– 13 –

6

Refrigerant piping

CAUTION

CAUTION

Use flare nuts that are included with the unit. Using 
different flare nuts may cause refrigerant gas leakage.

Refrigerant piping

Use the following item for the refrigerant piping.
Material: Seamless phosphorous deoxidized 
copper pipe.
Ø6.35, Ø9.52, Ø12.7 Wall thickness 0.8 mm or more

REQUIREMENT

When the refrigerant pipe is long, provide support 
brackets at intervals of 2.5 - 3 m to clamp the refrigerant 
pipe. Otherwise, abnormal sound may be generated.

CAUTION

CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

1. Reusable mechanical connectors and flared joints are 

not allowed indoors. When mechanical connectors 
are reused indoors, sealing parts shall be renewed. 
When flared joints are reused indoors, the flare part 
shall be refabricated.

2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes by using 

VACUUM PUMP.

4. Check the gas leakage. (Connected points)

Pipe size

Permissible piping length and 
height difference

They vary according to the outdoor unit.
For details, refer to the Installation Manual attached to 
the outdoor unit.

Flaring

• Cut the pipe with a pipe cutter.

Remove burrs completely. 
Remaining burrs may cause gas leakage.

• Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R32 or R410A differ from those 
of refrigerant R22, the flare tools newly 
manufactured for R32 or R410A are recommended.
However, the conventional 
tools can be used by adjusting 
projection margin of the 
copper pipe.

Projection margin in 
flaring: B (Unit: mm)

Rigid (Clutch type)

Flaring dia. meter size: A (Unit: mm)

CAUTION

CAUTION

• Do not scratch the inner surface of the flared part 

when removing burrs.

• Flare processing under the condition of scratches on 

the inner surface of flare processing part will cause 
refrigerant gas leak.

• Check that the flared part is not scratched, deformed, 

stepped, or flattened, and that there are no chips 
adhered or other problems, after flare processing.

• Do not apply refrigerating machine oil to the flare 

surface.

Model 

name

RAV-

HM30 type

HM40, 56 type

Pipe size

Gas side

9.5 mm

12.7 mm

Liquid side

6.4 mm

6.4 mm

Outside diameter 

size

R32 or R410A 

tool used

Conventional 

tool used

6.4, 9.5

0 - 0.5

1.0 - 1.5

12.7

Outside diameter 

size

A

+0

–0.4

6.4

9.1

9.5

13.2

12.7

16.6

B

A

Tightening connection

CAUTION

CAUTION

Do not apply excessive torque. Otherwise, the nut may 
crack depending on the conditions.

Tightening torque of flare pipe connections

Incorrect connections may cause not only a gas leak, 
but also a trouble of the refrigeration cycle.
Align the centers of the connecting pipes and tighten 
the flare nut as far as possible with your fingers. Then 
tighten the nut with a spanner and torque wrench as 
shown in the figure.

REQUIREMENT

Tightening with an excessive torque may crack the nut 
depending on installation conditions.
Tighten the nut within the specified tightening torque.

Evacuation

Perform vacuuming from the charge port of valve of the 
outdoor unit by using a vacuum pump.
For details, follow to the Installation Manual attached to 
the outdoor unit.
• Do not use the refrigerant sealed in the outdoor unit 

for evacuation.

REQUIREMENT

For the tools such as charge hose, use those 
manufactured exclusively for R32 or R410A.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant “R32 or 
R410A” referring to the attached Installation Manual of 
outdoor unit.
Use a scale to charge the refrigerant of specified 
amount.

REQUIREMENT

• Charging an excessive or too little amount of 

refrigerant causes a trouble of the compressor.
Charge the refrigerant of specified amount.

• A personnel who charged the refrigerant should write 

down the pipe length and the added refrigerant 
amount in the F-GAS label of the outdoor unit. It is 
necessary to fix the compressor and refrigeration 
cycle malfunction.

Open the valve fully

Open the valve of the outdoor unit fully. A 4 mm-
hexagonal wrench is required for opening the valve.
For details, refer to the Installation Manual attached to 
the outdoor unit.

Gas leak check

Check with a leak detector or soap water whether gas 
leaks or not, from the pipe connecting section or cap of 
the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC 
refrigerant (R32, R410A, R134a).

