Toshiba LC531 Series Скачать руководство пользователя страница 1

 

 

 

 

 

Unified Controller

 

 

 

Single-Loop Controller LC531/LC532 

 

 

Instruction Manual

 

 
 

6F8C1388 

Содержание LC531 Series

Страница 1: ...Unified Controller Single Loop Controller LC531 LC532 Instruction Manual 6F8C1388 ...

Страница 2: ...n herein may be changed in the future without notice 4 All possible measures have been taken to prepare the information herein If you have any question comment or find any error please contact us PROSEC TOSLINE TOSDIC CIEMAC are trademarks or registered trademarks of Toshiba Corporation Microsoft Windows are registered trademarks of Microsoft Corporation in the U S and other countries PROFIBUS is ...

Страница 3: ...mage 3 1 A serious injury indicates loss of sight injury burns high low temperature electric shock broken bones or intoxication that will have aftereffects and require hospitalization or long term hospital visits for healing 2 An injury indicates an injury burn or electric shock that does not need hospitalization or long term hospital visits for healing 3 A property damage indicates consequential ...

Страница 4: ...xceeding the allowed values A place with condensations due to rapid temperature changes A place with low or high temperature outside of the installation condition A place with high humidity outside of the installation condition A place with direct sunlight A place near equipment generating strong radio waves or magnetic fields Mandatory Install the device in a place where maintenance and inspectio...

Страница 5: ...se failure Mandatory Before touching the device module or board touch a grounded metal to discharge the static electricity of your body Otherwise it may cause malfunction or failure due to static electricity Mandatory Wipe off stain on the device module or board with a soft cloth For severe stain use a wet cloth wrung tightly Leaving them stained may cause improper judgment or malfunction Mandator...

Страница 6: ... may cause damage of the device or fire due to overheat as well as not obtaining the original performance of the device Prohibited Do not disassemble or modify the device modules or boards This will erode the device s safety and can cause erroneous operation or failure For repair of the equipment modules or boards contact Toshiba service representative Mandatory When the ambient or internal temper...

Страница 7: ...d Do not forcefully bend pull or twist the power cord and cables It may cause breaks or heating Prohibited Do not insert or drop metallic objects or clips into the device through any opening in the device It may cause fire Mandatory If parameters or an application program is changed write data to flash ROM using the Tool RAM memory backup will be available for 6 months 6 Safety Precautions on Disp...

Страница 8: ...tory Observe the care mark indicated on the packaged box during transportation and storage Modules may be damaged if the care mark is not observed Do not give shock to the product during transportation and storage Products are stored in a conductive mat and then packaged ...

Страница 9: ...systems and air traffic control systems Note 3 Special considerations means to have sufficient discussions with Toshiba s engineers to construct a safe system e g employing fool proof design fail safe design or redundant design Disclaimer Toshiba shall not be responsible for any damage caused by an fire earthquake for which Toshiba is not responsible for acts of a third party other accidents the u...

Страница 10: ...r with other means of backup Control output Inappropriate program or parameter values set with the Tool could adversely affect controller output stability and system performance Check for controller output stability with a simulation program for example in advance to verify that there will be no problem with connecting the product to your system Interlock design If there is a possibility of seriou...

Страница 11: ...anel wipe it with tissue paper or a soft cloth dipped in lukewarm water Do not use organic solvents or chemicals because such substances could cause discoloration Dielectric test Observe the following in making a dielectric test on the product Apply the AC voltage 500 VAC between the power terminal and grounding terminal on the terminal board and check that nothing abnormal occurs Before conductin...

Страница 12: ... point of danger This label is attached to points or places on the product where there is a possibility of electric shock or of product breakdown due to wrong wiring etc Pay attention to the following when you see this symbol Touching the power input terminals on a live power module has the great danger of causing electric shock Do not touch the power input terminals For safety be sure to switch p...

Страница 13: ...unding CHAPTER 3 SOFTWARE FUNCTIONS Describes program operations variables and standard inputs and outputs CHAPTER 4 REGISTRATION AND SETTING USING ENGINEERING TOOL Describes hardware configuration registration module parameter setting and tag registration using system examples CHAPTER 5 STARTUP AND STOPPING Describes how to check switches how to start and stop and the operation modes CHAPTER 6 SI...

Страница 14: ...e product correctly Note Describes what the user should observe to handle the product correctly Remark Describes a remark Related documents Unified Controller nv series Integrated Controller V series Engineering Tool 4 Basic 6F8C1290 Programming Instructions Manual 6F8C1226 PLC Server Engineering Tool Ver 2 0 Instruction Manual 6F8C1038 OIS DS SMART PLC Connection Function Instruction Manual 6F8C1...

Страница 15: ...Loop display front 15 1 2 2 Switch area side display side keyboard area side 19 1 2 3 Terminal block part back 22 Chapter 2 Installing Removing and Connection 25 2 1 Before Starting Work 26 2 1 1 Working conditions 26 2 1 2 Working procedures 26 2 2 Installing or Removing the LC531 LC532 28 2 2 1 LC531S S LC532S S housing depth 450mm 28 2 2 2 LC531E S LC532E S housing depth 250mm 30 2 2 3 Removing...

Страница 16: ...ration and Setting Using Engineering Tool 55 4 1 Example of System Configuration 57 4 2 Hardware Configuration Registration 58 4 2 1 Hardware configuration registration 58 4 2 2 Network registration 61 4 2 3 Module parameter registration 63 4 3 Tag Registration 64 4 3 1 Registration of tag editor and tag parameter 64 4 4 Variable Registration 71 4 4 1 Registration of standard variables 71 4 4 2 Re...

Страница 17: ...er controller transmission 81 Chapter 5 Startup and Stopping 83 5 1 Checking Switches 84 5 2 Starting Up 85 5 2 1 Display on the loop display during startup 86 5 2 2 Memory clear download and startup 86 5 3 Stopping 87 5 4 Transition of Operation Mode 88 5 5 Operation Mode Display 89 5 6 Control Operation during Startup and Stop 89 Chapter 6 Side Keyboard and Side Display 91 6 1 Side Keyboard and ...

Страница 18: ...8 4 2 Replacing the scale plate 115 Appendix A LC531 LC532 Specifications 117 A 1 General Specifications 119 A 2 Electric and External Specifications 120 A 3 I O Specifications built in 121 A 4 RS485 Communication Specifications 122 A 5 Ethernet Transmission Specifications 122 A 6 USB Specifications 123 A 7 LC531 LC532 Wiring Diagram 124 A 8 LC531 LC532 Software Specifications 125 Appendix B Detai...

Страница 19: ...iables PV_PARA PV_DATA 161 E 2 2 Controller Variables LP_PARA LP_DATA 168 E 2 3 Pushbutton Variables PB_PARA PB_DATA 174 E 3 Built in I O Variables SIO1 177 E 4 EC Bus Variables EC_BUS 178 E 5 Inter controller Transmission Variables STN_DATA 180 F 1 Module Parameter Setting 182 F 2 Module Parameter Data Display 183 G 1 Execution Performance of the LC531 LC532 186 G 2 Main Scan and Free Time 187 Ap...

Страница 20: ...e 198 H 2 7 Display the Version 199 H 2 8 Change the Controller Control Cycle MS task scan cycle 199 H 2 9 Restore the MV Error MVE 200 I 1 Making USB Connection for the First Time 201 I 2 USB Driver Installation 203 I 3 Setting the nv Engineering Tool and Communication Parameters 206 J 1 How to take a reference number 208 J 2 Reference number list 208 J 3 Raw data structure 217 Appendix H Details...

