– 88 –
14. Appendix
Lite-Vision plus Remote Controller (RB-RWS20-E) setup
1. Test run setup
<Procedure> Perform setting while the air conditioner stops.
1
Push the [
MENU] button to display the menu screen.
2
Push and hold the [
MENU] button and the [
∨
] button at the
same time to display the “Field setting menu”.
Æ
Push and hold the buttons for more than 4 seconds.
3
Push the [
∧
] / [
∨
] button to select “1. Test mode” on the
“Field setting menu screen, then push the “
Set” [
F2] button.
Æ
Pushing the “
Yes” [ F1] button sets the test mode and
the screen returns to the field setting menu screen.
Push [
CANCEL] twice, the screen (2) appears.
4
Push the [
ON / OFF] button to start the test mode. The
screen
(1)
shown in the left appears. (The screen
(2)
appears
when the operation is stopped.)
Æ
Perform the test mode in the “Cool” or “Heat” mode.
Æ
Temperature setting cannot be adjusted during the test mode.
Æ
Check codes are displayed as usual.
5
When the test mode is finished, push the [
∧
] / [
∨
] button
to select “1. Test mode” on the “Field setting menu” screen, then
push the “
Set” [
F2] button.
The screen
(3)
appears.
Æ
Pushing the “
Yes” [ F1] button stops the test mode
screen and continues the normal operation.
NOTE
The test mode stops after 60 minutes and the screen returns to the normal / detailed
display.
1.Test mode
2.Register service info.
3.Alarm history
4.Monitor function
5.FC setting
Field setting menu
Return
Set
1.Test mode
2.Register service info.
3.Alarm history
4.Monitor function
5.FC setting
Field setting menu
Return
Set
Return
Test mode start.
No
Yes
Test mode
Set
Yes
Test
(1)
Room A
12:00
Mode
Fan Speed
Cool
Test
(2)
Room A
12:00
Return
Test mode stop.
No
Yes
Test mode
(3)
Set
Yes