
−
20
−
FILE NO. SVM-06001
5-
4
. RAS-10
N
KP-HX / RAS-10
N2
A-HX
Indoor unit
Cross flow fan
Cooling
Cooling Compressor
Heat exchanger
Propeller fan
Outdoor unit
RM5510GNE94
Cooling
Mark ( ) means check points of Gas Leak.
O.D.:9.52 mm
O.D.:6.35 mm
Cooling
Packed valve
(
∅
9.52)
Packed valve
(
∅
6.35)
0.39 m
(Connecting pipe)
9.52
0.49 m
(Connecting pipe)
∅
6.35
T1
P
Refrigerant
R22 : 0.75 kg.
Heat exchanger
Capillary tube
∅
1.5 x 1000
l
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
Standard 0.5
6
12.0 High 27/19 35/24
Cooling Overload 0.6
8
17.0 High 32/23 43/26
Low temperature
0.48
5.0
Low
21/15
21/15
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Fan speed
(indoor)
50Hz
Note
•
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
∅