– 74 –
FILE NO. SVM-12085
8-3. Table Inspection of outdoor unit main parts
No.
Parts name
Checking procedure
1
Compressor
(Model : DA150A1F-20F)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
0.93
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
2
Compressor
(Model : DA150A1F-21F)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
1.07
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
3
Compressor
(Model : DA220A2F-22L)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
0.606
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
4
Fan motor
(Model : ICF-140-43-4R)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
21.00±1.05
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
5
Fan motor
(Model : ICF-280-A60-1)
Measure the resistance value of each winding by using the tester.
Position
Resistance value
Red – White
32.6±3.3
Ω
White – Black
Black – Red
Under 20°C
Red
White
Black
SVM-12085_051-114.indd 74
SVM-12085_051-114.indd 74
12/06/12 11:15 AM
12/06/12 11:15 AM