. REFRIGERANT CYCLE DIAGRAM
7
-1. Refrigerant Cycle Diagram
RAS-10
G2KCVP-T
/ RAS-10
G2ACVP-T
RAS-13
G2KCVP-T
/ RAS-13
G2ACVP-T
NOTE :
• The maximum pipe length of this air conditioner is 20m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
Deoxidized copper pipe
Outer dia. : 9.52mm
Thickness : 0.8mm
NOTE :
Gas leak check position
Refrigerant flow
T1
Temp. measurement
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allo
w
ab
le height
diff
erence :
10m
Allo
w
ab
le pipe length
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse Modulating
valve at liquid side
Compressor
DA108X1C-23FZ
Outdoor heat
exchanger
Propeller fan
Refrigerant amount : 1.10kg
OUTDOOR UNIT
TC
TA
Max.
: 20m
Min. : 1m
Chargeless : 15m
Charge : 20g/m
(16 to 20m)
TS
TD
Muffler
Temp. measurement
Ø1.2 x 80
s
Ø1.2 x 80
s
TO
Split capillary
TCJ
FILE NO. SVM-15058
- 20 -