– 86 –
NO.
Item
Specification outline
Remarks
11 A3-IPDU
control
IPDU controls inverter compressors by issuing commands relating to compressor
speeds, speed increases/decreases, and current release control values via the
interface P.C. board.
The main control functions of the IPDU P.C. board are described below.
1. Current release control
To prevent inverter input current from exceeding the specified value, output
frequency is controlled with AC input current as detected by T02 mounted on the
control P.C. board.
• A3-IPDU1, 2 and
3 are each
provided with a
TH sensor.
Zone C
Zone B
Zone A
Zone D
I
1
I
2
Current
Zone A:Compressors are operated normally.
Zone D:The current operating frequency is maintained.
Zone B:Operating frequency is lowered.
Zone C:The lowering of operating frequency is halted
to maintain the current frequency.
Current control values for various outdoor units are shown below.
Outdoor unit
HP capacity
I
1
I
2
14
12
10
8
18.5
14.5
19.0
15.0
18.0
14.0
18.5
14.5
2. Heat sink temperature detection control
1) This control function is aimed at protecting IGBT from overheating via a
thermistor (TH sensor) mounted in the compressor drive module (Q201) of A3-
IPDU.
2) When TH
≥
85 °C is detected, the fan operation mode is raised by one step,
followed by a series of additional step-ups right up to the highest mode at a rate
of one step/5 seconds.
3) After step 2), the normal fan mode is restored when TH falls to < 85 °C.
4) When TH
≥
105 °C, compressors are shut down.
5) Compressors are restarted 2 minutes and 30 seconds later, with an error count
of 1 recorded. If this is repeated four times (error count reaches 4), the error is
confirmed as final. The error [P07] is displayed. (There will be no more restarts.)
* Possible causes of the confirmed error include a heat buildup in the outdoor
unit, fan abnormality, blockage of the cooling duct, and IPDU P.C. board fault.
* The TH temperature used in this control function is the highest registered by
A3-IPDU1, A3-IPDU2, and A3-IPDU3.
3. Overcurrent protection control
1) When the overcurrent protection circuit on an IPDU P.C. board detects an
abnormal current, the compressor is shut down.
2) The compressor is restarted 2 minutes and 30 seconds later, with an error count
of 1 recorded. If the compressor successfully operates for at least 10 minutes
after a restart, the error count is cleared.
3) If the error count reaches 8, the error is confirmed as final.
4. High pressure SW control
1) When the high pressure SW of an inverter compressor is activated, the
compressor is shut down with an error count of 1 recorded.
2) The compressor is restarted 2 minutes 30 seconds later, and, if it successfully
operates for at least 10 minutes, the error count is cleared.
3) If the error count reaches 4, the error is confirmed as final. The error “P04” is
displayed.
• Connected to A3-
IPDU, the high-
pressure SW is
normally closed.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MMY-MAP0804FT7(Z)
Страница 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 46: ... 46 1 3 Flow Selector Unit RBM Y1123FE RBM Y1803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 53: ... 53 12 14HP Model MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 294: ... 294 MMY MAP0804FT8 Z ZG E MMY MAP1004FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 296: ... 296 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 297: ... 297 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 304: ... 304 MMY MAP0804FT8 Z ZG TR MMY MAP1004FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 306: ... 306 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 307: ... 307 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 313: ... 313 Outdoor unit MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 314: ... 314 MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 316: ... 316 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 317: ... 317 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 323: ... 323 Outdoor unit MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 324: ... 324 MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 326: ... 326 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 327: ... 327 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...