Unit: N•m

Outside diameter size

Tightening torque

6.4 mm

14 - 18

9.5 mm

34 - 42

12.7 mm

49 - 61

Work using two spanner

25-EN

26-EN

Содержание RAV-HM301MUT-E

Страница 1: ...AIR CONDITIONER SPLIT TYPE Installation Manual R32 Indoor Unit Compact 4 Way type RAV HM301MUT E RAV HM401MUT E RAV HM561MUT E Model name For commercial use English ...

Страница 2: ...erant HFC R32 which does not destroy the ozone layer This indoor unit is for the R32 refrigerant Be sure to combine with an outdoor unit for the R32 refrigerant Product information of ecodesign requirements Regulation EU 2016 2281 http ecodesign toshiba airconditioning eu en Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of installation place 7 4 Installation 9 5 Drain piping ...

Страница 3: ... pertaining to this electrical work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge ...

Страница 4: ...t in water leakage electric shock or fire Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit ...

Страница 5: ...r conditioner is running Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Appliance and pipe work shall be installed operated and stored in a room with a floor area larger than Amin m How to get Amin m Amin M 2 5 0 22759 h0 M is the refrigerant charge amount in appliance in kg h0 is the installa...

Страница 6: ...on using a solderless terminal etc Connection trouble in the places where the wire is connected in the middle may give rise to smoking and or a fire Electrical wiring work shall be conducted according to law and regulation in the community and Installation Manual Failure to do so may result in electrocution or short circuit Test run Before operating the air conditioner after having completed the w...

Страница 7: ...ossibly resulting in rupture injury or other trouble 1 Refer to the Definition of qualified installer or qualified service person This Air Conditioner has adopted a refrigerant HFC R32 which does not destroy the ozone layer As the R32 refrigerant is easily affected by impurities such as moisture oxidized film oil etc due to the high pressure be careful not to allow the moisture dirt existing refri...

Страница 8: ...lace where drained water will not cause any problem Avoid installing in the following places Place exposed to air with high salt content seaside area or place exposed to large quantities of sulfide gas hot spring The unit should be used in these places special protective measures are needed A restaurant kitchen where a lot of oil is used or place near machines in a factory Oil adhering to the heat...

Страница 9: ... 10 mm or more 200 200 15 or more 271 or more 1000 or more 271 or more 1000 or more 1000 or more An obstacle 15 or more 1 400 or more 560 or more 3 Check port 450 2 Check port 450 1000 or more Ceiling height Unit m When the height of the ceiling exceeds the distance of the item Standard 4 way in below table the warm air is difficult to reach the floor It is necessary to change the setup value of t...

Страница 10: ... to 594 13 to 20 Panel external dimension 620 13 to 20 13 to 20 Ceiling open dimension 580 to 594 Panel external dimension 620 External view Unit mm 23 5 0 146 191 320 214 256 93 40 132 173 257 70 53 193 154 146 8 3 12 184 ØA Ceiling open dimension 580 to 594 Bottom face of ceiling Wiring entry for remote control Unit external dimension 575 Refrigerant pipe connecting port Gas side Refrigerant pip...

Страница 11: ...ccording to size in the unit external view as shown below Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Indoor unit Panel fixing screw Installation pattern Accessory Installation pattern attachment hole New concrete slab Install the bolts with insert brackets or anchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in a...

Страница 12: ...ireless type remote controller can be installed in the same room 7 m o r le s s 5 Drain piping CAUTION CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained and apply a heat insulation so as not to cause a dew drop Inappropriate piping work may result in water leakage in the room and wet of furniture Piping Heat insulating material Require the fo...

Страница 13: ...6 mm or less Underside of ceiling Indoor unit 300 mm or less Rising up 850 mm or less After the electric work has finished pour water during COOL mode operation If the electric work has not yet finished pull out the float switch connector CN34 Red from the electrical control box and check draining by plugging the single phase 220 240 V power to the terminal blocks and If doing so the drain pump mo...

Страница 14: ...mm Liquid side 6 4 mm 6 4 mm Outside diameter size R32 or R410A tool used Conventional tool used 6 4 9 5 0 0 5 1 0 1 5 12 7 Outside diameter size A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 B A Tightening connection CAUTION CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Tightening torque of flare pipe connections Incorrect connections may cause not only a gas ...

