– 182 –
Check code
Location
of
detection
System status
Description
Error detection
condition(s)
Check items (locations)
Outdoor 7-segment display
Main
remote
controller
Check
code
Sub-code
I/F
Detected
outdoor unit
No.
E28
E28
All stop
Outdoor header unit receives
error code from outdoor
follower unit.
• Check check code displayed
on outdoor follower unit.
<Convenient functions>
If SW04 is pushed and held for
at least 1 second while [E28] is
displayed on the 7-segment
display of outdoor header unit,
the fan of the outdoor unit that
has been shut down due to an
error comes on.
If SW04 and SW05 are pushd
simultaneously, the fans of
normal outdoor units come on.
To stop the fan or fans, push
SW05 on its own.
Outdoor
follower unit
error
Indoor unit
—
—
F01
Stop of
corresponding
unit
Sensor resistance is infinity or
zero (open/short circuit).
• Check connection of TCJ
sensor connector and wiring.
• Check resistance
characteristics of TCJ sensor.
• Check for defect in indoor
P.C. board.
Indoor TCJ
sensor error
Indoor unit
—
—
F02
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TC2
sensor connector and wiring.
• Check resistance
characteristics of TC2 sensor.
• Check for defect in indoor
P.C. board.
Indoor TC2
sensor error
Indoor unit
—
—
F03
Stop of
corresponding
unit
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TC1
sensor connector and wiring.
• Check resistance
characteristics of TC1 sensor.
• Check for defect in indoor
P.C. board.
Indoor TC1
sensor error
I/F
F04
—
F04
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TD1
sensor connector.
• Check resistance
characteristics of TD1 sensor.
• Check for defect in outdoor
P.C. board (I/F).
TD1 sensor error
I/F
F05
—
F05
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TD2
sensor connector.
• Check resistance
characteristics of TD2 sensor.
• Check for defect in outdoor
P.C. board (I/F).
TD2 sensor error
I/F
01:
TE1 sensor error
02:
TE2 sensor error
F06
F06
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TE1/
TE2 sensor connectors.
• Check resistance
characteristics of TE1/TE2
sensors.
• Check for defect in outdoor
P.C. board (I/F).
TE1/TE2 sensor
error
I/F
F07
—
F07
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TL
sensor connector.
• Check resistance
characteristics of TL sensor.
• Check for defect in outdoor
P.C. board (I/F).
TL sensor error
I/F
Symbol O
signifies site of
IPDU error.
E31
E31
All stop
Communication is disrupted
between IPDUs (P.C. boards)
in inverter box.
• Check wiring and connectors
involved in communication
between IPDU-I/F P.C. board
for bad contact or broken wire.
• Check for defect in outdoor
P.C. board (I/F, A3-IPDU or
Fan IPDU).
• Check for external noise.
IPDU
communication
error
Sub MCU
communication
error
80
All stop
Communication between MCU
and Sub MCU stopped.
• Operation of power supply
reset (OFF for 60 seconds
or more)
• Outdoor I/F PC board error
check
Communication
error between MCU
and Sub MCU
1
O
O
O
O
O
O
O
O
2
O
O
O
O
O
O
O
O
3
O
O
O
O
O
O
O
O
A3-IPDU Fan
IPDU
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
80
O
O
O
O
O
O
O
O
Sub
MCU
O
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MMY-MAP0804FT7(Z)
Страница 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 46: ... 46 1 3 Flow Selector Unit RBM Y1123FE RBM Y1803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 53: ... 53 12 14HP Model MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 294: ... 294 MMY MAP0804FT8 Z ZG E MMY MAP1004FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 296: ... 296 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 297: ... 297 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 304: ... 304 MMY MAP0804FT8 Z ZG TR MMY MAP1004FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 306: ... 306 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 307: ... 307 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 313: ... 313 Outdoor unit MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 314: ... 314 MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 316: ... 316 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 317: ... 317 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 323: ... 323 Outdoor unit MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 324: ... 324 MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 326: ... 326 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 327: ... 327 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...