6-3. Tools
6-3-1. Required Tools
Refer to the “
4. Tools
” (Page 14)
6-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to
the following steps.
Connect the charge hose to packed valve
service port at the outdoor unit’s gas side.
Recover the refrigerant, and check no
refrigerant remains in the equipment.
(For refrigerant charging, see the figure below.)
Connect the charge hose of the vacuum
pump adapter.
Open fully both packed valves at liquid and
gas sides.
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum
pump’s power switch. Then, evacuating the
refrigerant in the cycle.
When the compound gauge’s pointer has indicated
–0.1 Mpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump’s
power switch.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic
balance, connect the connecting hose to the
cylinder and the connecting port of the electronic
balance, and charge
liquid refrigerant.
(INDOOR unit)
(Liquid side)
Refrigerant
cylinder (With
siphon pipe)
Check valve
(Gas side)
Open/Close
valve for charging
Electronic balance for refrigerant charging
Opened
(OUTDOOR unit)
Closed
Service port
Fig. 6-4-1 Configuration of refrigerant charging
1) Never charge refrigerant exceeding the specified amount.
2) If the specified amount of refrigerant cannot be charged, charge refrigerant
bit by bit
in COOL mode.
3) Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified
amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and
may cause a rupture or personal injury.
service valve
service valve
- 35 -
FILE NO.
SVM-18043
Содержание RAV-GM1101ATJP-E
Страница 21: ...2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV GM561AT P GM801AT P 21 FILE NO SVM 18043 ...
Страница 22: ...2 2 RAV GM1101AT P GM1401AT P 22 FILE NO SVM 18043 ...
Страница 28: ...4 WIRING DIAGRAM 4 1 RAV GM561AT P GM801AT P 28 FILE NO SVM 18043 ...
Страница 29: ...4 2 RAV GM1101AT P GM1401AT P 29 FILE NO SVM 18043 ...
Страница 116: ... Inverter assembly GM56 116 FILE NO SVM 18043 ...
Страница 120: ... Inverter assembly GM80 120 FILE NO SVM 18043 ...
Страница 124: ... Inverter assembly GM110 140 124 FILE NO SVM 18043 ...
Страница 127: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...