Страница 15: ...re is connected in the middle may give rise to smoking and or a fire CAUTION CAUTION For power supply specifications follow the Installation Manual of outdoor unit Do not connect 220 240 V power to the terminal blocks for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires during peeling them Perfo...

Страница 16: ... units refer to the following table Remote controller wiring Wiring between indoor unit and outdoor unit 1 Figure below shows the wiring connections between the indoor and outdoor units and between the indoor units and remote controller The wires indicated by the broken lines or dot and dash lines are provided at the locally 2 Refer to the both indoor and outdoor unit wiring diagrams 3 The power o...

Страница 17: ...cable type and diameter Cord clamp can be attached on either right or left side When twin system are connected clamp two cables with one cord clamp Wire type Specification Cord clamping position Cabtyre cable 3 core stranded wire 2 5 mm Side D Cabtyre cable 4 core stranded wire 1 5 mm Side C Side D Space 8 5 mm Side C Space 4 mm Hook part Screws Cover of electrical control box CAUTION CAUTION 1 Ma...

Страница 18: ...p control change cyclically Select the indoor unit to change settings for The fan of the selected indoor unit runs and the louvers start swinging The indoor unit can be confirmed for which to change settings 3 Push OFF timer button to confirm the selected indoor unit 4 Push the menu button to make Code No flash Change Code No with setting button 5 Push the menu button to make Set data flash Change...

Страница 19: ...cur during cooling mode When the setting has been determined lights up Set data Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C Set data Filter sign term 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H Set data Swing of louvers 0001 Standard swing Factory default 0002 Dual swing 0003 Cycle swing 1 0001 ...

Страница 20: ...r Indoor unit Indoor unit Indoor unit Indoor unit Group control for system of multiple units One group can control up to 16 TU2C Link or 8 TCC Link indoor units with one remote controller Refer to the Wiring specifications Group control in single system For wiring procedure and wiring method of the individual line Identical refrigerant line system follow to Electrical connection Wiring between lin...

Страница 21: ...push the buttons 3 Push the ON OFF button return to the normal mode 9 Test run Before test run Before turning on the power supply carry out the following procedure 1 By using 500 V megger check that resistance of 1 MΩ or more exists between the terminal block 1 to 3 and the earth grounding work If resistance of less than 1 MΩ is detected do not run the unit 2 Check the valve of the outdoor unit be...

Страница 22: ...perature to 17 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 30 C with the temp setup buttons Monitoring function This function can be used to call the service monitor mode from the remote controller during a test run to obtain the temperature of the sensors of the remote controller indoor unit and outdoor unit 1 Push and hold menu ...

Страница 23: ...ay from the grille and remove Hook Fall preventive strap 4 Cleaning with water or vacuum cleaner If dirt is heavy clean the air filter using tepid water with a neutral detergent or just water After cleaning with water dry the air filter sufficiently in a shaded place 5 Mount the air filter 6 Close the air intake grille Check that the fall preventive strap of the air intake grille is attached to th...

Страница 24: ...st dirt appearance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ceiling panel louvers Indoor Dust dirt...

Страница 25: ...nsor TA indoor P C board Open circuit or short circuit of the room temp sensor TA was detected Auto reset F12 ALT TS sensor trouble Outdoor TS sensor may be displaced disconnected or short circuited Entire stop F13 ALT Heat sink sensor trouble Outdoor Abnormal temperature was detected by the temp sensor of the IGBT heat sink Entire stop F15 ALT Temp sensor connection trouble Outdoor Temp sensor TE...

Страница 26: ... may be gas leakage from the pipe or connecting part Check for gas leakage Entire stop P19 ALT 4 way valve trouble Outdoor Indoor 4 way valve indoor temp sensors TC TCJ An trouble was detected due to temperature drop of the indoor unit heat exchanger sensor when heating Auto reset P20 ALT High pressure protective operation Outdoor High pressure protection Entire stop P22 ALT Outdoor unit fan troub...

Страница 27: ...EB99847701 DH91308201 ...

Отзывы: