RAS-1
8
G2KCVP-T
/ RAS-1
8G2ACVP-T
NOTE :
•
Deoxidized copper pipe
Outer dia. : 12.7mm
Thickness : 0.8mm
NOTE :
Gas leak check position
Refrigerant flow
T1
TO
Temp. measurement
TC
TA
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allo
w
ab
le height
diff
erence :
10m
Allo
w
ab
le pipe length
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse Modulating
valve at liquid side
Compressor
DA131S1B-31FZ
Outdoor heat
exchanger
Refrigerant amount : 1.40kg
Propeller fan
OUTDOOR UNIT
Max. : 20m
Min. :
3
m
Chargeless : 15m
Strainer
Charge : 20g/m
(16 to 20m)
The maximum pipe length of this air conditioner is 20 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
Muffler
Accumulater tank
TD
TS
Muffler
FILE NO. SVM-15058
- 21 -