2) Fan speed
≥
400
when the motor stopped.
Air conditioner ON
(Remote controller)
YES
YES
NO
NO
Indoor unit controller
Fan motor ON
3) Fan lock
OFF status of
fan motor continues.
4) Motor operates as shown in the table below.
1) Outdoor unit
operation
command
(Outdoor
fan
control)
Air conditioner
OFF
Alarm
display
Item
2.
Outdoor fan
motor control
Operation flow and applicable data, etc.
The blowing air volume at the outdoor unit side is controlled.
Receiving the operation command from the controller of indoor
unit, the controller of outdoor unit controls fan speed.
∗
For the fan motor, a DC motor with non-stage variable speed
system is used.
However, it is limited to 8 stages for reasons of controlling.
Description
1) The operation command sent
from the remote controller is
processed by the indoor unit
controller and transferred to the
controller of the outdoor unit.
2) When strong wind blows at
outdoor side, the operation of air
conditioner continues with the fan
motor stopped.
3) Whether the fan is locked or not
is detected, and the operation of
air conditioner stops and an
alarm is displayed if the fan is
locked.
4) According to each operation
mode, by the conditions of
outdoor temperature (To) and
compressor revolution, the speed
of the outdoor fan shown in the
table is selected.
Compressor revolution (rps)
~
20
~
33
~
42
~
43
Normal operation
To > 38
O
C
350
630
800
800
28 < To < 38
O
C
350
550
630
800
15 < To < 28
O
C
300
550
550
630
10 < To < 15
O
C
300
470
470
550
5 < To < 10
O
C
300
350
350
470
0 < To < 5
O
C
300
300
300
350
To < 0
0
0
300
0
300
0
300
Sleep or Quiet
To > 38
O
C
350*
550*
630*
80
0*
operation
To < 38
300*
470*
550*
630*
To is abnormal
300~350 300~550 300~630 300~720
Normal operation
To > 38
O
C
400
800
900
900
28 < To < 38
O
C
400
700
800
900
15 < To < 28
O
C
350
620
700
800
10 < To < 15
O
C
350
530
530
700
5 < To < 10
O
C
350
400
400
470
0 < To < 5
O
C
350
350
350
400
To < 0
0
0~400
0~400
0~400
Sleep or Quiet
To > 38
O
C
400*
700*
800*
900*
operation
To < 38
350*
470*
700*
800*
To is abnormal
350~400 350~400 350~800 350~900
RAS-2M2
1
U2ACVG-SG
RAS-3M3
1
U2ACVG-SG
*Maximum revolution
To : Outdoor temp. sensor
Compressor revolution (rps)
~
16
~
18
~
36
~
37
Normal operation
To > 38
O
C
400
800
900
900
28 < To < 38
O
C
400
700
800
900
15 < To < 28
O
C
350
600
700
800
10 < To < 15
O
C
350
530
530
700
5 < To < 10
O
C
350
400
400
470
0 < To < 5
O
C
350
350
350
400
To < 0
0
0~400
0~400
0~400
Sleep or Quiet
To > 38
O
C
400*
700*
800*
900*
operation
To < 38
350*
470*
700*
800*
To is abnormal
350~400 350~400 350~800 350~900
RAS-3M4
1
U2ACVG-SG
- 37 -