Check the flare nut connections for the gas leak with
a gas leak detector or soap water.
Fig. 10-
6
-1
Check places
for outdoor unit
Check places for
indoor unit (Flarenut
connection)
Fig. 10-
6
-2
10-
6
-3. Test operation
To switch the TEST RUN (COOL) mode, press
Temporary switch
for 10 sec.
(
The unit will make a short Pi sound.)
Temporary switch
Fig. 10-
6
-
3
10-
6
-4. Auto restart setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
1. Press and hold the
Temporary switch
on the indoor unit
for
3 seconds to set the operation. (3
Pi
sound and
OPERATION lamp blink 5 time/sec for 5 seconds)
2. Press and hold the
Temporary switch
on the indoor
unit for 3 seconds to cancel the operation. (3
Pi
sound but OPERATION lamp does not blink)
•
In case of ON timer or OFF timer are set, AUTO
RESTART OPERATION dose not activate.
–
78
–
To separate using of remote control for each indoor
unit in case of 2 air conditioner are installed near.
Remote Control B Setup.
1. Press RESET button on the indoor unit to turn the air
conditioner ON.
2. Point the remote control at the indoor unit.
3. Push and hold
button on the Remote Control by
the tip of the pencil. "00" will be shown on the display.
Pre
ss
during pushing "B" will show on
the display and "00" will disappear and the air
conditioner will turn OFF. The Remote Control B
is memorized.
4.
Note :
2. Remote Control A has not “A” display.
3. Default setting of Remote Control from
factory
is A.
• When two indoor units are installed in the same room
or adjacent two rooms, if operating a unit, two units
may receive the remote control signal simultaneously
and operate. In this case, the operation can be
preserved by setting either one remote control to B
setting. (Both are set to A setting in factory shipment.)
• The remote control signal is not received when the
settings of indoor unit
and remote control are different.
•
There is no relation between A setting/B seting and
A room/B room when connecting the piping and
cables.
Repeat above step to reset Remote Control
to be A.
1
.
FILE NO. SVM-1
401
7
Information
10-
6
-
2
.
Remote Control A-B Selection
10-
6
.
Others
10-
6
-1.
Gas leak test