– 91 –
11-7. Trouble Diagnosis by Outdoor LED
For the outdoor unit, the self-diagnosis is possible by
five LEDs (Red).
• LEDs (Red) (D11 to D15) are provided on the sub-
control board under surface of the inverter, and as
shown below, they are checked from the wiring port
when removing the wiring cover.
(1) If a trouble occurs, LED (Red) goes on according
to the trouble as described in the table below.
(2) When two or more troubles occur, LEDs go on
cyclically.
(3) Usually, LEDs (Red) go off.
D09 D10 D11 D12 D13
LED (Red)
Contents
Indoor alarm
code
LED indication
D09
D10
D11
D12
D13
Normal running
None
IGBT short circuit, Compressor motor rear short
14
Trouble on position detecting circuit
16
Trouble on current detecting circuit
17
CONDENSOR PIPE TEMP. SENSOR(TE) fault
18
SUCTION PIPE TEMP. SENSOR(TS) fault
18
DISCHARGE PIPE TEMP. SENSOR(TD) fault
19
Trouble on outdoor fan
1A
OUTDOOR TEMP. SENSOR(TO) fault
1B
Trouble on compressor system
1C
GAS SIDE PIPE TEMP. SENSOR a (TGa) fault
1C
GAS SIDE PIPE TEMP. SENSOR b (TGb) fault
1C
TGa, TGb sensor out of place, PMV fault
1C
Communication trouble between MCU
1C
Compressor lock
1D
Trouble on discharge temp. Gas leakage
1E
Compressor break down
1F
: LED ON,
: LED OFF