Frequency normal down
Frequency slow down
Frequency hold
Frequency slow up
(Up to command)
As command is
Abnormal stop
TD [˚C]
a
b
c
d
e
1.
Pulse Modulating Valve (PMV) control
1) For PMV withGM56, 80 : 50 to 500, GM110, 140 : 30 to 500 pulses during operation, respectively.
2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC
sensor.
3) In heating operation, PMV is controlled with the temperature difference between TS sensor and TE
sensor.
4) For the temperature difference in items 2) and 3), -1 to 5K is aimed as the target in both cooling and
heating operations.
5) When the cycle excessively rose in both cooling and heating operations, PMV is controlled by TD
sensor.
The aimed value is usually GM56, 80 : 100°C, GM110, 140 : 91°C in both cooling and heating
operations.
REQUIREMENT
A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the
compressor life. In a case of trouble on the compressor, be sure to check there is no error in the resistance
value an the refrigerating cycle of each sensor after repair and then start the operation.
2. Discharge temperature release control
1) When the discharge temperature did not fall or the discharge temperature rapidly went up by PMV
control, this control lowers the compressor frequency. It subdivides the frequency control up to 0.6Hz
to stabilize the cycle.
2) When the discharge temperature detected an abnormal stop zone, the compressor stops and then
restarts after 2 minutes 30 seconds.
The error counting is cleared when the operation continued for 10 minutes. If the error is detected by
4 times without clearing, the error is determined and restarting is not performed.
∗
The cause is considered as excessively little amount of refrigerant, PMV error or clogging of the cycle.
3) For displayed contents of error, confirm on the check code list.
GM56, 80
a
GM110, 140
117
111
b
115
109
c
106
106
d
103
103
e
96
96
7. OUTDOOR CONTROL CIRCUIT
7-1. Outline of Main Controls
- 42 -
FILE NO.
SVM-18043
Содержание RAV-GM1101ATJP-E
Страница 21: ...2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV GM561AT P GM801AT P 21 FILE NO SVM 18043 ...
Страница 22: ...2 2 RAV GM1101AT P GM1401AT P 22 FILE NO SVM 18043 ...
Страница 28: ...4 WIRING DIAGRAM 4 1 RAV GM561AT P GM801AT P 28 FILE NO SVM 18043 ...
Страница 29: ...4 2 RAV GM1101AT P GM1401AT P 29 FILE NO SVM 18043 ...
Страница 116: ... Inverter assembly GM56 116 FILE NO SVM 18043 ...
Страница 120: ... Inverter assembly GM80 120 FILE NO SVM 18043 ...
Страница 124: ... Inverter assembly GM110 140 124 FILE NO SVM 18043 ...
Страница 127: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...