– 76 –
NO.
Item
Specification outline
Remarks
8 Cooling oil
(refrigerant)
recovery
control
While the outdoor unit is recovering cooling oil (refrigerant), the indoor units perform
the following control tasks:
[common for operational (cooling thermo ON / thermo OFF / FAN), as well as
nonoperational indoor units]
1) Open the indoor PMV to a certain degree.
2) Engage in recovery control for a specified period of time and return to normal
cooling operation at the end of this period upon terminating the control.
3) Operate the drain pump throughout the recovery control period and for about 1
minute after it.
• Recovery operation
normally takes
place roughly every
2 hours.
• The opening
position of the
indoor PMV
depending on the
type and capacity
of the indoor unit.
9 Heating
refrigerant (oil)
recovery
control
While the outdoor unit is recovering heating refrigerant (oil), the indoor units perform
the following control tasks:
1) Open the indoor PMV to a certain degree.
2) Control the indoor fan according to the operation mode.
[Indoor units operating in heating thermo ON/OFF state]
Let the indoor fan continue operating, but turn it off if the temperature of the indoor
heat exchanger drops.
[Indoor units operating in FAN mode]
Turn off the indoor fan and display “HEATING STANDBY
” on the remote
controller.
[Non-operational indoor units]
Keep the indoor fan turned off.
3) Terminate the recovery operation depending on the TC2 temperature reading.
The timing of termination is determined by each indoor unit.
4) Operate the indoor fan and drain pump for about 1 minute after the termination
of the recovery operation. (Applicable to 4-way cassette type, 2-way cassette
type and 1-way cassette type)
• Recovery
operation
normally takes
place roughly
every hour.
• The opening
position of the
indoor PMV
depending on the
type and capacity
of the indoor unit.
10 Defrosting
control
While the outdoor unit is engaged in defrosting control, the indoor units perform the
following control tasks:
1) Open the indoor PMV to a certain degree.
2) Control the indoor fan according to the operation mode.
[Indoor units operating in heating thermo ON/OFF state]
Let the indoor fan continue operating for a while, but turn it off as the temperature
of the indoor heat exchanger drops.
[Indoor units operating in FAN mode]
Let the indoor fan continue operating.
[Non-operational indoor units]
Keep the indoor fan turned off.
3) As defrosting control comes to an end, it gives way to heating refrigerant (oil)
recovery control.
(For control details, see “9. Heating refrigerant (oil) recovery control” above.)
• For defrosting
commencement
conditions, see
item of outdoor
unit, “7.
Defrosting control
(reverse defrosting
method)” above.
• The opening
position of the
indoor PMV
depending on the
type and capacity
11 Short
intermittent
operation
compensation
control
1. For 5 minutes after startup, the system is forced to continue operating even if it
reaches the thermo OFF region.
2. However, priority is given to cooling/heating selection, operation standby, and
protective control, so that there is no overriding of thermo OFF in these cases.
12 Drain pump
control
1. During cooling (including DRY operation), the drain pump is operated at all times.
2. If the float switch is activated while the drain pump is in operation, the drain pump
continues operating, with the relevant check code displayed.
3. If the float switch is activated while the drain pump is turned off, thermo OFF is
forced on the air conditioner, with the drain pump put into operation. If the float
switch continues to be activated for about 5 minutes, the drain pump is turned off,
with the relevant check code displayed.
Check code [P10]
13 Elimination of
residual heat
1. When the air conditioner is turned off after engaging in heating operation, the
indoor fan is operated for about 30 seconds in “breeze” mode.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MMY-MAP0804FT7(Z)
Страница 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 46: ... 46 1 3 Flow Selector Unit RBM Y1123FE RBM Y1803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 53: ... 53 12 14HP Model MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 294: ... 294 MMY MAP0804FT8 Z ZG E MMY MAP1004FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 296: ... 296 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 297: ... 297 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 304: ... 304 MMY MAP0804FT8 Z ZG TR MMY MAP1004FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 306: ... 306 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 307: ... 307 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 313: ... 313 Outdoor unit MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 314: ... 314 MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 316: ... 316 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 317: ... 317 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 323: ... 323 Outdoor unit MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 324: ... 324 MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 326: ... 326 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 327: ... 327 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...