Outdoor Unit
Installation Manual
6
Refrigerant piping
CAUTION
Install in rooms that are 5 m
3
or larger. If
a leak of refrigerant gas occurs inside the
room, an oxygen de
fi
ciency may occur.
Detaching the Valve cover
Remove the 5 screws.
• Pull the valve cover in the direction of the arrow, and remove it.
Valve cover
Refrigerant Piping Connection
Flaring
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Roughness
Warp
2. Remove the burr inside of the pipe.
When removing the burr, be careful so that chips do not fall into the pipe.
3. Remove the
fl
are nuts attached to the outdoor/indoor unit, then insert them
into each of the pipes.
4. Flare the pipes.
See the following table for the projection margin (A) and
fl
aring size (B)
B
A
Die
Pipe
Pipe
A
B
Flare Nut
Outside
diameter
Thickness
Rigid
(clutch
type)
R32 tool
Imperial
(wing
nut type)
R32 tool
Width
across
fl
at
Tighten torque
mm
mm
mm
mm
mm
mm
N•m
kgf•m
6.35
0.8
0 to 0.5
1.5 to
2.0
9.1
17
14 to
18
1.4 to
1.8
9.52
0.8
0 to 0.5
1.5 to
2.0
13.2
22
33 to
42
3.3 to
4.2
12.7
0.8
0 to 0.5
2.0 to
2.5
16.6
26
50 to
62
5.0 to
6.2
CAUTION
• Do not scratch the inner surface of the
fl
ared part when removing burrs.
• Flare processing under the condition of
scratches on the inner surface of
fl
are
processing part will cause refrigerant gas
leak.
Pipe connection
1. Make wire and pipe connections for each indoor unit separately.
2. Align the centres of the connecting pipes and tighten the
fl
are nut as much
as possible with your
fi
ngers, then tighten the nut using a torque wrench.
Be sure to tighten the nut at the speci
fi
ed torque value.
• If you use one outdoor unit for several indoor units of a different class,
connect the largest one
fi
rst A, then connect the rest in the order B to C.
• Do not remove the
fl
are nuts for any ports you are not going to use for
connection.
• Do not leave the
fl
are nut unattached for a long period of time.
• Use a different-diameter joint if the diameters of the connection port and
connection piping are different.
• Mount the different-diameter joint on the connection port of the outdoor
unit.
CAUTION
•
KEEP IMPORTANT 6 POINTS FOR
PIPING WORK.
(1) Take away dust and moisture (inside
of the connecting pipes).
(2) Tighten the connections (between
pipes and unit).
(3) Evacuate the air in the connecting
pipes using a VACUUM PUMP.
(4) Check gas leak (connected points).
(5) Be sure to fully open the packed
valves before operation.
(6) Reusable mechanical connectors
and
fl
ared joints are not allowed
indoors. When mechanical
connectors are reused indoors,
sealing parts shall be renewed.
When
fl
ared joints are reused
indoors, the
fl
are part shall be
refabricated.
Air Purge
From the sake of environmental protection, use a vacuum pump to extract the
air during installation.
* Prepare a 4 mm hexagon wrench.
1. Connect a charge hose.
• Make sure that the Handle Hi of the gauge manifold valve is closed fully.
• Connect the port of the gauge manifold valve and the service port
(Valve core (Setting Pin)) using the charge hose.
NOTE
If a control valve or charge valve is attached to the charge hose, leak
of R32 refrigerant can be avoided.
2. Open the Handle Low of the gauge manifold valve fully, then operate the
vacuum pump.
• Loosen
the
fl
are nut of the at the gas end a little to make sure that air is
taken in, then tighten the nut.
• If
you
fi
nd air is not taken in, make sure that the charge hose is
connected to the port(s) securely.
• Perform extraction for about 15 or more minutes and make sure that the
compound pressure gauge reading is –101 kPa (–76 cmHg).
• If the compound pressure gauge reading is not –101 kPa (–76 cmHg),
there is a possibility air is being taken in from the port(s).
• Make sure that the charge hose is connected to the port(s) securely.
3. Close the Handle Low of the gauge manifold valve fully, then stop
operating the vacuum pump.
• Leave the gauge and pump as they are for 1 or 2 minutes, then make
sure that the compound pressure gauge reading stays at –101 kPa (–76
cmHg).
• You need not add refrigerant.