Toshiba RAS-M05PKVSG-E Скачать руководство пользователя страница 5

EN

3

• Do not use any refrigerant different from the one speci

fi

 ed for complement or 

replacement.

  Otherwise, abnormally high pressure may be generated in the refrigeration 

cycle, which may result in a failure or explosion of the product or an injury to 
your body.

• Do not use means to accelerate the defrosting process or to clean, other than 

those recommended by the manufacturer.

• The appliance shall be stored in a room without continuously operating ignition 

sources (for example: open 

fl

 ames, an operating gas appliance or an operating 

electric heater).

• Be aware that refrigerants may not contain an odour.
• Do not pierce or burn as the appliance is pressurized. Do not expose the 

appliance to heat, 

fl

 ame, sparks, or other sources or ignition. Else, it may 

explode and cause injury or death.

• For R32 model, use pipes, 

fl

 are nut and tools which is speci

fi

 ed for R32 

refrigerant. Using of existing (R22) piping, 

fl

 are nut and tools may cause 

abnormally high pressure in the refrigerant cycle (piping), and possibly result in 
explosion and injury.

• Thickness of copper pipes used R32 must be more than 0.8mm. Never use 

copper pipes thinner than 0.8mm.

• Do not perform 

fl

 are connection inside a building or dwelling or room, when 

joining the heat exchanger of indoor unit with interconnection piping. Refrigerant 
connection inside a building or dwelling or room must be made by brazing or 
welding. Joint connection of indoor unit by 

fl

 aring method can only be made 

at outdoor or at outside of building or dwelling or room. Flare connection may 
cause gas leak and 

fl

 ammable atmosphere.

• After completion of installation or service, con

fi

 rm there is no leakage of 

refrigerant gas. It may generate toxic gas when the refrigerant contacts with 

fi

 re.

• Appliance and pipe-work shall be installed, operated and stored in a room with a 

fl

 oor area larger than A

min

 m

2

.

  How to get A

min

 m

2

 :  A

min

 = (M / (2.5 x 0.22759 x h

0

))

2

  M is the refrigerant charge amount in appliance in kg. h

0

 is the installation height 

of the appliance in m: 0.6 m for 

fl

 oor standing/1.8 m for wall mounted/1.0 m for 

window mounted/2.2 m for ceiling mounted (For these units recommend 
installation height 2.5 m.).

• Comply with national gas regulations.

Содержание RAS-M05PKVSG-E

Страница 1: ...AL Indoor unit RAS M05 07PKVSG E 1122950199 R32 ENGLISH ESPAÑOL FRANÇAIS ITALIANO DEUTSCH PORTUGUÊS POLSKI ČESKY PУCСКИЙ HRVATSKI MAGYAR NEDERLANDS ΕΛΛΗΝΙΚΑ SVENSKA SUOMI NORSK DANSK ROMÂNĂ БЪЛГАРСКИ EESTI LATVISKI SLOVENČINA SLOVENŠČINA LIETUVIŲ ...

Страница 2: ...lation Place 7 Cutting a Hole and Mounting Installation Plate 7 Wiring Connection 8 How to Connect Remote Controller for Wire Operation 8 Piping and Drain Hose Installation 9 Indoor Unit Fixing 10 Drainage 10 OTHERS 11 Gas Leak Test 11 Remote Control A B Selection 11 Test Operation 11 Auto Restart Setting 11 APPENDIX 12 CONTENTS EN ...

Страница 3: ...oes not require admission or repeated hospital treatment 2 Property damage means greater damage which affects assets or resources For general public use Power supply cord and connecting cable of appliance use shall be at least polychloroprene sheathed flexible cord design H07RN F or cord designation 60245 IEC66 Shall be installed in accordance with national wiring regulations This appliance must b...

Страница 4: ...ELECTRIC PARTS MAY BE DAMAGED CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE ...

Страница 5: ...d possibly result in explosion and injury Thickness of copper pipes used R32 must be more than 0 8mm Never use copper pipes thinner than 0 8mm Do not perform flare connection inside a building or dwelling or room when joining the heat exchanger of indoor unit with interconnection piping Refrigerant connection inside a building or dwelling or room must be made by brazing or welding Joint connection...

Страница 6: ...ater or other moisture before installation could result in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install the unit at place where leakage of flammable gas may occur In case gas leaks and accumulates at surrounding of the unit it may cause of fire Do not install in a place that can increase...

Страница 7: ...mend to use vacuum to clean by sucking the dusts which stick or dip inside the filter or use the blower to blow the dust go out through the filter 2 If necessary to use water to clean simply use the plain water to wash the filter dry with the sunlight for 3 4 hours or until it completely dry Nevertheless use hair drier to dry it However washing with water it may reduce the performance of the filte...

Страница 8: ... holder Wireless remote control Shield pipe Attach to the front panel Air filter Hook Installation plate Hook 65 mm or more 300 mm or more 300 mm or more Insert the cushion between the indoor unit and wall and tilt the indoor unit for better operation For the rear left and left piping Wall Make sure to run the drain hose sloped downward Do not allow the drain hose to get slack Cut the piping hole ...

Страница 9: ...ed The indoor unit shall be installed at least 2 5 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION 5 4 45 5 7 Side view Top view Indoor unit R e c e p t i o n r a n g e Remote control Remote control Reception range Indoor unit The center of the pipe hole is above the arrow Pipe hole Ø65 mm 120 mm 6 When the installation plate is directly mounted on the wall 1...

Страница 10: ...ontrol wire Remote controller How to Connect Remote Controller for Wire Operation For indoor unit Wiring Connection Indoor unit Wiring of the connecting cable can be carried out without removing the front panel 1 Remove the air inlet grille Open the air inlet grille upward and pull it toward you 2 Remove the terminal cover and cord clamp 3 Insert the connecting cable according to the local cords i...

Страница 11: ...to initial condition when user shutdown power supply of air conditioner Control wire Hole for hang remote controller Remote controller Control wire Screw Ø3 1 16L for hang remote controller Wall Screw Ø3 1 25L for fix battery cover Remote controller 8 9 Battery cover Screw Tighten firmly but not over 0 15 N m 0 02 kgf m 1 Remove cover of remote controller by sliding down and take it out 2 If batte...

Страница 12: ...rise the drain hose 50 mm or more Do not put the drain hose end into water Do not put the drain hose end in the drainage ditch 1 2 1 Hook here Installation plate Hook Press unhook Push Push Indoor Unit Fixing For detaching the indoor unit from the installation plate pull the indoor unit toward you while pushing its bottom up at the specified parts 1 Pass the pipe through the hole in the wall and h...

Страница 13: ...the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation between A setting B setting and A room B room when connecting the piping and c...

Страница 14: ...il a large quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel f...

Отзывы: