7-6-2. Single cooling/Single heating Test Operation Check
The Single cooling/Single heating test operation check can be performed on both the indoor remote controller
and the outdoor header unit interface PC board.
(1) Test operation start/stop operation
Test operation from the indoor remote controller
• Wired remote controller: Refer to the items below in “Test operation” of the wired remote controller.
• Wireless remote controller: Refer to the items below in “Test operation” of the wireless remote controller.
• Lite-Vision plus remote controller : Refer to the installation manual of RBC-AMS51E
Wired remote controller
Wireless remote controller (Except the 4-
way Cassette type and the Ceiling type)
Test run (Forced cooling operation)
Requirement:
• Finish the forced cooling operation in a short
time because it applies excessive strength to the
air conditioner.
How to perform forced cooling operation
1.
When TEMPORARY button is pushed for 10
seconds or more, “Pi!” sound is heard and the
operation changes to a forced cooling operation.
After approx. 3 minutes, a cooling operation starts
forcedly.
Check cool air starts blowing. If the operation does
not start, check wiring again.
2.
To stop a test operation, push TEMPORARY
button once again (Approx. 1 second).
• Check wiring / piping of the indoor and outdoor
units in forced cooling operation.
1, 5
3
2, 4
Operation content
Procedure
1
2
When the Test button is pushed for 4 seconds or
more, “TEST” is displayed in the display section,
and the unit enters test operating mode.
5
Push the Test button to clear the test operating mode.
(“TEST” disappears from the display section, and
the status returns to the normal stopped status.)
3
Using the Select Mode button, select the
“ COOL” or “ HEAT” operating mode.
• Do not use an operating mode other than
“ COOL” or “ HEAT”.
• Temperature adjustment is unavailable during
test operation.
• Error is detected as usual.
Push the button.
4
When the test operation has finished, push the
button to stop the operation.
(The same display as in procedure 1 appears in
the display section.)
TEMPORARY-Taste
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MMY-MAP0804FT7(Z)
Страница 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 46: ... 46 1 3 Flow Selector Unit RBM Y1123FE RBM Y1803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 53: ... 53 12 14HP Model MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 294: ... 294 MMY MAP0804FT8 Z ZG E MMY MAP1004FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 296: ... 296 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 297: ... 297 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 304: ... 304 MMY MAP0804FT8 Z ZG TR MMY MAP1004FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 306: ... 306 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 307: ... 307 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 313: ... 313 Outdoor unit MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 314: ... 314 MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 316: ... 316 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 317: ... 317 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 323: ... 323 Outdoor unit MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 324: ... 324 MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 326: ... 326 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 327: ... 327 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...