How to remove the drain cap

Clip the drain cap by needle-nose 
pliers and pull out.

How to remove the drain hose

•  The drain hose can be removed by removing the 

screw securing the drain hose and then pulling out 
the drain hose.

•  When removing the drain hose, be careful of any 

sharp edges of steel plate. The edges can injuries.

•  To install the drain hose, insert the drain hose 

fi

 rmly until the connection part contacts with heat 

insulator, and then secure it with original screw.

How to 

fi

 x the drain cap

1)  Insert hexagon wrench (4 mm) 
  in a center head.

2)  Firmly insert the drain cap.

Firmly insert the drain hose and drain cap; otherwise, water may leak.

CAUTION

Drain hose

Piping and Drain Hose Installation

*  Since dewing results in a machine trouble, make sure to insulate both 

connecting pipes. (Use polyethylene foam as insulating material.)

     

Piping and drain hose forming

1.  Die-cutting back body slit

  Cut out the slit on the left or right side of the back body for the left or right 

connection and the slit on the bottom left or right side of the back body 
for the bottom left or right connection with a pair of nippers.

Rear right

Rear left

Bottom left

Left

Bottom right

Right

Die-cutting

back body slit

Changing

drain hose

Piping preparation

2.  Changing drain hose

  For leftward connection, bottom-leftward connection and rearleftward 

connection’s piping, it is necessary to change the drain hose and drain 
cap.

*

Remark

 :  1.  Recommend to use double insulation lead wire for connect 

remote control and air conditioner.

 

2.  For wire operation, 1 remote control can control only 1 indoor 

unit.

 

3.  In wire operation, remote controller will return to initial 

condition (PRESET, TIMER and CLOCK will return to 
initial condition) when user shutdown power supply of air 
conditioner.

Control wire

Hole for hang
remote controller

Remote controller

Control wire

Screw (Ø3.1×16L) 
for hang remote 
controller

Wall

Screw (Ø3.1×25L) 
for 

fi

 x battery cover

Remote controller

8

9

!

Battery cover

Screw

Tighten 

fi

 rmly but not over 

0.15 N·m (0.02 kgf·m)

  1. Remove cover of remote controller by sliding down and take it out.
  2. If batteries are exist, please take them out. The combination of using 

wire controller and batteries may cause of batteries explosion.

  3. Make hole for insert control wire by use screwdriver break the polyester 

sheet as shown on 

fi

 gure 

4

.

  4. Insert control wire from rear side of remote controller as shown on 

fi

 gure 

5

.

  5. Fix control wire which arrange as shown on 

fi

 gure 

6

 and 

7

 to terminal 

by provided screws (tighten 

fi

 rmly but not over 0.25 N·m (0.03 kgf·m)).

  6. Set control wire through gutter way at rear side of remote controller as 

shown on 

fi

 gure 

8

.

  7. Fix provided screw (Ø3.1×16L) on the wall to hang remote controller as 

shown on 

fi

 gure 

9

.

  8. Mark and arrange hole for 

fi

 x below screw (Ø3.1×25L) as shown on 

fi

 gure 

9

.

  9. Assembly battery cover which provided with accessory bag then use 

provide screw (Ø3.1×25L) to 

fi

 x battery cover together with wall as 

shown on 

fi

 gure 

!

 (tighten 

fi

 rmly but not over 0.15 N·m (0.02 kgf·m)).

10. Reassembly cover of remote controller.

     For remote controller

4

5

Polyester sheet close hole 
for insert control wire

Control wire

6

7

Control wire

Terminal

* Wire size 28-22AWG 

or 0.08-0.32 mm

2

  Outer diameter not over 4.7 mm, 

control wire length 30 m. or less.

30 mm

10 mm

* Terminals for wiring can be either on right (type A) or left (type B), depending 

on the controller packed in carton.

Type A

Type B

Do not apply lubricating oil
(refrigerant machine oil) 
when inserting the drain 
cap. Application causes 
deterioration and drain
leakage of the plug.

Insert a hexagon wrench 
(4 mm).

