14

Outdoor Unit

Installation Manual

3. Turn on the circuit breaker to supply electricity.
  In the initial LED display status, D805 is lighted as below.

™

 : ON, 

˜

 : OFF,   : Rapid Flashing (5 times/sec.),

¯

 : Slow Flashing (1 time/sec.)

D800

D801

D802

D803

D804

D805

˜

˜

˜

˜

˜

™

Start running all the indoor units connected to the outdoor unit in the 
cooling mode.
(The indoor unit in the room that doesn’t operate the cooling mode cannot 
be checked.)

4. After 5 minutes, hold down SW01 for at least 5 seconds, and check that 

D800 is lighted and D804 light is 

fl

 ashing (1 time/sec.).

D800

D801

D802

D803

D804

D805

™

˜

˜

˜

¯

˜

5. Press the SW01 4 times until the LED is displayed as below.

D800

D801

D802

D803

D804

D805

˜

˜

™

˜

˜

6. Press SW02 for 1 times. Then D805 light is 

fl

 ashing (5 times/sec.).

D800

D801

D802

D803

D804

D805

˜

˜

™

˜

7. Hold down SW02 for at least 5 seconds. Then the wiring/piping check 

starts automatically. (The LED display is lighted for a moment.)

D800

D801

D802

D803

D804

D805

˜

˜

™

˜

¯

™

•  If no problems are detected, the checking operation returns to the 

normal operation automatically. The LED is displayed as below.

D800

D801

D802

D803

D804

D805

˜

˜

˜

˜

˜

™

8. The below is displayed when the error is detected.
  (* Repetition of 3 sec ON / 0.5 sec OFF)

D800

D801

D802

D803

D804

D805

™

*

™

*

™

*

™

*

™

*

™

  Press the SW01 3 times until the LED is displayed as below, to check the 

room judged as error.

D800

D801

D802

D803

D804

D805

˜

™

˜

˜

˜

  Incorrect wiring/piping can be checked by pressing SW02. The LED is 

displayed as below. Turn off the circuit breaker, then check wiring/piping 
again.

Check result

D800 D801 D802 D803 D804 D805

Description

˜

˜

˜

˜

˜

¯

Normal operation (no error)

™

˜

˜

˜

˜

¯

Trouble in unit A

˜

™

˜

˜

˜

¯

Trouble in unit B

˜

˜

™

˜

˜

¯

Trouble in unit C

™

™

˜

˜

˜

¯

Trouble in unit A and B

™

˜

™

˜

˜

¯

Trouble in unit A and C

˜

™

™

˜

˜

¯

Trouble in unit B and C

™

™

™

˜

˜

¯

Trouble in unit A, B and C

•  The D800 LED represents unit A.
•  The D801 LED represents unit B.
•  The D802 LED represents unit C.

9. When you want to start over the operation of the SW01 and SW02, press 

the SW01 and the SW02 at the same time for 5 sec. (The procedure will 
set back to step 3.) However, do not execute the operation during the 
check. If by any chance the check is stopped by the operation, start over 
the check after turning off the power once.

10. Notes

•  It sometimes takes about 30 minutes maximum for the check.
•  During the check, the compressor and the fan of the outdoor/indoor unit 

repeat ON/OFF.

•  You cannot check wiring/piping when the external temperature is 5°C 

or less. Also, there is a possibility to misjudge if the indoor temperature 
becomes too low by cooling operation. In that case, execute the cooling 
operation for per room and check if the connection is normal.

„

Gas Leak Inspection

Refer to the “

„

 Gas Leak Inspection” on page 12.

„

Test run

1. If you perform the test run in summer, start running in the cooling mode 

fi

 rst to decrease the temperature of the room, then run in the heating 

mode.

  (Heating mode: Set the temperature to 30°C.)

•  If you perform the test run in winter, start running in the heating mode 

fi

 rst to increase the temperature of the room, then run in the cooling 

mode.

  (Cooling mode: Set the temperature to 17°C.)

2. For the test run, be sure to satisfy the following conditions below:

-  Perform the test run for each indoor unit respectively.
-  Perform the test run for about 10 minutes in both the cooling mode 

and the heating mode.

•  You can perform the test run in the cooling/heating mode by utilizing 

the thermo sensor of the indoor unit.

  Cooling mode: Warm the thermo sensor using an appliance such as 

a hair dryer.

  Heating mode: Put a cold towel on the thermo sensor.

„

Instructions for the Customers

•  Explain to the customers the proper operation procedure and let them 

operate the air conditioner along with the supplied instruction manual.

•  When multiple indoor units are connected to the outdoor unit, the cooling 

mode and the heating mode are not available at the same time.

  When multiple indoor units are running at the same time, the operation 

mode of the unit which starts running 

fi

 rst is applied to the other units.

•  When you start running the indoor unit or change the operation mode, the 

unit starts running after 3 minutes. This is due to the protection function of 
the unit, not a malfunction.

•  When the external temperature becomes low, the pre-heating of the 

compressor starts to protect it. Keep the circuit breaker on for use.

  The electricity consumption during pre-heating is about 30 W.
  If the circuit breaker is turned off, the indoor unit may not start running for 

about 10 minutes or more.

•  Electronic expansion valves are used for the outdoor unit.
  When you turn on the power, the outdoor unit starts clattering every 1 or 

2 months. This clattering is not a malfunction, but occurs when the unit is 
returning to the default setting for optimised control.

•  While an indoor unit is running in the heating mode, the outdoor unit 

supplies refrigerant to the other indoor units which are not running.

  Therefore, noise may come from the other indoor units or the exterior of 

them may become warm.

