TEMPORARY OPERATION

11

In case of the misplaced or discharged remote control
 

  Pressing the RESET button, the unit can start or stop 

without using the remote control.

 

  Operation mode is set on AUTOMATIC 

operation, preset temperature is 24°C 
and fan operation is automatic speed.

TIMER OPERATION

12

Everyday timer allows the user to set both the ON & OFF timers and will 
be activated on a daily basis.

Setting the ON Timer

Setting the OFF Timer

1

Press 

ON

 : Set the desired ON 

timer.

Press 

OFF

: Set the desired OFF 

timer.

2

Press 

SET

 : Set the timer.

Press 

SET

 : Set the timer.

3

Press 

CLR

 : Cancel the timer.

Press 

CLR

 : Cancel the timer.

 

•  Keep the remote control in accessible transmission to the indoor unit; 

otherwise, the time lag of up to 15 minutes will occur.

  •  The setting will be saved for the next same operation.

Note:

Setting Everyday Timer

1

Press

 

ON

 

: Set the ON timer.

3

Press 

SET

.

2

Press

 

OFF

 

: Set the OFF timer.

4

Press 

SET

 button during the (  or  ) 

mark 

fl

 ashing.

  •  During the every day timer is activating, both arrows (  ,  ) are indicated.

PRESET OPERATION

13

Set your preferred operation for future use. The setting will be memorized by the 
unit for future operation (except air

fl

 ow direction).

  1. Select your preferred operation.

  2. Press and hold 

PRESET

 for 3 seconds to memorize the setting. The 

P

 mark 

displays.

 3. 

Press 

PRESET

 : Operate the preset operation.

AUTO RESTART OPERATION

14

To automatically restart the conditioner after the power failure (Power of the 
unit must be on.)

Setting

  1. Press and hold the RESET button on the indoor unit for 3 seconds to set 

the operation. (3 beep sound and OPERATION lamp blink 5 time/sec for 5 
seconds)

    • Do not operate ON timer and OFF timer.
  2. Press and hold the RESET button on the indoor unit for 3 seconds to cancel 

the operation. (3 beep sound but OPERATION lamp does not blink)

To operate at super low fan speed for quiet operation (except in DRY mode)

 Press 

QUIET

 : Start and stop the operation.

 

Note:

 Under certain conditions, QUIET operation may not provide adequate 

cooling due to  low sound features.

To save energy while sleeping, automatically control air 

fl

 ow and automatically 

turn OFF.

 Press 

COMFORT

SLEEP

 : Select 1, 3, 5 or 9 hrs for OFF timer operation.

 

Note:

  The cooling operation, the set temperature will increase automatically 

1 degree/hour for 2 hours (maximum 2 degrees increase).

Indoor Unit and Remote Control

  •  Clean the indoor unit and the remote control with a wet cloth when 

needed.

  •  No benzine, thinner, polishing powder or chemically-treated duster.

QUIET OPERATION

15

COMFORT SLEEP OPERATION

16

SELF CLEANING OPERATION 

19

OPERATION AND PERFORMANCE

20

  1. Three-minute protection feature: To prevent the unit from being activated 

for 3 minutes when suddenly restarted or switched to ON.

  2. Some minor cracking sound may occur when unit operating. This is normal 

because the cracking sound may be caused by expansion / contraction of 
plastic.

Air conditioner operating conditions

Temp.

Operation

Outdoor Temperature

Room Temperature

Cooling

21°C ~ 43°C

21°C ~ 32°C

Dry

19°C ~ 43°C

17°C ~ 32°C

The unit does not operate.

Cooling is abnormally low.

•  The power main switch is turned 

off.

•  The circuit breaker is activated to 

cut off the power supply.

•  Stoppage of electric current
•  ON timer is set.

• The 

fi

 lters are blocked with dust.

•   The temperature has been set 

improperly.

•   The windows or doors are opened.
•   The air inlet or outlet of the outdoor 

unit is blocked.

•   The fan speed is too low.
•   The operation mode is FAN or 

DRY.

TROUBLESHOOTING (CHECK POINT)

21

REMOTE CONTROL A-B SELECTION

22

To separate using of remote control for each indoor unit in case of 2 air conditioners 
are installed nearly.

Remote Control B Setup.

  1. Press RESET button on the indoor unit to turn the air conditioner ON.
  2. Point the remote control at the indoor unit.
  3. Push and hold 

CHK 

 button on the Remote Control by the tip of the pencil. “00” 

will be shown on the display.

 4. 

Press 

MODE

 during pushing 

CHK 

. “B” will show on the display and “00” 

will disappear and the air conditioner will turn OFF. The Remote Control B is 
memorized.

Note:

 1.  Repeat above step to reset Remote Control 

to be A.

 

2.  Remote Control A has not “A” display.

 

3. Default setting of Remote Control from 

factory is A.

To start the sleep timer (OFF timer) operation

 Press 

SLEEP

 : Select 1, 3, 5 or 9 hrs for OFF timer operation.

