156
No. Component
Procedure
Remarks
⑤
Inverter
assembly
(continued)
5) Remove the terminal cover of the compressor,
and disconnect the compressor leads from the
compressor.
WARNING
The fast-on terminals of the compressor
lead wires may become loose when they
are disconnected. When reconnecting them,
crimp them slightly with radio pliers or the
like and ensure they are not loose before
reinsertion. The fast-on terminals could
overheat and cause a fire if loose.
6) Remove the screws of the inverter assembly
and inverter fixing plate (lower).
(M4×10, 1 )
7) Lift up on the inverter assembly and move it
forward and out.
Inverter assembly
Inverter assembly
●Remove the inverter assembly.
Screw (1 position)
Thermostat
Compressor leads
Black
Red
Put on the
sleeve.
White
Notes on Compressor Leads
• Connect each compressor lead wire to its
designated terminal.
• Do not press the fast-on terminals twice.
• After disconnecting the fast-on terminals that
have been inserted once, replace the
compressor leads.
• Make sure to keep the exposed compressor
lead wires straight.
• Be careful not to apply excess stress to the
terminals and lead wires.
• Attach the terminal cover after passing the
lead wires through the bushing. At this time, be
careful not to let the lead wires get caught in
the gap with the terminal cover.
Screw (1 position)
Thermostat
Compressor leads
Black
Red
Put on the
sleeve.
White
Notes on Compressor Leads
• Connect each compressor lead wire to its
designated terminal.
• Do not press the fast-on terminals twice.
• After disconnecting the fast-on terminals that
have been inserted once, replace the
compressor leads.
• Make sure to keep the exposed compressor
lead wires straight.
• Be careful not to apply excess stress to the
terminals and lead wires.
• Attach the terminal cover after passing the
lead wires through the bushing. At this time, be
careful not to let the lead wires get caught in
the gap with the terminal cover.