No gap

Содержание RAS-M05PKVSG-E

Страница 1: ...AL Indoor unit RAS M05 07PKVSG E 1122950199 R32 ENGLISH ESPAÑOL FRANÇAIS ITALIANO DEUTSCH PORTUGUÊS POLSKI ČESKY PУCСКИЙ HRVATSKI MAGYAR NEDERLANDS ΕΛΛΗΝΙΚΑ SVENSKA SUOMI NORSK DANSK ROMÂNĂ БЪЛГАРСКИ EESTI LATVISKI SLOVENČINA SLOVENŠČINA LIETUVIŲ ...

Страница 2: ...lation Place 7 Cutting a Hole and Mounting Installation Plate 7 Wiring Connection 8 How to Connect Remote Controller for Wire Operation 8 Piping and Drain Hose Installation 9 Indoor Unit Fixing 10 Drainage 10 OTHERS 11 Gas Leak Test 11 Remote Control A B Selection 11 Test Operation 11 Auto Restart Setting 11 APPENDIX 12 CONTENTS EN ...

Страница 3: ...oes not require admission or repeated hospital treatment 2 Property damage means greater damage which affects assets or resources For general public use Power supply cord and connecting cable of appliance use shall be at least polychloroprene sheathed flexible cord design H07RN F or cord designation 60245 IEC66 Shall be installed in accordance with national wiring regulations This appliance must b...

Страница 4: ...ELECTRIC PARTS MAY BE DAMAGED CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE ...

Страница 5: ...d possibly result in explosion and injury Thickness of copper pipes used R32 must be more than 0 8mm Never use copper pipes thinner than 0 8mm Do not perform flare connection inside a building or dwelling or room when joining the heat exchanger of indoor unit with interconnection piping Refrigerant connection inside a building or dwelling or room must be made by brazing or welding Joint connection...

Страница 6: ...ater or other moisture before installation could result in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install the unit at place where leakage of flammable gas may occur In case gas leaks and accumulates at surrounding of the unit it may cause of fire Do not install in a place that can increase...

Страница 7: ...mend to use vacuum to clean by sucking the dusts which stick or dip inside the filter or use the blower to blow the dust go out through the filter 2 If necessary to use water to clean simply use the plain water to wash the filter dry with the sunlight for 3 4 hours or until it completely dry Nevertheless use hair drier to dry it However washing with water it may reduce the performance of the filte...

Страница 8: ... holder Wireless remote control Shield pipe Attach to the front panel Air filter Hook Installation plate Hook 65 mm or more 300 mm or more 300 mm or more Insert the cushion between the indoor unit and wall and tilt the indoor unit for better operation For the rear left and left piping Wall Make sure to run the drain hose sloped downward Do not allow the drain hose to get slack Cut the piping hole ...

Страница 9: ...ed The indoor unit shall be installed at least 2 5 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION 5 4 45 5 7 Side view Top view Indoor unit R e c e p t i o n r a n g e Remote control Remote control Reception range Indoor unit The center of the pipe hole is above the arrow Pipe hole Ø65 mm 120 mm 6 When the installation plate is directly mounted on the wall 1...

Страница 10: ...ontrol wire Remote controller How to Connect Remote Controller for Wire Operation For indoor unit Wiring Connection Indoor unit Wiring of the connecting cable can be carried out without removing the front panel 1 Remove the air inlet grille Open the air inlet grille upward and pull it toward you 2 Remove the terminal cover and cord clamp 3 Insert the connecting cable according to the local cords i...

Страница 11: ...to initial condition when user shutdown power supply of air conditioner Control wire Hole for hang remote controller Remote controller Control wire Screw Ø3 1 16L for hang remote controller Wall Screw Ø3 1 25L for fix battery cover Remote controller 8 9 Battery cover Screw Tighten firmly but not over 0 15 N m 0 02 kgf m 1 Remove cover of remote controller by sliding down and take it out 2 If batte...

Страница 12: ...rise the drain hose 50 mm or more Do not put the drain hose end into water Do not put the drain hose end in the drainage ditch 1 2 1 Hook here Installation plate Hook Press unhook Push Push Indoor Unit Fixing For detaching the indoor unit from the installation plate pull the indoor unit toward you while pushing its bottom up at the specified parts 1 Pass the pipe through the hole in the wall and h...

Страница 13: ...the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation between A setting B setting and A room B room when connecting the piping and c...

Страница 14: ...il a large quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel f...

Отзывы: