– 111 –
6-8-1. Power peak-cut Control (Standard): TCB-PCDM4E
PJ17
CN513
SW07
TB1
[ON]
[OFF]
TB2
COM
ON
COM
OFF
Bit 2 OFF
L1
SW1
SW2
SW2
SW1
ON
OFF
1 2 3 4
Connection cable
Locally procured
[OPERATION]
L1: Display lamp suring power peak cut control
Optional PCB
Header outdoor unit
Outdoor unit
interface PCB
Display
relay
Power
supply
Shield
wire
Shield
wire
For SW1 and SW2, be sure to provide no-
voltage contacts for each terminal.
The input signals of SW1 and SW2 may be pulse
input (100 msec or more) or continuous make.
Interface P.C. board of header outdoor unit
SW07 Bit 1 ON
SW07 Bit 1 OFF
Power peak-cut control P.C.
board
Power peak-cut control ON
signal received
SW1
ON
OFF
0% (forced stop)
60% capacity (upper limit regulated)
ON
Power peak-cut control OFF
signal received
OFF
ON
100% (normal operation)
100% (normal operation)
OFF
SW2
L1
PJ17
TB1
TB2
COM
ON
COM
OFF
CN513
SW07
Bit 2 ON
L1
SW1
ON
OFF
1 2 3 4
[ON]
[OFF]
Connection cable
Locally procured
[OPERATION]
L1: Display lamp suring power peak cut control
Optional PCB
Header outdoor unit
J16 Cut
Shield wire
Shield wire
Outdoor unit
interface PCB
Display
relay
Power
supply
Operation
An external power peak-cut control signal limits the peak capacity of the outdoor unit.
L1: Power peak-cut control indication lamp
SW1: Power peak-cut control ON switch (ON as long as target power peak-cut control has been reached or
exceeded, normally OFF)*1
SW2: Power peak-cut control OFF switch (OFF as long as target power peak-cut control has not been reached
or exceeded, normally ON)*1
*1 The inputs of SW1 and SW2 can be either pulse (100 msec or wider) or step signals.
Do not turn on SW1 and SW2 simultaneously.
* Be sure to provide a contact for each terminal.
Power peak-cut control settings
Two-core cable support <only available with SHRS-i and SMMS-i (4 series)>
SMMS-i series allows ON/OFF power peak-cut control to be implemented using a power peak-cut control ON
input (SW1) alone, provided that the J16 jumper wire on the interface P.C. board of the header outdoor unit has
been removed.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MMY-MAP0804FT7(Z)
Страница 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 46: ... 46 1 3 Flow Selector Unit RBM Y1123FE RBM Y1803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 53: ... 53 12 14HP Model MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 294: ... 294 MMY MAP0804FT8 Z ZG E MMY MAP1004FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 296: ... 296 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 297: ... 297 MMY MAP1204FT8 Z ZG E MMY MAP1404FT8 Z ZG E AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 304: ... 304 MMY MAP0804FT8 Z ZG TR MMY MAP1004FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 306: ... 306 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 307: ... 307 MMY MAP1204FT8 Z ZG TR MMY MAP1404FT8 Z ZG TR AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 313: ... 313 Outdoor unit MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 314: ... 314 MMY MAP0804FT8 Z ZG MMY MAP1004FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 316: ... 316 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 317: ... 317 MMY MAP1204FT8 Z ZG MMY MAP1404FT8 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 323: ... 323 Outdoor unit MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 324: ... 324 MMY MAP0804FT7 Z ZG MMY MAP1004FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 326: ... 326 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 327: ... 327 MMY MAP1204FT7 Z ZG MMY MAP1404FT7 Z ZG AMP Air Conditioning www ampair co uk sales ampair co uk ...