34-EN
33-EN
– 17 –
2
Each time [
] [
] setting button is
pushed, indoor unit numbers in the group
control change cyclically. Select the
indoor unit to change settings for.
• The fan of the selected indoor unit runs and the
louvers start swinging. The indoor unit can be
con
fi
rmed for which to change settings.
3
Push OFF timer button to con
fi
rm the
selected indoor unit.
Code No.
Set data
4
Push the menu button to make Code No.
[
]
fl
ash. Change Code No. [
] with
[
] [
] setting button.
5
Push the menu button to make Set data
[
]
fl
ash. Change Set data [
]
with [
] [
] setting button.
6
Push OFF timer button to complete the set
up.
y
To change other settings of the selected
indoor unit, repeat from Procedure
4
.
7
When all the settings have been completed,
push ON/OFF button to
fi
nish the settings.
(Return to the normal mode)
“
”
fl
ashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while “
” is
fl
ashing.)
• To change settings of another indoor unit, repeat
from Procedure
1
.
To secure better effect of
heating
When it is dif
fi
cult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can
be raised. Also use a circulator or other machinery to
circulate heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
y
Specify
[06]
for the Code No. in Procedure
4
.
y
For the Set data in Procedure
5
, select the Set data
of shift value of detection temperature to be set up
from the following table.
Set data
Detection temperature shift value
0000
No shift
0001
+1°C
0002
+2°C
(Factory default)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
Filter sign setting
According to the installation condition, the
fi
lter sign
term (Noti
fi
cation of
fi
lter cleaning) can be changed.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
y
Specify
[01]
for the Code No. in Procedure
4
.
y
For the Set data in Procedure
5
, select the Set data
of
fi
lter sign term from the following table.
Set data
Filter sign term
0000
None
0001
150 H
0002
2500 H
(Factory default)
0003
5000 H
0004
10000 H
• The
fi
lter sign may be unavailable depending on the
remote controllers.
Remote controller sensor
The temperature sensor of the indoor unit senses
room temperature usually. Set the remote controller
sensor to sense the temperature around the remote
controller.
Select items following the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
y
Specify
[32]
for the Code No. in Procedur
4
.
y
Select the following data for the Set data in
Procedure
5
.
Set data
Remote controller sensor
0000
Not in use (Factory default)
0001
In use
When
fl
ashes, the remote controller sensor is
defective.
Select the Set data [0000] (not in use) or replace the
remote controller.
Communication type
When connecting to the central control device
dedicated to TCC-Link, it is necessary to change to
TCC-Link.
Follow to the basic opreration procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
y
Specify
[FC]
for the Code No. in Procedure
4
.
y
Select the Set data [0000] (TCC-Link) in Procedure
5
.
Set data
Communication type
0000
TCC-Link
0004
TU2C-Link (Factory default)
Fan speed setting when
thermostat-OFF in cooling
mode
Set the fan speed when the room temperature reaches
the set temperature in the cooling mode.
Follow to the basic opreration procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
y
Specify
[9A]
for the Code No. in Procedure
4
.
y
Select the following data for the Set data in
Procedure
5
.
Set data
Fan speed when thermostat-OFF
in cooling mode
0000
Remote controller setting
0001
Extremely low speed (UL)
(Factory default)
8°C operation
Pre-heating operation can be set for cold regions
where room temperature drops to below zero.
Follow to the basic opreration procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
y
Specify
[d1]
for the Code No. in Procedure
4
.
y
Select the following data for the Set data in
Procedure
5
.
Set data
8°C Operation setting
0000
None (Factory default)
0001
8°C Operation setting
Installing optional parts
When installing optional parts, data setup may be
required with remote controller.
Be sure to set the data, according to Installation
Manual for optional parts.
Information
The following functions require a connection with
the RBC-AMTU
½½½
and RBC-AMSU
½½½
remote
controller. For details, refer to the manual included with
the remote controller.
• Individual unit selection during group operation
• Individual setting of louver position (wind direction)
• Swing type setting
• Louver lock (no swing) setting
• Energy saving operation (Power saving operation)
• Noti
fi
cation of
fi
lter cleaning time
Others
The following functions can be used with this model.
Refer to the Service Manual for more information.
• Rotation / backup operation
• Free cooling
• Secondary heating
• Power shift