– 235 –
8-8. Leakage/Clogging of Refrigerating Cycle Circuit
List of Check Codes Generated upon Occurrence of Leakage/Clogging in Outdoor Cycle or Oil
Circuit Part
(MMY-MAP0804
∗
, 1004
∗
,)
Clogging
Part
Outdoor PMV1, 2, 4
Outdoor PMV4 circuit check valve
SV14 valve
SV14 valve circuit check valve
Corresponding unit
A
Activation of high-pressure protection
Activation of low-pressure protection
Discharge temp. error (TD1)
Discharge temp. error (TD2)
P20
H06
P03
P17
Rise of abnormal pressure
Fall of pressure
Rise of discharge temp.
(compressor 1)
Rise of discharge temp.
(compressor 2)
Site of fault
(see next page)
Detected fault and check code
Check target unit
Symptom
Part
Site of fault
(see next page)
Detected fault and check code
Check target unit
Symptom
Check valve in discharge pipe
convergent section
SV11 valve
SV11 valve circuit check valve
Corresponding unit
B
High-pressure protection operation
High-pressure SW system error
P20
P04-XX
Abnormal rise of pressure
Check valve in discharge pipe
Corresponding unit
C
High-pressure SW system error
P04-XX
Abnormal rise of pressure
Check valve in oil-equalization circuit
Capillary
Strainer
Corresponding unit
D
Oil level detection circuit error
Oil level low detection and protection
H16-XX
H07-XX
Oil circuit error or oil
shortage judgment
SV3A valve
Other connected unit
E
Oil level low detection and protection
H07-XX
Oil level low
SV3B valve
Corresponding unit
F
Oil level low detection and protection
H07-XX
Oil level low
SV3C valve
Other connected unit
G
Oil level low detection and protection
H07-XX
Oil level low
Oil return distributor
Corresponding unit
J
Oil level low detection and protection
H07-XX
Oil level low
SV3C bypass capillary
Corresponding unit
K
Oil level detection circuit error
H16-04
Oil circuit error
SV3A valve
Corresponding unit
E
Oil level low detection and protection
H07-XX
Oil level low
SV3C valve
Corresponding unit
G
Oil level low detection and protection
H07-XX
Oil level low
Check valve in discharge pipe
convergent section
Corresponding unit
B
Oil level low detection and protection
Compressor breakdown
Compressor error (lockup)
H07-XX
H01-XX
H02-XX
Refrigerant entrapment
Check valve in discharge pipe
Corresponding unit
C
Oil level low detection and protection
Compressor breakdown
Compressor error (lockup)
H07-XX
H01-XX
H02-XX
Refrigerant entrapment
Outdoor PMV1, 2
Corresponding unit
A
Outdoor liquid backflow error
Oil level low detection and protection
P13
H07-XX
Refrigerant entrapment
Other connected unit Discharge temp. error (TD1)
Discharge temp. error (TD2)
P03
P17
Rise of discharge temp.
(compressor 1)
Rise of discharge temp.
(compressor 2)
Corresponding unit
Check valve in oil-equalization
circuit
D
Oil level low detection and protection
H07-XX
Excessive amount of oil
(Leaking side)
Insufficient amount of oil
(Normal side)
SV3E valve
Corresponding unit
I
Oil level detection circuit error
Oil level low detection and protection
H16-05
H07-XX
Oil circuit error
Oil level low
Oil level low
SV3D valve
SV3D valve circuit capillary
Strainer
Corresponding unit
H
Oil level low detection and protection
H07-XX
Oil level low
Leakage
Note:
“XX” represents sub-code
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MMY-MAP0804FT7(Z)
Страница 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 46: ... 46 1 3 Flow Selector Unit RBM Y1123FE RBM Y1803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 53: ... 53 12 14HP Model MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 294: ... 294 MMY MAP0804FT8 Z ZG E MMY MAP1004FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 296: ... 296 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 297: ... 297 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 304: ... 304 MMY MAP0804FT8 Z ZG TR MMY MAP1004FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 306: ... 306 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 307: ... 307 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 313: ... 313 Outdoor unit MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 314: ... 314 MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 316: ... 316 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 317: ... 317 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 323: ... 323 Outdoor unit MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 324: ... 324 MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 326: ... 326 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 327: ... 327 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...