7-2. Operation Data
<Cooling>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 10G2KVP-E 1.0 to 1.2 13 to 15 40 to 42 High High 37
13G2KVP-E 0.9 to 1.1 12 to 14 41 to 43 High High 42
16G2KVP-E 0.8 to 1.0 11 to 13 42 to 44 High High 62
<Heating>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/- 7/6 10G2KVP-E 2.3 to 2.5 33 to 35 2 to 3 High High 48
13G2KVP-E 2.5 to 2.7 36 to 38 2 to 3 High High 44
16G2KVP-E 2.7 to 2.9 39 to 41 1 to 2 High High 64
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m