105
13
DETACHMENTS
13-1.RAV-GP561ATW*
No.
Part name
Procedure
Remarks
(1)
Common
procedure
WARNING
Stop operation of the air conditioner and turn off breaker
switch.
CAUTION
Ensure wearing of gloves when performing any work in
order to avoid injury from parts, etc.
1. Detachment
1) Stop operation of the air conditioner, and turn off the
main switch of the breaker for air conditioner.
2) Remove the valve cover.
(3 pcs, M4 × 10 hexagon screws)
• After removing screw, remove the valve cover
pulling it downward.
3) Remove the wiring cover.
(1 pc, M4 × 8 truss screw)
• After removing screw, remove the wiring cover
pulling it upward.
4) Remove cord clamp (3 pcs, M4 × 14 truss screws),
and then remove connecting cable.
5) Remove the upper cabinet.
(5 pcs, M4 × 10 hexagon screws)
• After removing screws, remove the upper cabinet
pulling it upward.
6) Remove the water-proof cover.
2. Attachment
1) Attach the water-proof cover.
NOTE
The water-proof cover must be attached without fail in
order to prevent rain water, etc. from entering inside the
indoor unit.
2) Attach the upper cabinet.
(5 pcs, M4 × 10 hexagon screws)
3) Perform cabling of connecting wires, and attach the
cord clamp.
• Fix the cord clamp by tightening the screws (3 pcs,
M4 × 14 truss screws), fitting 2 concave parts of
the cord clamp to each connecting wires.
4) Attach the wiring cover.
(1 pc, M4 × 8 truss screw)
5) Attach the valve cover.
(3 pcs, M4 × 10 hexagon screws)
• Insert the upper part into the square hole of the
side cabinet, set hook claws of the valve cover to
square holes (at three positions) of the main unit,
and attach it pushing upward.
These 2 bending
parts shall be put
inside of a unit by
bending these 2
ports.
This part shall be put
on the side cabinet.
Fit the corner of the
water proof cover to
the corner of the
front cabinet.
This part shall cover
the gap between the
inverter box and the
front cabinet.
This line shall
be pavallel to
the front
cabinet.
How to mount the water-proof cover