Check code
Location
of
detection
System status
Description
Error detection
condition(s)
Check items (locations)
Outdoor 7-segment display
Main
remote
controller
Check
code
Sub-code
I/F
01: TS condition
P15
P15
P17
—
P17
All stop
Protective shutdown due to
sustained suction
temperature at or above
judgment criterion
for at least 10 minutes is
repeated four times or more.
<TS error judgment criterion>
In cooling operation: 60˚C
In heating operation: 40˚C
• Check for insufficiency in
refrigerant quantity.
• Check outdoor service valves
(discharge gas side, suction
gas side, liquid side) to
confirm full opening.
• Check PMVs (PMV1, 2, 4) for
clogging.
• Check resistance
characteristics of TS1 sensor.
• Check for defect in 4-way
valve.
• Check SV4 circuit for leakage
• Check SV5 circuit leakage.
• Check mispiping of discharge
gas/suction gas main pipes.
• Check Cool/Heat FS unit.
Check SVD valve, SVS valve
leakage.
(Check SVDD valve, SVSS
valve leakage.)
Connecting piping to FS unit
Mispiping of (discharge gas/
suction gas)
Gas
leakdetection
(TS1 condition)
I/F
All stop
Discharge temperature (TD2)
exceeds 115˚C.
• Check outdoor service valves
(discharge gas side, suction
gas side, liquid side) to
confirm full opening.
• Check outdoor PMVs
(PMV1, 2, 4) for clogging.
• Check resistance
characteristics of TD2 sensor.
• Check for defect in 4-way
valve.
• Check SV4 circuit for leakage.
• Check SV4 circuit (for wiring
or installation error involving
SV41, SV42 and SV43).
• Check SV5 valve circuit
leakage.
• Check SV6 circuit (Clogging,
valve operation error)
• Check mispiping of discharge
gas/suction gas main pipes.
• Check Cool/Heat FS unit.
Check SVD valve, SVS valve
leakage.
(Check SVDD valve, SVSS
valve leakage.)
Connecting piping to FS unit
Mispiping of (discharge gas/
suction gas)
Check wiring between FS unit
and indoor unit, connection of
connectors
Check miswiring of SVS/SVD
valve.
Discharge
temperature TD2
error
I/F
02: TD condition
All stop
Protective shutdown due to
sustained discharge
temperature (TD1, TD2 or TD3)
at or above 108˚C for at least
10 minutes is repeated four
times or more.
• Check for insufficiency in
refrigerant quantity.
• Check PMVs (PMV 1, 2, 4) for
clogging.
• Check resistance
characteristics of TD1, TD2
and TD3 sensors.
• Check indoor filter for
clogging.
• Check piping for clogging.
• Check SV4 circuit (for leakage
or coil installation error).
• Check mispiping of discharge
gas/suction gas main pipes.
• Check Cool/Heat FS unit.
Check SVD valve, SVS valve
leakage.
(Check SVDD valve, SVSS
valve leakage.)
Connecting piping to FS unit
Mispiping of (discharge gas/
suction gas)
Check wiring and connection
of connectors between FS
unit and indoor unit.
Check miswiring of SVS/SVD
valves.
Gas leak
detection
(TD condition)
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MMY-MAP0804FT7(Z)
Страница 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 46: ... 46 1 3 Flow Selector Unit RBM Y1123FE RBM Y1803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 53: ... 53 12 14HP Model MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 294: ... 294 MMY MAP0804FT8 Z ZG E MMY MAP1004FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 296: ... 296 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 297: ... 297 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 304: ... 304 MMY MAP0804FT8 Z ZG TR MMY MAP1004FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 306: ... 306 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 307: ... 307 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 313: ... 313 Outdoor unit MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 314: ... 314 MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 316: ... 316 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 317: ... 317 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 323: ... 323 Outdoor unit MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 324: ... 324 MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 326: ... 326 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 327: ... 327 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...