8
P9 ASD Installation and Operation Manual
System Setup Requirements
•
With the exception of the
TBA Pump Number
), ensure that all
Time-Based Alternation
parameter settings and the real-time clock settings for each ASD within the system are the same.
•
When using the ASD as an integral part of a larger system, it is the responsibility of the ASD
installer/maintenance personnel to ensure that there is a fail-safe in place (i.e., an arrangement
designed to switch the system to a safe condition if there is a fault or failure).
•
Power factor improvement capacitors or surge absorbers
MUST NOT
be installed on the output of
the ASD.
•
Use of the built-in system protective features is highly recommended (i.e., E-Off, Overload
Protection, etc.).
•
The operating controls and system status indicators should be clearly readable and positioned
where the operator can see them without obstruction.
•
Additional warnings and notifications shall be posted at the equipment installation location as
deemed required by
.
•
System safety features should be employed and designed into the integrated system in a manner
such that system operation, even in the event of system failure, will not cause harm or result in
system damage or injury to personnel (i.e., E-Off, Auto-Restart settings, System Interlocks, etc.).
•
The programming setup and system configuration of the ASD may allow it to start the motor
unexpectedly. A familiarity with the
Time-Based Alternation
(
), (
Virtual Linear Pump)
Auto Start-Stop
),
Auto-Restart
(
), and the
Sleep Timer
(
) settings are a
requirement to use this product.
•
The setup procedures included within this manual may require a
Reset
before performing the
procedure. Application-specific settings may then be performed. The pre-Reset conditions may be
saved (see
•
There may be thermal or physical properties, or ancillary devices integrated into the overall system,
that may allow for the ASD to start the motor without warning. Signs to this effect must be posted
at the equipment installation location.
•
If a secondary magnetic contactor (MC) or an ASD output disconnect is used between the ASD and
the load, it should be interlocked to halt the ASD before the secondary contact opens. If the output
contactor is used for bypass operation, it must be interlocked such that commercial power is never
applied to the ASD output terminals (U, V, or W).
•
When using an ASD output disconnect, the ASD and the motor must be stopped before the
disconnect is either opened or closed. Closing the output disconnect while the 3-phase output of the
ASD is active may result in equipment damage or injury to personnel.
CAUTION
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......