Содержание RAS-2M10U2AVG-E

Страница 1: ...oor Unit AIR CONDITIONER MULTI SPLIT TYPE Model name RAS 2M10U2AVG E RAS 2M14U2AVG E RAS 2M18U2AVG E RAS 3M18U2AVG E NOTE Descriptions about operations for the 3 indoor units in this manual are not applicable to RAS 2M10U2AVG E RAS 2M14U2AVG E and RAS 2M18U2AVG E R32 ...

Страница 2: ...9 Test run 13 10 Pump down Operation 15 11 Troubleshooting 15 12 Appendix 16 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual attached to the indoor unit IMPORTANT NOTICE For details on how to install the indoor units refer to th...

Страница 3: ...t type is R32 this unit uses a flammable refrigerant If refrigerant leaks and comes in contact with fire or heating part it will create harmful gas and there is risk of fire Read the OWNER S MANUAL carefully before operation Service personnel are required to carefully read the OWNER S MANUAL and INSTALLATION MANUAL before operation Further information is available in the OWNER S MANUAL INSTALLATIO...

Страница 4: ... NEW REFRIGERANT AIR CONDITIONER INSTALLATION THIS AIR CONDITIONER USES THE NEW HFC REFRIGERANT R32 WHICH DOES NOT DESTROY THE OZONE LAYER R32 REFRIGERANT IS APT TO BE AFFECTED BY IMPURITIES SUCH AS WATER OXIDIZING MEMBRANES AND OILS BECAUSE THE PRESSURE OF R32 REFRIGERANT IS APPROX 1 6 TIMES OF REFRIGERANT R22 AS WELL AS THE ADOPTION OF THIS NEW REFRIGERANT REFRIGERATING MACHINE OIL HAS ALSO BEEN...

Страница 5: ...OR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE STOVES ETC WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R32 WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT THE GAS PRESSURE IN THE R...

Страница 6: ...rant inside the unit is flammable If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker it may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer from which you purchased the unit Do not use the unit until a service person confirms that the portion from which the refrig...

Страница 7: ...d the manual A dedicated circuit and the rated voltage must be used Insufficient power supply or improper installation may cause electrical shock or fire Use a cabtyre cable to connect wires in the indoor outdoor units Midway connection stranded wire and single wire connections are not allowed Improper connection or fixing may cause a fire Wiring between the indoor unit and outdoor units must be w...

Страница 8: ...on failure or excess current resulting in fire or electrical shock If you detect any damage do not install the unit Contact your supplying dealer immediately Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches Do not wash air conditioners with pressure washers Electric leaks may cause electric shocks or fires Be sure to comply with local re...

Страница 9: ...s for installation work Failure to do so may cause personal injury when handling parts with sharp edges Do not touch the air intake section or the aluminium fins of the outdoor unit It may cause injury Do not install the outdoor unit in a place which can be a nest for small animals Small animals could enter and contact internal electrical parts causing a failure or fire Request the user to keep th...

Страница 10: ...the above the safety protection functions may be activated Example of indoor unit class RAS B10UFV E1 is abbreviated as 10 Indoor unit class Standard connecting pipe diameter RAS 2M10U2AVG E RAS 2M14U2AVG E RAS 2M18U2AVG E RAS 3M18U2AVG E Unit C 07 or 10 or 13 6 35 9 52 mm Unit B 07 or 10 or 13 or 16 6 35 9 52 mm 6 35 9 52 mm 6 35 9 52 mm 3 6 35 9 52 mm 3 Unit A 07 or 10 or 13 or 16 6 35 9 52 mm 6...

Страница 11: ... if outdoor work is difficult you can change the procedure For example by making adjustments to the wiring and piping lengths on the inside rather than the outside When using an air conditioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install t...

Страница 12: ...time Use a different diameter joint if the diameters of the connection port and connection piping are different Mount the different diameter joint on the connection port of the outdoor unit CAUTION KEEP IMPORTANT 6 POINTS FOR PIPING WORK 1 Take away dust and moisture inside of the connecting pipes 2 Tighten the connections between pipes and unit 3 Evacuate the air in the connecting pipes using a V...

Страница 13: ... the fixed wiring 4 Disconnect the charge hose from the service port then open the valve stem fully using a 4 mm hexagon wrench Hexagon wrench is required Service port cap 4 mm Valve stem cap 5 Tighten the service valve stem cap and service port cap securely CAUTION Use a torque wrench and tighten the nut at the specified torque value 6 Tighten all the caps on the valves securely then perform a ga...

Страница 14: ...fied by the matching numbers on the terminal block of the indoor and the outdoor unit 5 Fix the wiring connections for the power source and each indoor unit securely using a cord clamp 6 Attach the terminal cover and the valve cover Stripping Length of connecting cable for outdoor unit 55 5 5 30 1 L 2 3 5 5 30 55 L N Earth screw Earth screw Power cord Connecting cable Unit A Earth screw Earth scre...

Страница 15: ... or less Also there is a possibility to misjudge if the indoor temperature becomes too low by cooling operation In that case execute the cooling operation for per room and check if the connection is normal Gas Leak Inspection Refer to the Gas Leak Inspection on page 12 Test run 1 If you perform the test run in summer start running in the cooling mode first to decrease the temperature of the room t...

Страница 16: ...lve at the liquid end 9 Make sure that the compound pressure gauge reading is 101 kPa 76 cmHg 10 Close the valve stem of the service valve at the gas end 11 The refrigerants collection operation is finished in maximum 10 minutes After the collection is finished promptly stop the operation of all the indoor unit There are cases that the compressor restarts 12 When you want to start over the operati...

Страница 17: ...ture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel freeze ester series PVE only of ether series The winding insulation of the co...

Страница 18: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116691098 1 ...

Отзывы: