Applicable controls
REQUIREMENT
• When you use this air conditioner for the first time,
it takes approx. 5 minutes until the remote control
becomes available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes
approx. 5 minutes
until the remote control
becomes available.
<When power is turned on for the second (or
later) time>
It takes
approx. 1 minute
until the remote control
becomes available.
• Normal settings were made as factory default.
Change the indoor unit settings as required.
• Use the wired remote control to change the
settings.
Basic procedure for changing
settings
Change the settings while the air conditioner is not
working.
(Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table: Do
NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
1
Push and hold
button and “TEMP.”
button simultaneously for at least 4
seconds. After a while, the display flashes
as shown in the figure. Confirm that the
CODE No. is [01].
If the CODE No. is not [01], push
button to clear
the display content, and repeat the procedure from
the beginning. (No operation of the remote control
is accepted for a while after
button is pushed.)
(While air conditioners are operated under the
group control, “ALL” is displayed first. When
is pushed, the indoor unit number
displayed following “ALL” is the header unit.)
* The settings cannot be changed using the
wireless remote control, sub remote control,
or remote-controlless system (for central
remote control only). Therefore, install the
wired remote control to change the settings.
Power
on
“SETTING”
flashes
“SETTING”
goes out
Remote
control is
available
Approx. 5 minutes
Power
on
“SETTING”
flashes
“SETTING”
goes out
Remote
control is
available
Approx. 1 minutes
1
6
1
3
2
5
4
(* Display content varies with the indoor unit
model.)
2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the
louvers start swinging. The indoor unit for
change settings can be confirmed.
3
Specify CODE No. [
] with “TEMP.”
/
buttons.
4
Select SET DATA [
] with “TIME”
/
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure
2
.
• To change other settings of the selected indoor
unit, repeat from Procedure
3
.
Use
button to clear the settings. To make
settings after
button was pushed, repeat from
Procedure
2
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While
is flashing, no operation of the
remote control is accepted.)
External static pressure
settings
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure (
1
→
2
→
3
→
4
→
5
→
6
).
• Specify [5d] to the CODE No. in procedure
3
.
• For the SET DATA of procedure
4
, select a SET
DATA of the external static pressure to be set up
from the following table.
<Change on wired remote control>
SET DATA
External static pressure
0000
Standard (Factory default)
0001
High static pressure 1
0003
High static pressure 2
0006
Low static pressure