– 184 –
Check code
Location
of
detection
System status
Description
Error detection
condition(s)
Check items (locations)
Outdoor 7-segment display
Main
remote
controller
Check
code
Sub-code
I/F
F24
—
F24
All stop
Output voltage of Pd
sensor is zero
(sensor open-
circuited).
Pd > 4.15MPa
despite compressor
having been turned
off.
• Check connection of Pd sensor
connector.
• Check for defect in Pd sensor.
• Check for defect in outdoor P.C. board
(I/F).
Pd sensor error
Indoor unit
—
—
F29
Stop of
corresponding
unit
Indoor P.C. board
does not operate
normally.
• Check for defect in indoor P.C. board
(faulty EEPROM)
Other indoor error
I/F
F31
—
F31
All stop *1
Outdoor P.C. board
(I/F) does not
operate normally.
• Check power supply voltage.
• Check power supply noise.
• Check for defect in outdoor P.C. board
(I/F).
Outdoor
EEPROM error
IPDU
01:
Compressor 1 side
02:
Compressor 2 side
03:
Compressor 3 side
H01
H01
All stop
Inverter current
detection circuit
detects overcurrent
and shuts system
down.
• Check power supply voltage.
(AC380-415V ± 10%).
• Check for defect in compressor.
• Check for possible cause of abnormal
overloading.
• Check for defect in outdoor P.C. board
(A3-IPDU).
Compressor
breakdown
IPDU
01:
Compressor 1 side
02:
Compressor 2 side
03:
Compressor 3 side
H02
H02
All stop
Overcurrent is
detected several
seconds after startup
of inverter
compressor.
• Check for defect in compressor.
• Check power supply voltage.
(AC380-415V ± 10%).
• Check compressor system wiring,
particularly for open phase.
• Check connection of connectors/
terminals on A3-IPDU P.C. board.
• Check conductivity of case heater.
(Check for refrigerant entrapment inside
compressor.)
• Check for defect in outdoor P.C. board
(A3-IPDU).
• Check outdoor MG-CTT.
Compressor
error (lockup)
MG-CTT error
IPDU
01:
Compressor 1 side
02:
Compressor 2 side
03:
Compressor 3 side
H03
H03
All stop
Current flow of at
least specified
magnitude is
detected despite
inverter compressor
having been shut
turned off.
• Check current detection circuit wiring.
• Check defect in outdoor P.C. board
(A3-IPDU).
Current detection
circuit error
I/F
H05
—
H05
All stop
Discharge
temperature of
compressor 1 (TD1)
does not increase
despite compressor
being in operation.
• Check installation of TD1, TK1, TK2,
TK3, TK4, TK5 sensor.
• Check connection of TD1, TK1, TK2,
TK3, TK4, TK5 sensor connector and
wiring.
• Check resistance characteristics of TD1
sensor.
• Check for defect in outdoor P.C. board
(I/F).
TD1 sensor
miswiring
(incomplete
insertion)
I/F
H06
—
H06
*1 Total shutdown in case of header unit
Continued operation in case of follower unit
MG-CTT: Magnet contactor
All stop
Low-pressure Ps
sensor detects
operating pressure
lower than 0.02MPa.
• Check service valves to confirm full
opening (both discharge gas side, suction
gas side and liquid sides).
• Check outdoor PMVs for clogging
(PMV1, 2).
• Check for defect in SV2 or SV4 circuits.
• Check for defect in lowpressure
Ps sensor.
• Check indoor filter for clogging.
• Check valve opening status of indoor PMV.
• Check refrigerant piping for clogging.
• Check operation of outdoor fan (during In
single heating, collective operation).
• Check for insufficiency in refrigerant
quantity.
• Check clogging in circuit at auxiliary heat
exchanger liquid side .
(PMV4, Checked valve)
• Check 4-way valve error (Reversal error)
• Check miswiring of discharge/suction gas
main piping.
• Check Cool/Heat FS unit.
• Check mispiping of discharge/suction gas
piping to Cool/Heat FS unit.
• Check piping between Cool/Heat FS unit
and room.
• Check miswiring of SVD/SVS valve, and
mis mounting of coil.
• Check opened status of SVS valve.
• Check SV14 circuit error
Activation of
low-pressure
protection
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MMY-MAP0804FT7(Z)
Страница 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 46: ... 46 1 3 Flow Selector Unit RBM Y1123FE RBM Y1803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 53: ... 53 12 14HP Model MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 294: ... 294 MMY MAP0804FT8 Z ZG E MMY MAP1004FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 296: ... 296 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 297: ... 297 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 304: ... 304 MMY MAP0804FT8 Z ZG TR MMY MAP1004FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 306: ... 306 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 307: ... 307 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 313: ... 313 Outdoor unit MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 314: ... 314 MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 316: ... 316 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 317: ... 317 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 323: ... 323 Outdoor unit MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 324: ... 324 MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 326: ... 326 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 327: ... 327 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...