SLEEP TIMER OPERATION

17

 Firstly, turn off the circuit breaker.

Filter Reset (Some models only)

FILTER lamp lights on; the 

fi

 lter must be cleaned.

To turn off the lamp, push the RESET button on the indoor unit or the FILTER 
button on the remote control.

MAINTENANCE

18

To protect bad smell caused by the humidity in the indoor unit.
 1. 

If 

the   button is pressed once during “Cool” or “Dry” mode, the fan will 

continue to run for other 20 minutes, then it will turn off automatically. This 
will reduce the moisture in the indoor unit.

  2. To stop the unit immediately, press the 

 3 times within 30 seconds.

Note:

  •  SELF CLEANING operation is default setting from factory.
  •  To cancel this function, press and hold the reset button on the indoor unit 

for 20 seconds.

    The SELF CLEANING operation will be cancelled. (5 beep sound but 

OPERATION lamp does not blink)

  •  Do the same to set this function again. (5 beep sound and OPERATION 

lamp blink 5 time/sec for 5 seconds)

  •  AUTO RESTART operation will be cancelled by setting or cancellation of 

SELF CLEANING operation. Set it again if necessary.

EN

Содержание RAS-07SKP-E

Страница 1: ...OWNER S MANUAL AIR CONDITIONER SPLIT TYPE For general public use Indoor unit RAS 07 13 SKP Series Outdoor unit RAS 07 13 S2A Series ENGLISH ESPAÑOL FRANÇAIS PУCСКИЙ ...

Страница 2: ...N 3 Do not move the louver manually by others The louver may automation positioning by come operation mode Note REMOTE CONTROL 4 PRESET ONE TOUCH QUIET SWING TIMER ON FILTER CHK CLOCK OFF CLR SLEEP SET FIX Hi POWER ECO PURE COMFORT SLEEP MODE TEMP FAN 5 4 3 9 8 7 6 1 1 Infrared signal emitter 2 Start Stop button 3 Mode select button MODE 4 Temperature button TEMP 5 Fan speed button FAN 6 Swing lou...

Страница 3: ...ND PERFORMANCE 20 1 Three minute protection feature To prevent the unit from being activated for 3 minutes when suddenly restarted or switched to ON 2 Some minor cracking sound may occur when unit operating This is normal because the cracking sound may be caused by expansion contraction of plastic Air conditioner operating conditions Temp Operation Outdoor Temperature Room Temperature Cooling 21 C...

Страница 4: ...OL REMOTO 4 1 Emisor de señales infrarrojas 2 Botón de funcionamiento parada 3 Botón selector de modo MODE 4 Botón de temperatura TEMP 5 Botón de velocidad del ventilador FAN 6 Botón de rotación del deflector SWING 7 Botón de ajuste de dirección FIX 8 Botón del temporizador de encendido ON 9 Botón del temporizador de apagado OFF Botón del temporizador de dormir SLEEP Botón de Configuración SET Bot...

Страница 5: ... o cuando ponga en ON el conmutador 2 Puede producirse algún pequeño sonido de rotura durante el funcionamiento de la unidad Esto es normal ya que el sonido de rotura podría causarse por la expansión contracción de plástico Condiciones de funcionamiento del acondicionador de aire Temp Funcionamiento Temperatura exterior Temperatura Ambiente Refrigeración 21 C 43 C 21 C 32 C Deshumidificación 19 C ...

Страница 6: ...ue TÉLÉCOMMANDE 4 1 Emetteur de signaux infrarouges 2 Touche de marche arrêt 3 Touche de sélection de mode MODE 4 Touche de réglage de la température TEMP 5 Touche de vitesse de ventilation FAN 6 Touche de balancement du volet de soufflage SWING 7 Touche de réglage de la claire voie FIX 8 Touche de mise en marche de la minuterie ON 9 Touche d arrêt de la minuterie OFF Touche de minuterie d arrêt a...

Страница 7: ...ndant 3 minutes environ en cas de remise en marche immédiate après un arrêt de l appareil 2 Quelques faibles sons de craquement peuvent se faire entendre pendant le fonctionnement de l appareil Ceci est normal car ces craquements peuvent être provoqués par l expansion la contraction du plastique Conditions de fonctionnement du climatiseur Temp Mode de fonctionnement Température extérieure Températ...

Страница 8: ...режима Пpимeчaниe ПУЛЬТ ДИСТАНЦИОННОГО УПРАВЛЕНИЯ 4 1 Излyчaтeль инфpaкpacного cигнaлa yпpaвлeния 2 Кнопкa пycкa оcтaновки 3 Кнопкa выбоpa peжимa MODE 4 Кнопкa тeмпepaтypы TEMP 5 Кнопкa cкоpоcти peжимa вeнтилиpовaния FAN 6 Кнопка качания жалюзи SWING 7 Кнопкa ycтaновки жaлюзи FIX 8 Кнопкa тaймepa включeния ON 9 Кнопкa тaймepa выключeния OFF Кнопкa тaймepa выключeния ycтaнaвливaeмого пepeд cном SLE...

Страница 9: ...йcтвa в тeчeниe 3 минyт пpи нeмeдлeнном повтоpном пycкe поcлe paботы или пpи ycтaновкe выключaтeля питaния в положeниe ON включeно 2 Во время работы блока возможен незначительный звук потрескивания Это нормально потому что причиной потрескивающего звука может быть расширение сжатие пластика Уcловия paботы кондиционepa Teмпepaтypa Peжим Наружная температура Комнатная температура Oxлaждeниe 21 C 43 ...

Страница 10: ...ة اﳌﺮﺷﺢ ﺗﻨﻈﻴﻒ ﻳﺠﺐ FILTER اﳌﺮﺷﺢ ﻣﺼﺒﺎح ﻳﻀﻲء اﳌﻮﺟﻮد FILTER اﳌﺮﺷﺢ زر او اﻟﺪاﺧﻠﻴﺔ اﻟﻮﺣﺪة ﻋﻠﻰ اﳌﻮﺟﻮد RESET اﻟﻀﺒﻂ اﻋﺎدة زر اﺿﻐﻂ اﳌﺼﺒﺎح ﻻﻃﻔﺎء ﺑﻌﺪ ﻋﻦ اﻟﺘﺤﻜﻢ ﻣﻮﺟﻪ ﻋﻠﻰ ١٨ ١٩ ٢٠ أو اﳌﻔﺎﺟﺊ اﻟﺘﺸﻐﻴﻞ إﻋﺎدة ﻋﻨﺪ دﻗﺎﺋﻖ ٣ ﳌﺪة اﻟﻮﺣﺪة ﺗﺸﻐﻴﻞ ﻟﺘﻔﺎدي ﻟﻠﺤﻤﺎﻳﺔ دﻗﺎﺋﻖ ﺛﻼث ﺧﺎﺻﻴﺔ ١ ON وﺿﻊ اﻟﻰ اﻟﺘﺤﻮل ان ﳝﻜﻦ اﻟﻄﻘﻄﻘﺔ ﺻﻮت ﻻن وذﻟﻚ ﻃﺒﻴﻌﻲ ﻫﺬا اﻟﻮﺣﺪة ﺗﺸﻐﻴﻞ ﻋﻨﺪ ﻗﻠﻴﻠﺔ ﻃﻘﻄﻘﺔ ﻳﺤﺼﻞ ان ﳝﻜﻦ ٢ اﻟﺒﻼﺳﺘﻴﻚ ﺗﻘﻠﺺ ﲤﺪد ﺳﺒﺒﻪ ﻳﻜﻮن اﻟﻬﻮاء ﻣﻜﻴﻔﺔ ﺗﺸﻐﻴﻞ ﻇﺮو...

Страница 11: ...ر 3 TEMP اﳊﺮارة درﺟﺔ زر 4 FAN اﳌﺮوﺣﺔ ﺳﺮﻋﺔ زر 5 SWING اﻟﺘﻬﻮﻳﺔ ﺷﻖ ﺗﺄرﺟﺢ زر 6 FIX اﻟﺘﻬﻮﻳﺔ ﺷﻖ ﺿﺒﻂ زر 7 ON اﻟﺘﺸﻐﻴﻞ ﻣﺆﻗﺖ زر 8 OFF اﻹﻳﻘﺎف ﻣﺆﻗﺖ زر 9 SLEEP اﻟﻨﻮم ﻣﺆﻗﺖ زر SET اﻟﺘﻬﻴﺌﺔ زر CLR اﻻﻟﻐﺎء زر PRESET اﳌﺴﺒﻘﺔ واﻟﺘﻬﻴﺌﺔ اﻟﺬاﻛﺮة زر ONE TOUCH اﻟﻮاﺣﺪة اﻟﻠﻤﺴﺔ زر Hi POWER اﻟﻘﺪرة ﻋﺎﻟﻲ زر ECO اﻻﻗﺘﺼﺎدي اﻟﺘﺸﻐﻴﻞ زر QUIET ﻫﺎدئ وﺿﻊ زر COMFORTSLEEP ﻫﺎدئ ﺳﻜﻮن وﺿﻊ زر FILTER اﳌﺮﺷﺢ ﺿﺒﻂ اﻋﺎدة زر CLOCK اﻟﺴﺎﻋﺔ ﺿﺒﻂ اﻋﺎدة زر ...

Страница 12: ... اﳌﺎﻟﻚ ﻛﺘﻴﺐ ﻋﺮﺑﻲ 1110250123 ﺳﺒﻠﺖ ﻃﺮاز ﻫﻮاء ﻣﻜﻴﻔﺔ اﻟﻌﺎم اﻻﺳﺘﻌﻤﺎل ﻓﻲ اﻟﺸﺎﺋﻊ اﻟﺪاﺧﻠﻴﺔ اﻟﻮﺣﺪة RAS 07 13 SKP Series اﳋﺎرﺟﻴﺔ اﻟﻮﺣﺪة RAS 07 13 S2A Series ...

Отзывы: