indoor unit If the sensor is set to that of the remote controller the temperature measured by the remote sensor is displayed 3 Displays the temperature around the vent of the outdoor...

Страница 12: ...ayed 5 Push the CANCEL button to return The screen returns to the Initial setting screen 1 Push the button to select 1 Clock on the Initial setting screen then push the Set F2 button 2 Push the button to select the Year Month Day and time Push the F1 F2 button to set the value 3 Push the MENU button Initial setting 1 2 1 Clock 2 Name of room 3 Screen contrast 4 Backlight 5 Key lock Set Return Set ...

Страница 13: ...other cause NOTE The available date range is from January 1st 2018 to December 31st 2099 1 Push the button to select 2 Name of room on the Initial setting screen then push the Set F2 button 2 Set the name of the remote controller Enter the characters of the name in the screen 1 Move the cursor to select the character with the button and F1 F2 button the selected character is highlighted then push ...

Страница 14: ...setting screen then push the Set F2 button 2 Push the F1 F2 button to adjust 3 Push the MENU button The screen returns to the Initial setting screen Return Set Fix ABCDE FGH I J KLMNO PQRST UVWXY Z abcde f g h i j klmno p q r s t uvwxy z 12345 67890 Bedroo Del Return Set Del ABCDE FGH I J KLMNO PQRST UVWXY Z abcde f g h i j klmno p q r s t uvwxy z 12345 67890 705A Fix Initial setting 1 2 1 Clock 2...

Страница 15: ...sh the MENU button When ON is selected the back light is turned on during operating with the remote controller When OFF is selected the back light is not turned on NOTE The back light of the LCD is turned on as factory default The back light is on for a predetermined time after button operation Initial setting 1 2 1 Clock 2 Name of room 3 Screen contrast 4 Backlight 5 Key lock Set Return Set Backl...

Страница 16: ...ock 4 Push the MENU button When Lock is selected the key cannot be used during key lock When Unlock is selected the key can be used even during key lock All keys are unlocked while Check is displayed For the key lock setting refer to the owner s manual The factory default is Lock Initial setting 1 2 1 Clock 2 Name of room 3 Screen contrast 4 Backlight 5 Key lock Set Return Set ON OFF Set temp Lock...

Страница 17: ...In the dual remote controller system the latter operation overrides the former The remote controller is set as Header remote controller as factory default If the Header Follower remote controller settings are not set correctly the 30 or 32 check code is displayed 1 Push the button to select 6 Header Follower on the Initial setting screen then push the Set F2 button 2 Push the button to select the ...

Страница 18: ...utton 2 Push the button to select a language 3 Push the MENU button The screen text changes to the selected language The factory default is English Initial setting 2 2 6 Header Follower 7 Language 8 Press hold 4 sec 9 Clock display Set Return Language 1 2 English French Français German Deutsch Return Fix Italian Russian Language 2 2 Dutch Return Fix Nederlands Set ...

Страница 19: ...n 2 Push the button to select ON or OFF 3 Push the MENU button When ON is selected the air conditioner starts stops running when the ON OFF button is pressed and hold 4 seconds When OFF is selected the air conditioner starts stops running when the ON OFF button is pressed Initial setting 2 2 Set Return 6 Header Follower 7 Language 8 Press hold 4 sec 9 Clock display Press hold 4sec ON OFF Return Fi...

Страница 20: ...he schedule timer etc 1 Push the button to select 9 Clock display on the menu screen then push the Set F2 button 2 Push the button to select 24H or AM PM 24H 24 hour clock AM PM 12 hour clock 3 Push the MENU button The screen returns to the Initial setting screen Initial setting 2 2 Set Return 6 Header Follower 7 Language 8 Press hold 4 sec 9 Clock display Clock display 24H AM PM Return Fix Set ...

Страница 21: ...he room temperature rises falls enough for the thermostat to turn off In order to prevent a continuous operation the forced test operation is released after 60 minutes have passed and returns to the normal operation 1 Push the MENU button to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the buttons for more t...

Страница 22: ...n is stopped Perform the test mode in the Cool or Heat mode Temperature setting cannot be adjusted during the test mode Check codes are displayed as usual 3 When the test mode is finished push the button to select 1 Test mode on the Field setting menu screen then push the Set F2 button The screen 3 appears Pushing the Yes F1 button stops the test mode screen and continues the normal operation NOTE...

Страница 23: ... is not available for some models In this case enter information manually Enter the contact number for service displayed in 2 Service information of 11 information on the menu screen Enter the model name and serial number displayed in 1 Model information of 11 information on the menu screen Push the MONITOR button Refer to 4 Monitor function page 27 for details When the group control is used selec...

Страница 24: ...r model name Enter reset the model name of the indoor unit 5 Indoor unit serial No Enter reset the serial number of the indoor unit 1 Push the button to select 1 Service contact tel No then push the Set F2 button 2 Move the cursor to select the character selected character is highlighted with the F1 F2 button then enter the contact number with the button 3 Push the MENU button 1 Service contact te...

Страница 25: ...o enter the model name of the indoor unit Select 5 Indoor unit serial No to enter the serial number of the indoor unit 2 Push the button to select 1 Manual model name input on the Outdoor model name screen then push the Set F2 button Select 1 Manual serial No input to enter the serial number of the outdoor unit Select 1 Manual model name input to enter the model name of the indoor unit Select 1 Ma...

Страница 26: ... serial number of the indoor unit select 2 Serial No selection 2 Push the button to select Remote controller or Outdoor unit When Outdoor unit is selected the model name or serial number of the outdoor unit is not displayed When Indoor unit is selected the model name or serial number received from the indoor unit is displayed When Remote controller is selected the manually entered model name or se...

Страница 27: ...hen the error occurred for the first time is displayed for the repeated alarm 1 Push the Reset F2 button while the list of alarm history is displayed 2 Push the Yes F1 button after the confirmation screen is displayed Delete the alarm history in each remote controller when the dual remote controller system is used 1 Test mode 2 Register service info 3 Alarm history 4 Monitor function 5 Setting lou...

Страница 28: ... Set F2 button Push the button to select the code to check data 2 Refer to the Installation Manual supplied with the indoor unit or outdoor unit or service manual for details about the check code and data 3 Push the CANCEL button to return to the Field setting menu screen 1 Test mode 2 Register service info 3 Alarm history 4 Monitor function 5 Setting louver position Field setting menu 1 2 Return ...

Страница 29: ... set the setting 3 After setting each item push the MENU button to confirm the changes to the settings Change the flap position indication for when swinging is cancelled in Fixed position indicator When ON is selected the louver stops and the indication becomes as shown on the right when swinging is cancelled Factory default When OFF is selected the stop position and indication becomes as shown on...

Страница 30: ...button Move the cursor to select data with the F2 button then set data with the button 2 Refer to the Installation Manual supplied with the indoor unit or service manual for details about the Function code and data 3 Push the MENU button to set the other Function codes After Continue is displayed on the screen push the Yes F1 button 4 Push the No F2 button to finish the setting operation appears o...

Страница 31: ... 30 Installation Manual EN ...

Страница 32: ...EH97071201 ...

Отзывы: