264
P9 ASD Installation and Operation Manual
OC1
Over-Current During
Acceleration
• Improper V/f setting.
• Restart from a momentary power outage.
• The ASD is starting into a rotating motor.
• ASD/Motor is not properly matched.
• Phase-to-phase short (
U
,
V
, or
W
).
•
Accel
time is too short.
•
Voltage Boost
setting is too high.
• Motor/machine is jammed.
• Mechanical brake is engaged while the ASD is running.
• ASD current exceeds 340% of the rated FLA on ASDs that are 100 HP or
less during acceleration. On ASDs that are greater than 100 HP, this fault
occurs when the ASD current exceeds 320% of the rated FLA during
acceleration.
OC1P
Overheat During
Acceleration
• Cooling fan is inoperative.
• Ventilation openings are obstructed.
• Internal thermistor is disconnected.
• Acceleration time is too short.
• Improper V/f setting.
• ASD or the motor is improperly matched to the application.
OC2
Over-Current During
Deceleration
• Phase-to-phase short (U, V, or W).
• Deceleration time is too short.
• Motor/machine is jammed.
• Mechanical brake is engaged while the ASD is running.
• ASD current exceeds 340% of the rated FLA on ASDs that are 100 HP or
less during deceleration. On ASDs that are greater than 100 HP, it occurs
when the ASD current exceeds 320% of the rated FLA during deceleration.
OC2P
Overheat During
Deceleration
• Cooling fan is inoperative.
• Ventilation openings are obstructed.
• Internal thermistor is disconnected.
• Deceleration time is too short.
• DC Injection current is too high.
• ASD or the motor is improperly matched to the application.
OC3
Over-Current During
Run
• Load fluctuations.
• ASD is operating at an elevated temperature.
• ASD current exceeds 340% of the rated FLA on ASDs that are 100 HP or
less during a fixed-speed run or if during a fixed-speed run the ASD
overheats. On ASDs that are greater than 100 HP, it occurs when the ASD
current exceeds 320% of the rated FLA on a fixed-speed run.
Note:
The event that caused the trip(s) must be corrected or must decrease to less than the threshold value
required to cause the trip to allow for a Reset to be recognized. In the event of multiple active trips,
the trip displayed will remain until all faults are corrected and cleared.
Table 15. P9 ASD Fault Listing. (Continued)
LED Screen
LCD Screen
Possible Causes/Troubleshooting
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......