Страница 21: ...us transmission 5 1 1 3 Connection with the CIEMAC DS system via the PLC server 6 1 1 4 Connection with the S3 controller via the Ethernet module 7 1 1 5 Connection with the PU811 controller via the Ethernet module 9 1 1 6 Connection with the Remote I O via the MODBUS 11 1 1 7 Connection with the PUM1 controller via the Ethernet module 12 1 2 Names and Functions of the LC531 LC532 14 1 2 1 Loop di...

Страница 22: ...ation programs Characteristics LC53 offers the following characteristics Loop display It has the loop display function that allows instrument display and operation of up to 8 loops PID control For PID control our proprietary Hyper PID control advanced two degree of freedom PID control is adopted for execution of PID control of up to 8 loops Build in I O s It has analog input 6 channels MV output 2...

Страница 23: ...on Manual 3 Network installation It has the Ethernet communication port and RS485 communication port allowing connection with other LC53 units connection with other controllers and connection with the monitoring system for data exchange or display operation and monitoring from the monitoring system ...

Страница 24: ...small scale systems via Ethernet transmission 1 Up to 16 units of the LC53 can be connected to the OIS DS SMART via Ethernet transmission For the OIS DS SMART refer to OIS DS SMART PLC Connection Function Instruction Manual 6F8C1039 2 In addition inter controller transmission can be performed among the LC53 s For details refer to Appendix E 5 Inter controller Transmission Variables STN_DATA Figure...

Страница 25: ...t the monitoring scanner function and EC bus communication protocol Connect the nv Engineering Tool to the Ethernet communication port of the LC53 via a hub It is also possible to connect the nv Engineering Tool to the Ethernet communication port of the LC53 without using any hub In this case use a cross type Ethernet transmission cable Refer to Appendix J MODBUS The reference specification for th...

Страница 26: ...ler Transmission Variables STN_DATA Figure 1 3 Example of connection between the CIEMAC DS and LC53 Remark For information on how to use the PLC server refer to PLC Server Engineering Tool Ver 2 0 Instruction Manual 6F8C1038 The PLC server can monitor connect with up to 64 LC53 units Connect the nv Engineering Tool to a hub via Ethernet The PLC server collects the data of LC53 at one cycle of the ...

Страница 27: ...ation of the S3 controller refer to 4 6 Registration of S3 Controller Using Inter Controller Transmission For details of the S3 controller refer to Sequence Controller S3 User s Manual Functions 6F8C0908 Figure1 4 Example of connection between the S3 controller and LC53 Remark Controllers and versions which allow inter controller transmission with the LC53 are as follows Equipment Software format ...

Страница 28: ...S3 controller is duplicated you must start from configuration of the IP address during switch over promotion To start inter controller transmission specify the size of an inter controller transmission variable for N size of the USEND_T command command 16 0320 An incorrect size results in error STATUS 5001 When the S3 controller is duplicated user tracking is required for the inter controller trans...

Страница 29: ... 4 7 Registration of PU811 Controller Using Inter Controller Transmission For details of the PU811 controller refer to Sequence Controller type1 User s Manual Functions 6F8C0908 Figure1 5 Example of connection between the PU811 controller and LC53 Remark Controllers and versions which allow inter controller transmission with the LC53 are as follows Equipment Software format Version PU811 SHTYPE1A ...

Страница 30: ...ecify the size of an inter controller transmission variable for N size of the USEND_N command command 16 0920 An incorrect size results in error STATUS 5001 When the PU811 controller is duplicated user tracking is required for the inter controller transmission variable Make sure to specify user tracking Turn ON the engineering switch No 4 of the LC53 The PU811 EN911 cannot receive data when the sw...

Страница 31: ...53 version V01 20 or higher V01 21 or higher V01 21 or higher Note Remote I O station can be connected to one unit only However when MODBUS General is selected a different station number can be specified for each module The following table shows the remote I O s that allow MODBUS connection For remote I O s other than the followings the connection can be made by selecting MODBUS General In this ca...

Страница 32: ...sion variables of the LC53 refer to Appendix E 5 Inter controller Transmission Variables STN_DATA For registration of the PUM1 controller refer to 4 8 Registration of PUM1 Controller Using Inter Controller Transmission For details of the PUM1 controller refer to nv series type1 light Controller Unit User s Manual Functions 6F8C1498 UNIT1 3 HUB Ethernet 192 168 n 1 IF661 PUM1 EN651A IF658 EN655 192...

Страница 33: ...cation socket communication computer link and PC link Use one of the PUM1 controller sockets this means one less socket for socket communication To start inter controller transmission specify the size of an inter controller transmission variable for N size of the USEND_N command command 16 0320 An incorrect size results in error STATUS 5001 When the PUM1 controller is duplicated you must start fro...

Страница 34: ...8C1388 14 1 2 Names and Functions of the LC531 LC532 The figure below shows the appearance of the single loop controller LC53 Figure 1 7 Appearance of the LC53 Loop display Side keyboard LC53 main unit Side display Loop display operation area Loop display area ...

Страница 35: ...ade with manual operation switch mode automatic mode Executes automatic control in accordance with the specified control algorithm mode remote setting value Executes cascade control ratio control or executes control based on the set value sent from host computer FAST SEL 0 10 20 30 40 50 60 70 80 90 100 0 20 40 60 80 100 HLT L P P V SV M V SV MV 7 HALT display red 8 ALARM display red 9 CMP display...

Страница 36: ...lution Underflow and overflow indication points are provided To change the speed of this operation refer to 11 FAST SEL pushbutton 5 SV bar graph This bar graph indicates SV with 1 resolution Like the PV indicator bar graph this bar graph can indicate SV value for loops 1 to 8 If a process high low alarm occurs the normal bar graph range blinks In addition using switch this blinking can be stopped...

Страница 37: ...alues are in display displayed digits 5 The current display can be checked with 16 Status display The current loop value can be checked with 13 Loop number display For other numerical information display refer to Appendix B 5 Special Display in the Numerical Display Area 11 FAST SEL pushbutton If this button is used simultaneously with the MV manual operation pushbuttons or SV setting pushbuttons ...

Страница 38: ...1 LC532 6F8C1388 18 16 Status display The target type PV SV or MV for numerical display is displayed 17 USB communication port The nv Engineering Tool or maintenance tool can be connected directly 18 TAG No plate The TAG number is written on the plate ...

Страница 39: ...e view Left Side View Right Side View Mounting fixture Del HeIp lns Esc 3 2 1 ABC MNO DEF 6 5 4 9 8 7 TUV GHI PQRS JKL VWXYZ Enter 0 Maintenance switch Status indicator LED Rotary switch 0 to F Engineering selection switch Battery Side display Stopper 2 Stopper 1 Side keyboard RUN TX RX LNK 100M 10M Maint SW Eng SW STN H L BATTERY CR2032 Terminal part Housing LC53 main unit LC53 main unit Loop dis...

Страница 40: ...nate with an error ON Restart 7 Ethernet Class setting 8 7 8 Class OFF OFF ClassC 192 168 0 ON OFF ClassC 192 168 1 OFF ON ClassB 172 16 64 ON ON Remark The DIP switch setting values are read when the power is turned on The settings are not reflected when they are changed during execution For memory clear engineering switch SW No 1 operation refer to 5 2 2 Memory clear download and startup If the ...

Страница 41: ...d 100Mbps 10M Ethernet transmission speed 10Mbps Table 1 4 Other parts of the LC53 Part Usage Remark Battery This battery protects internal information in case of power failure Model name CR2032 lithium battery Stopper 1 These stoppers fix the LC53 module to the housing To operate the side display and keyboard draw it out while pressing it upward Stopper 2 For unit replacement draw it out while pr...

Страница 42: ...ance switch Figure 1 10 Back of LC53 and terminal block RS485 terminating resistance switch When connecting the LC53 via EC bus transmission set the RS485 terminating resistance switch to ON at the LC53 unit located at the end For other units set it to OFF Remark For the termination process for EC bus transmission refer to 2 3 2 EC bus transmission termination process Ethernet communication port R...

Страница 43: ...output referenced to signal common 15 to 16 MV current output 1 to 2 4 20mA output referenced to 0V LC531 only 17 to 19 Contact input 1 to 3 One side of the contact is connected to power supply common for DIO 24V 5mA input 20 to 24 Digital output 1 to 5 One side of load is connected to DC power supply for DIO open collector 0 1A output TB1 terminal block Left side This is the terminal block to con...

Страница 44: ...Chapter 1 Overview of Single Loop Controller LC531 LC532 6F8C1388 24 ...

Страница 45: ...using depth 450mm 28 2 2 2 LC531E S LC532E S housing depth 250mm 30 2 2 3 Removing the LC531 LC532 main unit 32 2 2 4 Panel installation 33 2 3 RS485 Communication Cable Connection 34 2 3 1 RS485 communication cable connection 34 2 3 2 EC bus transmission termination process 35 2 4 Direct connection of the nv Engineering Tool 36 2 4 1 Ethernet connection 36 2 4 2 USB connection 37 2 5 Grounding 38...

Страница 46: ...ch a grounded piece of metal to discharge static from your body before starting work 2 1 2 Working procedures Do not touch any part other than those required Be careful not to lose any screws removed Do not drop any screw in the LC53 main unit and in the housing Consult with one of our service representatives if any error or failure has occurred Be careful not to injure your hands by the sharp pro...

Страница 47: ...Controller LC531 LC532 Instruction Manual 27 Note Never disassemble any part other than specified in this manual It may cause damage to the equipment Important Before work make sure to turn off the power of the LC53 Otherwise it may cause burnout or an electric shock ...

Страница 48: ...1S S LC532S S housing depth 450mm Installing Place the support angle so that it will be at the bottom of the back of the housing Figure 2 2 Insert the housing in which the LC53 main unit is mounted from the front of the installing panel and place the clamping hardware on the top Figure 2 2 Rotate the bar with a slotted screwdriver to fix the housing to the panel Be careful not to tighten it too mu...

Страница 49: ...e 2 4 Using the support angle fixing hardware Bar Installing panel 3 Rotate the bar to fix the housing to the installing panel Support angle Screwdriver Housing side Clamping hardware Housing top Support angle Housing side Housing back 25mm or more Use L shaped type 2 5mm or more 4 Fix the housing to the support angle with the support angle fixing hardware Support angle 24 ...

Страница 50: ...Figure 2 5 Rotate the bar of the clamping hardware placed on the top and bottom with a slotted screwdriver to fix the housing to the panel Be careful not to tighten it too much Figure 2 6 Removing Remove it in the reserved order of installing Figure 2 5 Installing and removing Housing LC53 main unit 1 Mount the housing and insert into the panel Installing panel front Bar Clamping hardware 2 Place ...

Страница 51: ... LC532 Instruction Manual 31 Figure 2 6 Using the clamping hardware Installing panel 3 Rotate the bar to fix the housing to the installing panel Installing panel Bar Mount the clamping hardware on the bottom Bar Housing bottom Mount the clamping hardware on the top Housing top Screwdriver Housing side ...

Страница 52: ...ront operation panel Figure 2 7 Pulling out the LC53 main unit Release the lock of the LC53 main unit Figure 2 8 Releasing the lock of the LC53 main unit Remove the LC53 main unit from the housing Remove the flat cable from the rear panel connector of the LC53 Main Unit Figure 2 9 Removing the LC53 main unit Housing 2 1 LC53 main unit Installing panel Flat cable Housing 4 5 LC53 main unit Housing ...

Страница 53: ...nel installation The dimensions of the panel cut opening for installing the LC53 to the panel are shown below Figure 2 10 Dimensions of the panel cut opening 72 3 n 4 1 0 0 68 0 7 0 138 1 0 0 G When installing the LC53 units in the vertical direction allow a space G of 50mm or more in between Panel Install n units Stand alone Stand alone ...

Страница 54: ...the terminal block TB1 on the back of the LC53 as shown below Figure 2 11 Wiring of the RS485 communication cable Note When performing wiring to the power supply terminal block or RS485 terminal block make sure that there is no error If power is fed to wrong connection it may cause burnout or electric shock TB1 31 to 33 Transmission signal line Shielded wire Transmission cable Housing back Transmi...

Страница 55: ... position For termination process set the RS485 terminating resistance switch on the terminal part back of the LC53 main unit to ON Connecting PC and multiple units of the LC53 are connected via EC bus as shown below Figure 2 12 Terminal position when the monitoring PC and LC53 are connected When multiple units of the LC53 are connected via EC bus Figure 2 13 Terminal position when multiple units ...

Страница 56: ...ansmission cable Removal of Ethernet cable After shutting down nv Engineering Tool remove the Ethernet transmission cable from the Ethernet communication port of the LC53 Then remove the Ethernet transmission cable from the Ethernet communication port of the PC for the nv Engineering Tool Note When inserting the Ethernet transmission cable check the insertion direction of the connector and insert ...

Страница 57: ...ring Tool and start it again 4 Restart the PC Connection of USB cable Connect the USB communication port of the PC for the nv Engineering Tool and the USB communication port of the LC53 directly with a USB cable Note Before inserting the USB connector always touch the lower lock metal part of the LC53 main unit to remove unnecessary electrostatic noise The shapes of the USB connector of the USB co...

Страница 58: ...abinet grounding Separate the N line 0V of the power supply from the frame grounding wire Also connect the frame grounding wiring to the grounding terminal at one point External signal cable Connect the shielding wire of a multi core cable to the shield processing terminal at the cabinet inlet Wiring inside the cabinet should be free of shielding wire if possible to save space and to ensure a suff...

Страница 59: ... equipment other than this system to the ground bus Grounding controllers installed at separate locations When controllers are not installed in the same room ground each of them to one ground point at each installation site as shown in Figure 2 15 Figure 2 15 Example grounding of controllers installed at separate locations Ground bus Cabinet to LC53 Cabinet to LC53 Cabinet to LC53 Cabinet to LC53 ...

Страница 60: ...power supply common and the grounding of a terminal block for one minute To protect the equipment from damage due to a stray test voltage or to malfunction disconnect the power cable and input signal cable in advance 2 5 5 Wiring for panel lighting When a fluorescent light is used for panel lighting do not run the wiring for lighting in the signal wiring duct ...

Страница 61: ...2 Program structure 42 3 1 3 Program management 43 3 2 Variables 45 3 2 1 Variable types 45 3 2 2 Variable classification table 47 3 2 3 Variable initialization 48 3 3 I O 49 3 3 1 Standard built in I O 49 3 3 2 MODBUS connection I O to be implemented in the future 49 3 4 Standard I O 50 3 4 1 Tags and standard I O functions 50 3 4 2 Tag types 50 3 4 3 Standard I O process 51 3 4 4 Process alarm 5...

Страница 62: ...s are automatically generated and not visible from the user A program indicates a unit of execution The program main body consists of multiple standard instruction words and sets of functions and function blocks that are building blocks of a program A function means a function that consists of prepared function instruction words and standard type function programs created arbitrarily by the user T...

Страница 63: ...de memory The code memory has a memory structure partitioned into memory blocks 16 steps 64 bytes One POU occupies consecutive memory blocks depending on the size of the program The table below shows the number of POUs memory size and the number of memory blocks Table 3 2 Program management specifications Number of POUs Code memory size Number of steps Number of memory blocks 64 24KB 6K steps 384 ...

Страница 64: ...ogram 6 P_6 70 5 Main Scan Task Entry 7 MS_7 3 1 Program 7 P_7 80 5 Total 384 34 Number of blocks The result of Number of Steps 16 is rounded up Figure 3 2 An example of program DL When a program is changed online the controller finds consecutive free blocks of the size that can store the program and downloads the program there After that the controller releases the previously used blocks as free ...

Страница 65: ...assified into the following two types based on the scope of reference Local variable Local variables are effective only within the program They can be used as working memory in the program In programming a user program necessary variables can be assigned Controller global variable Controller global variables can be shared within the controller They can be used to exchange data among different prog...

Страница 66: ... 0 to 65535 REAL Real type 32 3 40282 1038 to 3 40282 1038 The data type complies with IEEE754 TIME Timer type 32 0 to 2147483647ms 24d20h31m23s647ms WORD Word type 16 0000 to FFFF DWORD Double word type 32 00000000 to FFFFFFFF 3 Classification depending on usage Controller global variables and local variables can be classified as follows depending on the usage Classification of controller global ...

Страница 67: ...e 4 LP_PARA PB Pushbutton variable 5 PB_PARA P Polygonal line variable P_PARA T Timer variable T_PARA C Counter variable C_PARA 7 Controller Standard Tag instrument variable data PV Indicator variable 3 PV_DATA LP Controller variable 4 LP_DATA PB Pushbutton variable 5 PB_DATA P Polygonal line variable P_DATA T Timer variable T_DATA C Counter variable C_DATA 8 Controller Standard General variable R...

Страница 68: ... variable Continued 5 EC bus variable Continued 6 Tag instrument variable parameter Continued 7 Tag instrument variable data Continued Note 1 8 General variable Continued 9 I O variable Input Continued Note 2 Output Zero output initially Note 3 10 Remote I O variable Input Continued Note 2 Output Zero output initially Note 3 Note Note 1 SV is continued MV starts from the final value at power off o...

Страница 69: ...hows the description of the standard built in I Os Table 3 6 Standard built in I O I O type Description ch Analog input Voltage input 1 5V 6 Analog output Voltage output 1 5V 2 MV current output Current output 4 20mA LC531 only 2 Digital input Contact input 24V 5mA 3 Digital output Open collector output 0 1A 5 Pulse output Pulse output Open Close LC532 only 1 3 3 2 MODBUS connection I O to be impl...

Страница 70: ...d I O P ro gram P ID p ro ces s P V proce ss Input value L P proce ss Output value M V P V I O I O A I P I A O P O S V P B proce ss Input value Output value P ro gram D ig ita l p ro ces s I O D I I O D O F I F O I O Figure 3 5 Relations between tags standard I Os and programs 3 4 2 Tag types The table below shows the types of tags used in standard I Os Table 3 7 Tag types and number of points TAG...

Страница 71: ...g order 1 Normalization Normalization is performed according to the upper range CH and lower range CL settings of the input counter When the input counter is equal to CH PV is set to RH instrument range upper limit When the input counter is equal to CL PV is set to RL instrument range lower limit 2 Temperature and pressure correction 2 1 Temperature and pressure correction 2 2 Extraction of square...

Страница 72: ... process Integration Value MAX is performed Pulse integration value conversion For pulse integration values only input from the intelligent serial PI module endless counter from 0 to 65535 is used The following integration value calculation is performed Current Integration Value Pulse Difference Count X PU X D X K Previous Integration Value During an integration reset Integration Value 0 is retain...

Страница 73: ...ss The following processes are performed according to the pushbutton variable parameter settings DI input process DI of the specified intelligent serial I O is stored in FI of PB Input reversal process is performed according to the setting DO output process At button operation from the host setting resetting and reversal of FO are performed according to the pushbutton variable parameter setting FO...

Страница 74: ... sensor error alarm PDE device error alarm Controller variable LP VPI valve opening error alarm DVE deviation alarm MVL MV lower limit alarm MVH MV upper limit alarm MVE MV error alarm Pushbutton PB IOE DI DO module error alarm Note Generation and recovery of the CLI control stop alarm of the controller is performed by the user with the program When alarm suppression is performed in the program al...

Страница 75: ... Registration 58 4 2 1 Hardware configuration registration 58 4 2 2 Network registration 61 4 2 3 Module parameter registration 63 4 3 Tag Registration 64 4 3 1 Registration of tag editor and tag parameter 64 4 4 Variable Registration 71 4 4 1 Registration of standard variables 71 4 4 2 Registration of system variables ZW 72 4 4 3 Registration of I O variables SIO1 73 4 5 Program Creation 74 4 6 R...

Страница 76: ...7 1 Registration of inter controller transmission variables 78 4 7 2 Registration of a program to start inter controller transmission 78 4 8 Registration of PUM1 Controller Using Inter Controller Transmission 80 4 8 1 Registration of inter controller transmission variables 80 4 8 2 Registration of a program to start inter controller transmission 81 ...

Страница 77: ...f analog inputs 3 points of digital input and 3 points of digital output are used The input and output points are assigned to tags to be used The nv Engineering Tool is connected via Ethernet Figure 4 1 Example of system configuration Remark Use nv Series Engineering Tool 4 of Version 4 9 6 or later to register the LC531 system Use nv Series Engineering Tool 4 of Version 4 10 6 or later to registe...

Страница 78: ...ation items such as System name and Station configuration are shown below Table 4 1 System name and station configuration Level Name slot No Device name System LC531_Sample Station LC531 nv oneloop station Unit Unit No 0 MainUnitLC Module Slot No 0 LC53 4 2 1 Hardware configuration registration Start the nv Engineering Tool Product tree Select the System folder at the upper left of the screen with...

Страница 79: ...ion folder shown at the lower left of the screen with the mouse and select New in the File menu Enter a station name in the text box of the input dialog Figure 4 3 Adding a station Expand the created LC531 nv oneloop station at the upper left of the screen with the mouse select the Units folder with the mouse and select New in the menu Select the unit number 0 and unit model name MainUnitLC in the...

Страница 80: ...h the mouse select the Modules folder with the mouse and select New in the menu Select the slot number 0 and module model name LC531 in the input dialog Figure 4 5 Adding a module As a result of the operations above the system product tree of the LC531 is registered as shown below Figure 4 6 LC531 system product tree screen after registration ...

Страница 81: ...New in the menu Select the network number 1 and network model name EtherLAN to add the network Figure 4 7 Adding a network Expand the created network 001 EtherLAN at the upper left of the screen with the mouse select the Modules folder with the mouse and select New in the menu Select the node number 1 and module name LC531 nv oneloop station_00 LC531 in the input dialog to register the module Figu...

Страница 82: ... 4 Registration and Setting Using Engineering Tool 6F8C1388 62 As a result of the operations above the network and LC531 module are registered as shown below Figure 4 9 Network module screen after registration ...

Страница 83: ... screen with the mouse and select Module Parameters in the File menu Figure 4 10 Network module registration screen Enter necessary parameters on the Module Parameters screen Make sure to enter MS task scan time ms of the LC531 For module parameters of the LC531 refer to Appendix F Details of Module Parameters Figure 4 11 Module parameter registration screen ...

Страница 84: ... 0 Built in IO AI point 1 AI1 PV Indicator 2 PV 1 Built in IO AI point 2 AI2 LP Controller 1 LP 0 Built in IO MV point 1 MV1 LP Controller 2 LP 1 Built in IO AO point 1 AO1 PB Pushbutton 1 PB 0 Built in IO DI point 1 DI1 Built in IO DO point 1 DO1 PB Pushbutton 2 PB 1 Built in IO DI point 2 DI2 Built in IO DO point 2 DO2 PB Pushbutton 3 PB 2 Built in IO DI point 3 DI3 Built in IO DO point 3 DO3 Co...

Страница 85: ...LC531 Instruction Manual 65 Select PV Indicator for Parameter Specify Record No Figure 4 13 PV indicator setting screen Table 4 3 Available tag types and record numbers Tag type Parameter type Record No PV PV Indicator 1 to 48 LP LP Controller 1 to 8 PB PB Pushbutton 1 to 32 ...

Страница 86: ...u on the toolbar of the tag editor and copy the initial values of the tool A dialog window is displayed Select Initial Value in Contents of copy and click Figure 4 14 Parameter initial value copy setting screen Initial values are set to the tag parameters Figure 4 15 PV indicator initial value setting screen ...

Страница 87: ...0 to 100 64000 in 16 bit resolution As tag initial values 12800 64000 are set DCL Input count low limit 12800 12800 PVA Input point variable name address notation AI1 MW9 4 AI2 MW9 6 Select the input point AI1 AI6 according to the menu of the setting dialog SIMM Simulation method Standard Standard If no I O wiring is provided PV input must be simulated When this is set to Standard to select the si...

Страница 88: ...stration and Setting Using Engineering Tool 6F8C1388 68 Figure 4 16 Example of settings PV Indicator and LP Controller for Loop 1 LP001 Figure 4 17 Example of settings PV Indicator and LP Controller for Loop 2 LP002 ...

Страница 89: ...arameters When the PV tag and LP tag are associated the tag variable is automatically registered as shown below Note When the order of registration of the PV tag and LP tag is reversed the PV tag and LP tag will not be associated Figure 4 18 Variable registration of PV_PARA LP001_0 LP002_0 Figure 4 19 Variable registration of PV_DATA LP001_1 LP002_1 Figure 4 20 Variable registration of LP_PARA LP0...

Страница 90: ...ed as the variable name tag variable USE PB use flag Used Used Used IA1 Input point variable name 1 address notation DI1 MX9 2 0 DI2 MX9 2 1 DI3 MX9 2 2 Select DI points DI1 DI3 and DO points DO1 DO5 according to the menu of the setting dialog OA1 Output point variable name 1 address notation DO1 MX9 34 0 DO2 MX9 34 1 DO3 MX9 34 2 DA01 Button release output 1 Reset Reset Reset In this example FO1 ...

Страница 91: ...ess the Default Variable D button in the Controller variable screen of Tools For variables refer to 3 2 Variables Table 4 7 Types of controller variables Variable name Description of variable ZW System variable User User variable EC_BUS EC bus variable PV_PARA Indicator variable parameter LP_PARA Controller variable parameter PB_PARA Pushbutton variable parameter P_PARA Polygonal line variable PV_...

Страница 92: ... 72 4 4 2 Registration of system variables ZW Select the controller variable Figure 4 24 Selecting the system variable ZW Clear Lock up L select Default Variable D and register standard variables of system variable ZW Figure 4 25 System variable ZW registration screen ...

Страница 93: ...of I O variables SIO1 Select the controller variable Figure 4 26 Selecting the I O variable SIO1 Clear Lock up L select Default Variable D and register standard variables of I O variable SIO1 Figure 4 27 I O variable SIO1 registration screen Remark For details of I O variables refer to Appendix E 3 Built in I O Variables SIO1 ...

Страница 94: ...e external variable V01 to SV in the C mode and a program that generates reversed output outputs when PB001 is in the A mode or stops when it is in the M mode of DO1 PB001 FO1 when DI1 PB001 FI1 is ON For information on how to use the program editor refer to Engineering Tool 4 Operation Manual Basics 6F8C1290 Figure 4 28 Example of program creation CAUTION This example shows a simplified program T...

Страница 95: ...of the diagnosis map 2 word transmission area 64 word and reception area 31 stations 64 word You may reduce the size of the reception area according to the number of stations 1 to 31 See below to find the size of an inter controller transmission variable Inter controller transmission variable size 66 maximum station number 64 You must configure the value found by the above for N size of the USEND_...

Страница 96: ...tart by RUN to start inter controller transmission A procedure to start inter controller transmission is as follows Figure 4 29 Procedure to start inter controller transmission Y N Issue operation mode control request USEND_T standby Issue reset request Issue parameter onfiguration request USEND_T configuration USEND_T reset Issue operation mode control request USEND_T RUN Station status read MREA...

Страница 97: ...smission and reception of sockets Once it is started normally it operates continuously until the S3 controller or EN311 is stopped The summary of operation of this command USEND_T is as follows 1 Launch REQ to open the socket When the socket is opened normally DONE ON and go to 2 In case of error ERROR ON and exit 2 Repeat the steps below Transmit 64 word in the transmission area every 1 second Sa...

Страница 98: ...ables in a specific address according to the structure shown below 4 7 2 Registration of a program to start inter controller transmission To operate the EN911 module configure the IP address and port number and start by RUN to start inter controller transmission A procedure to start inter controller transmission is as follows Figure 4 30 Details of the Inter controller transmission start instructi...

Страница 99: ...ission and reception of sockets Once it is started normally it operates continuously until the PU811 controller or EN911 is stopped The summary of operation of this command USEND_N is as follows 1 Launch REQ to open the socket When the socket is opened normally DONE ON and go to 2 In case of error ERROR ON and exit 2 Repeat the steps below Transmit 64 word in the transmission area every 1 second S...

Страница 100: ... transmission To achieve inter controller transmission the inter controller transmission variables must be declared and a program to start inter controller transmission needs to be created 4 8 1 Registration of inter controller transmission variables The PUM1 controller has no standard inter controller transmission variables The declarable types are user global and DW Declare the inter controller ...

Страница 101: ...ration of a program to start inter controller transmission A procedure to start inter controller transmission is as follows USEND_N_1 USEND_N REQ DONE CMD ERROR P STATUS N STATUS1 CMD1 TransData Size REQ1 DONE1 S ERR1 type1 light Figure 4 31 Details of the Inter controller transmission start instruction User variable Inter controller transmission 8190 TransData ...

Страница 102: ...is started normally it operates continuously until the PUM1 controller or EN655 is stopped The summary of operation of this command USEND_N is as follows 1 Launch REQ to open the socket When the socket is opened normally DONE ON and go to 2 In case of error ERROR ON and exit 2 Repeat the steps below Transmit 64 word in the transmission area every 1 second Save reception data in the reception area ...

Страница 103: ...ches 84 5 2 Starting Up 85 5 2 1 Display on the loop display during startup 86 5 2 2 Memory clear download and startup 86 5 3 Stopping 87 5 4 Transition of Operation Mode 88 5 5 Operation Mode Display 89 5 6 Control Operation during Startup and Stop 89 ...

Страница 104: ...hes 6 7 and 8 can be set by the user Rotary switch STN When other LC53 controllers and nv Engineering Tool are connected via Ethernet check that the IP addresses do not overlap 1 Check the Ethernet Class setting with 7 and 8 of the Engineering switches Eng SW 2 Check the IP address setting H L of the rotary switch STN Example When H 1 and L 2 are set in the Class B environment the following IP add...

Страница 105: ...ecute memory clear Waiting for download Turn on the power YES NO Download application with the engineering tool Request RUN execution NO YES RUN executed normally YES NO Memory related error YES NO A Setting related error Set correct data to parameters with the engineering tool or set the switches to correct data again A The LC53 may be defective Take the measures shown in the error log Replace th...

Страница 106: ...cimal alternately Remark For the meanings and detailed information about error codes refer to Appendix D System Log 5 2 2 Memory clear download and startup The procedure for memory clear download and startup is described below For memory clear set the engineering switch Eng SW 1 on the side of the LC53 to ON and turn on the power of the LC53 When memory clear is executed the numerical display area...

Страница 107: ...y stop Power supply is stopped to stop the LC53 When power supply stop is performed all I O outputs become OFF To return to the RUN execution state supply the power again Error stop ERROR When a critical error is detected during RUN execution of the LC53 it automatically goes to the ERROR mode and stops its operation The numerical display area of the loop display shows Err indicating an error and ...

Страница 108: ...error is detected and it is stopped OFF Transition to the HALT mode can be done by resetting the error Startup to the RUN mode can be done by auto restart Note DL wait Memory is cleared and it is waiting for download of application OFF Transition to the RUN mode can be done by download of the application Note For auto restart setting refer to 1 2 2 Switch area side display side keyboard area side ...

Страница 109: ...epending on the state of startup and stop This section describes MV SV and MODE of the controller LP and behavior of MV output in the following table Table 5 3 Control operation during startup stop State of LC53 Control operation and output DL wait memory clear MODE M mode SV 0 MV 0 MV output 0mA PO output stop Memory loss FROM is not saved MODE M mode SV 0 MV 0 MV output 0mA FROM is saved MODE M ...

Страница 110: ...Chapter 5 Startup and Stopping 6F8C1388 90 ...

Страница 111: ...keyboard and the display To explain key operation in this Chapter for example the operation Press key and then press is described as 6 1 Side Keyboard and Side Display Overview 92 6 1 1 Basic screen configuration 92 6 1 2 Key arrangement of side keyboard 93 6 1 3 Key operation overview Rule 94 6 1 4 Screen execution overview 95 6 2 Screen Configuration List 96 6 3 Menu Tree List 97 6 4 Alarm Displ...

Страница 112: ...e Display Overview 6 1 1 Basic screen configuration The side display is a 16 character 2 line LCD display The basic screen configuration is shown below Title This is the screen title for menu screen or item name for tag item display etc Item value Menu item or tag item for menu screen or a data value for data display Refresh icon Data refresh display in progress Alarm icon This indicates that an a...

Страница 113: ...the menu goes back to the previous menu Automatic alarm indication An alarm condition is periodically searched and an icon will be displayed if found Key operation lock Keep pressing to change into Key operation lock condition Keep pressing key again to release the key operation lock and the system returns to main menu Auto prohibition of key operation If no key operation is done for the specified...

Страница 114: ... to execute menu for menu screen confirm write data for data input and confirm alarm confirmation reset for alarm screen Numeric key Alphabet key Used to go to submenu for menu screen and display each data for data input Symbol key Indicates a minus sign or a decimal point at the time of data setting or appears depending on the cursor position Remark Special input of numeric keys When you enter he...

Страница 115: ...ta such as PV value is displayed the screen changes to data setting rewrite screen 4 Pressing key returns to one step previous screen 5 Pressing key on the data setting screen the entered data will be set overwritten and the screen returns to the previous screen 6 Pressing key on each screen its Help screen appears 7 Pressing any key returns to the previous screen 8 Pressing key longer 2 seconds o...

Страница 116: ...play Non appears if no alarm is generated Changes to the data change mode the cursor moves to the second line Returns to higher level screen Bar graph display screen Increases or decreases the bar graph indication Returns to higher level screen Help screen Moves from other screens to the HELP screen displays description of key operations and setting range Scrolls the displayed data No display at t...

Страница 117: ...notation only symbol not allowed 3 System variable Z Numeric value type Display setting of system variable Z 4 Variable parameter DP Numeric value type Display setting of variable parameter DP 5 Internal flag S Numeric value type Display setting of internal flag S 6 Internal variable Y Numeric value type Display setting of internal variable Y 5 External variable menu communication Submenu Display ...

Страница 118: ...etting menu Submenu 0 Display brightness adjustment Bar display Adjustment of brightness in steps 1 Display language switching List type English Japanese display switching Initial setting English 2 Auto lock setting List type Yes No 6 Clock setting Numeric value type Transition to 6 Maintenance 4 System info DATE 7 System code system name Numeric value type Display of the system code and system na...

Страница 119: ...reviation is displayed 6 4 1 System alarm System alarm is the function to display an alarm on the side display when an error related to the system such as a battery error or memory error occurs Alarms include major and minor failures The alarm display blinks in case of a major failure BAT abbreviation of the alarm Battery Fault error message Figure 6 4 Display example of system alarm Remark For sy...

Страница 120: ... when the user performs confirmation operation PV tag type PV LP PB 000 tag record number 000 and subsequent numbers PDE abbreviation of alarm Device Error error message Figure 6 5 Display example of process alarm Remark For details of the process alarm refer to Appendix Table H 2 Types of process alarms Setting of Auto recovery and Confirmed recovery can be done either with the nv Engineering Too...

Страница 121: ... 6 6 Display example of alarm icon Remark Update cycle of the alarm icon In system alarm and process alarm diagnosis the diagnosis items are diagnosed in 0 5 second cycles Therefore it may take up to 12 seconds from the occurrence of an alarm until the alarm icon is displayed or from the recovery from an alarm until the alarm icon disappears 6 4 4 Other error messages ROM RAM error or errors relat...

Страница 122: ...Chapter 6 Side Keyboard and Side Display 6F8C1388 102 ...

Страница 123: ...103 Chapter 7 Troubleshooting 7 1 System Log Function 105 7 2 Alarm Display Functions of Side Display 106 7 3 Alarm Display Functions of Loop Display 107 7 4 WDT Signal Output 108 ...

Страница 124: ...also check error information in detail by reading the system log from the LC53 with the nv Engineering Tool You can also monitor the operation state of the LC53 from the outside by using the WDT signal output by the LC53 Figure 7 1 Overview of troubleshooting Alarm display on loop display RUN display on side panel Alarm display on side display Monitoring WDT signal from outside nv Engineering Tool...

Страница 125: ... in the internal memory The LC53 records the following 4 types of errors and events Error log Records hardware and software error information Event log Records power on off and changes in operation mode Intervention event log Records intervention operations from the monitoring device and host system such as mode changes of tags and sequences and process alarm checking Transmission event log Record...

Страница 126: ... Display Functions of Side Display By operating the side key you can display alarm information currently generated on the side display without using the nv Engineering Tool Remark For alarm details of side display refer to Appendix H 1 Alarm Details ...

Страница 127: ...rm Blinking Battery error OFF when recovered Error log 8E01 8E81 In simulation PV_DATA SIM LP_DATA SIM simulation during linearization Process alarm 1 For the method to release the MV error alarm refer to Appendix H 2 9 Restore the MV Error MVE ALM in the ALARM display area indicates a process alarm or user alarm output when it is on Table 7 2 Description of ALM in the ALARM display Display state ...

Страница 128: ...ition using the system log of the nv Engineering Tool Software At status other than RUN INZ HALT DL WAIT ERROR Check the operation mode using the nv Engineering Tool or the Side display WDT output by application output ZW800 Check ZW800 using the nv Engineering Tool or the Side display Remark WDT signals can be output by writing ON OFF data to the ZW800 with the user application For the ZW800 refe...

Страница 129: ...ly Check 110 8 2 Periodic Check 111 8 3 Expendable Parts 113 8 3 1 Replacing the battery lithium battery 113 8 3 2 Disposing of the lithium battery 114 8 4 Replacements 115 8 4 1 Replacing the tag number plate 115 8 4 2 Replacing the scale plate 115 ...

Страница 130: ...the system is operating LC53 state display Check the display state of HLT ALM and CMP on the loop display front panel and the state of the LED display RUN on the side panel of the LC53 If any error is found check the system and bring it back to normal condition referring to Chapter 7 Troubleshooting ...

Страница 131: ...y are mounted Check that they are not loose Retighten the screws if loose Checking cables Check the individual cables that they are free of damage Replace damaged cables if any Measuring input voltage Measure the voltage of DC power supply input terminal for LC53 and check that the voltage is within the voltage range shown below If the voltage is out of the range specified check external power lin...

Страница 132: ...wer supply external signals and transmission signals are not loosened If any of these screws are loosened tighten them again WARNING Before checking the LC53 main unit or cables directly make sure that the input power supply the switch of the receiving distribution unit is turned off Otherwise it may cause an electric shock Mandatory ...

Страница 133: ... At every periodic inspection check the replacement year month and replace it with a new lithium battery as required If the HALT display on the front display panel of the LC53 blinks replace the lithium battery in the following procedure Note To replace the battery replace it while 24VDC is turned on 1 Press the hook at the top of the battery holder to remove the lithium battery 2 Insert a new lit...

Страница 134: ... Type CR2032 Sony or a product of compatible manufacturer WARNING Do not throw a lithium battery into fire An explosion may occur Prohibited CAUTION Dispose of lithium batteries by observing the ordinance or regulation of the local government Environmental contamination may occur Mandatory CAUTION If the battery is removed for 5 minutes or more while power is not applied to the equipment memory co...

Страница 135: ...he top of the tag number plate the part of the frame will be removed and you can take out the tag number plate Figure 8 2 Replacing the tag number plate 8 4 2 Replacing the scale plate Remove the tag number plate as described above and then pull out the scale plate When installing a scale plate insert it Figure 8 3 Replacing the scale plate 前面フ レ ームの上 部を持ち上げる TA G N o プ レ ート カ バ ー プ ラ ス テ ィ ッ ク と ...

Страница 136: ...Chapter 8 Maintenance and Inspection 6F8C1388 116 ...

Страница 137: ...A 2 Electric and External Specifications 120 A 3 I O Specifications built in 121 A 4 RS485 Communication Specifications 122 A 5 Ethernet Transmission Specifications 122 A 6 USB Specifications 123 A 7 LC531 LC532 Wiring Diagram 124 A 8 LC531 LC532 Software Specifications 125 ...

Страница 138: ...which are built in LC53 RS485 Communication Specifications It explains the RS485 communication specifications installed in LC53 Ethernet Transmission Specifications It explains the Ethernet transmission specifications installed in LC53 USB Specifications It explains the USB specifications installed in LC53 LC53 Wiring Diagram It describes the wiring diagram of power supply of LC53 I O RS485 Ethern...

Страница 139: ...ductive contamination or less IEC 61131 2 Corrosive gas No corrosive gas shall be present No material with silicon shall be present Vibration resistance 5 f 9Hz Half amplitude of 3 5 mm 9 f 150Hz Constant acceleration of 9 8m s2 Complied with IEC 60068 2 6 test Fc Impact resistance 147m s2 Complied with IEC 60068 2 27 test Ea Altitude 2000 m or less Free fall Shipping package state 1000mm Product ...

Страница 140: ...een FG and power supply Online installation and removal Online installation and removal of the LC53 main unit can be done Installation removal from the housing Casing External dimensions LC53 E S 72W 144H 250D mm LC53 S S 72W 144H 450D mm Weight LC53 E S Approx 2Kg LC53 S S Approx 3 5kg Panel cutout dimensions 68W 138H mm square hole plate thickness 8mm or less Panel material Panel ABS resin UL94 ...

Страница 141: ...t points 2 points Output range 1 to 5Vdc Signal common terminal SC terminal No 6 Insulation unit No insulation between channels Resolution 16bit Conversion data 12800 to 64000 count 1 to 5Vdc Load resistance range 5kΩ or more Reference output accuracy 0 1 Temperature drift 0 1 10 C Digital input DI1 to 3 Number of output points 3 points External signal No voltage contact external 24V 5mA 20 at con...

Страница 142: ...er of Station 32 Including host devices Insulation Insulation between power supply and internal circuit Communication method 2 line method Transmission method Asynchronous Transmission cable Twisted pair cables with shield A 5 Ethernet Transmission Specifications Table A 5 Ethernet transmission specifications Item External Specifications Transmission path specifications Function Connection between...

Страница 143: ...Specifications Table A 6 USB specifications Item Specifications Transmission path specifications Function Connection to nv Engineer Tool 4 Standard USB 2 0 full speed Topology 1 1 Transmission speed 12Mbps Connection connector PC side USB Terminal A male LC53 side USB Terminal B male Length of cable 2m or less Extension cable cannot use ...

Страница 144: ...t DO1 DO2 DO3 DO4 DO5 Digital output open collector 15 16 MV1 MV2 4 20mA output circuit between 0V WDT output Connector for Ethernet RJ45 26 27 28 29 25 Power supply common for DIO 30 5 DIO DIO DIO 24V input 4 Main power 24V input MV output 4 20mA R M input Pulse output R M input 24V 5mA Pulse Output Open Pulse Output Close LC532 only LC532 only Power supply 31 32 33 RS485 circuit Insulation FG RS...

Страница 145: ...iagnosis MV read back diagnosis Monitor function Program congestion monitor battery monitor Alarm function System alarm process Alarm Maintenance function Online monitor Note 2 system logs error log event log intervention event logs transmission event log Note 1 1 The performance value of program processing capacity is a general guideline value The above performance may not be obtained depending o...

Страница 146: ...Appendix A LC531 LC532 Specifications 6F8C1388 126 ...

Страница 147: ...lay Panel B 1 FAST SEL Switch Operation 129 B 2 NORMAL Mode and SELECT Mode 130 B 3 Display Operation Mode Transition 131 B 4 Operation Methods for the NORMAL Mode and SELECT Mode 132 B 5 Special Display in the Numerical Display Area 133 ...

Страница 148: ...ay front panel of the LC53 Figure B 1 LC53 loop display front panel FAST SEL pushbutton MV manual operation pushbutton Mode switch pushbutton SV setting pushbutton C A M FAST SEL HLT L P PV SV MV S V M V ALM CMP R M 1 C A M SEL 100 90 80 70 60 50 40 30 20 10 0 100 80 60 40 20 0 Numerical display area Bar display area ...

Страница 149: ...shbutton along with the MV manual operation pushbuttons or SV setting pushbutton NORMAL mode and SELECT mode selection When the FAST SEL pushbutton is used alone the display operation mode of the loop display is switched between the NORMAL mode and SELECT mode The mode toggles between the NORMAL mode and SELECT mode every time you press the FAST SEL pushbutton for less than 1 second If the LC53 st...

Страница 150: ...method described above Display and operation in the NORMAL mode Loop information is displayed Setting and operation of MV or SV can be done Control mode C A or M operation can be done Alarm check and PH PL display on the SV bar SEL display is off Display and operation in the SELECT mode Loop information is displayed Loop number can be switched Numerical data display PV MV or SV can be switched Con...

Страница 151: ... transition NORMAL mode FAST SEL ON Loop display MV SV operation Control mode operation For operation refer to Appendix Table B 1 NORMAL mode operation SELECT mode FAST SEL ON Alarm check PH PL display For operation refer to Appendix Table B 1 NORMAL mode operation RUN startup FAST SEL ON hold for 1 sec or longer FAST SEL OFF Loop number switch Numerical data display switch MV SV or PV Control mod...

Страница 152: ... display illuminates Remark MV manual operation pushbutton or SV setting pushbutton at the same time please move out FAST SEL pushbutton earlier when operation finished If moving out FAST SEL and MV manual operation pushbutton or SV setting pushbutton at the same time MV or SV may keep changing very rarely The table below shows the operation method in the SELECT mode Table B 2 SELECT mode operatio...

Страница 153: ... area In other modes the numerical display area has special display The table below describes the details Table B 3 Special display in the numerical display area State Display Remark Initialize mode The entire display area including the numerical display area illuminates for 2 3 seconds DL wait mode Displays dL HALT mode Displays HL ERROR mode Displays Err and alternately is the event number that ...

Страница 154: ...Appendix B Details of Loop Display Panel 6F8C1388 134 ...

Страница 155: ...135 Appendix C Outline Drawing C 1 LC531S S LC532S S Type 136 C 2 LC531E S LC532E S Type 137 ...

Страница 156: ... the LC53 main unit fully inserted into the housing To mount the LC531S S LC532S S type on a panel use clamping hardware and support angle to secure it Figure C 1 LC531S S LC532S S module outline drawing LC53 main unit 72 13 144 138 Front view Side view Housing 20 450 300 to 400 Support angle Clamping hardware 100 HLT L P ALM CMP R M 1 C A M SEL PV SV MV 90 80 70 60 50 40 30 20 10 0 100 80 60 40 2...

Страница 157: ...housing To mount the LC531E S LC532E S type on a panel use clamping hardware to secure it Figure C 2 LC531E S LC532E S module outline drawing 72 250 13 144 138 Front view Side view LC53 main unit Housing Draw out the LC53 main unit from the housing in this direction 20 Clamping hardware Clamping hardware 100 HLT L P ALM CMP R M 1 C A M SEL PV SV MV 90 80 70 60 50 40 30 20 10 0 100 80 60 40 20 0 FA...

Страница 158: ...Appendix C Outline Drawing 6F8C1388 138 ...

Страница 159: ...139 Appendix D System Log D 1 Error Log 141 D 2 Event Log 148 D 3 Intervention Event Log 151 D 4 Transmission Event Log 152 ...

Страница 160: ...tem log information can be read and viewed from the nv Engineering Tool when necessary The LC53 records the following 4 types of errors and events Error Log Records hardware and software error information Event Log Records power on off and changes in operation mode Intervention Event Log Records intervention operations from the monitoring device and host system such as mode changes of tags and seq...

Страница 161: ...ROM BCC check error Major failure Initial diagnosis Error rundown Error was detected in flash ROM BCC check BCC Block No Number of error occurrences Flash ROM failure Replace the CPU module and restart the system After replacing CPU module execute Memory Clear and Batch DL 8109 Flash ROM save error Major failure Executed Continued Error is detected from flash ROM save instruction Status Flash ROM ...

Страница 162: ... blocks Entry serial No 0 to 308 Insufficient capacity in consecutive free memory areas Execute Memory Clear and Batch DL and restart 8121 Packing process aborted 2 Caution Executed Continued Insufficient entry code memory was detected Block No Number of blocks Entry serial No 0 to 308 Insufficient capacity in consecutive free memory areas Execute Memory Clear and Batch DL and restart 8122 Packing...

Страница 163: ...d in user program was detected IP absolute IP relative IR Use of unsupported instruction or code memory error Check if any unsupported instruction is used If any unsupported instruction is used modify the user program If not execute Memory Clear and Batch DL and restart the system 9101 Task stall occurred Major failure Executed Error rundown Execution of main scan is stalling or stopped Status Tas...

Страница 164: ...ome zero 910E User task table operation error Caution Executed Continued Error occurred in handling of tag LP PV or PB table IP absolute IP relative IR Tag variable used in instruction dealing with tag variable LP PV or PB indicates outside tag memory area Check the tag variable again 9112 User task non numeric input Caution Executed Continued A non numeric value was input in executing a real inst...

Страница 165: ...information in flash ROM is damaged Save the user information to the flash ROM again If it does not recover from the error replace the CPU module and restart the system After replacing CPU module execute Memory Clear and Batch DL 9134 Download type error Caution Executed Continued Download was performed to non existing memory area 9135 Backup request interrupted Caution Executed Continued Backup p...

Страница 166: ...L 913A Program DL error 4 Caution Executed Continued Memory for copy command local instance could not be reserved RAM memory failure If it does not recover from the error after performing download again replace the CPU module and restart the system and then execute Memory Clear and Batch DL 9300 Total control stop Major failure Executed Error rundown Total control is in congestion Hardware failure...

Страница 167: ... device state 9981 ECBUS external variable all point recovery Recovery from minor error Periodic diagnosis Continued Transmission of one or more external variables V01 V32 of ECBUS was recovered The error occurrence state minor and major failures only is displayed on the error information map ZW410 ZW665 Errors are assigned to the error information map according to Failure level Large classificati...

Страница 168: ...LD4 Executed Intelligent I O standby mode start 810D O HOLD1 Executed Intelligent I O online mode start 8111 PHASE 3 Executed 811B RUN Executed RUN execution start 8200 RUN command Executed RUN execution is requested 8201 HALT command Executed HALT stop is requested 8202 Error Reset command Executed Error reset is requested 8205 Memory Clear command Executed Memory clear is requested 9001 Task DL ...

Страница 169: ...n Executed 910D Memory clear Initial Memory clear is executed 910E Save on Flash ROM command Executed Save of user information to flash ROM is requested 910F Task execution disable Executed Task execution is disabled 9110 Task execution enable Executed Task execution is enabled 9113 Intervention trace clear Executed Intervention event log is cleared 9114 Error trace clear Executed Error event log ...

Страница 170: ...arameter information registration Executed 9131 General variables information registration Executed 9132 Tag data information registration Executed 9137 Station global information registration Executed 9139 Backup start request Executed 913A Backup end request Executed 913B Restore start request Executed 913C Restore end request Executed 913D Program packing executed Executed Code memory and insta...

Страница 171: ...3 Intervention Event Log Table D 3 Intervention Event log Event No Trace Contents Level Timing Exec Remark Task Address Aux1 Aux2 Aux3 Cause Maintenance 8000 Control mode change 8001 SV change 8002 MV change 8003 DO output 8004 Scan ON OFF 8005 PV change 8006 DI change 8007 Simulation ON OFF 8008 Tag parameter change ...

Страница 172: ...x3 Cause Maintenance 98B2 Socket request Hex Hex Hex 98B3 Socket BIND request Hex Hex Hex 98B4 Socket LISTEN request Hex Hex Hex 98B5 Socket CONNECT request Hex Hex Hex 98B6 Socket ACCEPT request Hex Hex Hex 98B7 Socket SHUTDOWN request Hex Hex Hex 98B8 Socket CLOSE request Hex Hex Hex 98B9 Socket connection information Hex Hex Hex 98BA Socket remote close Hex Hex Hex ...

Страница 173: ...es PV LP PB 160 E 2 1 Indicator Variables PV_PARA PV_DATA 161 E 2 2 Controller Variables LP_PARA LP_DATA 168 E 2 3 Pushbutton Variables PB_PARA PB_DATA 174 E 3 Built in I O Variables SIO1 177 E 4 EC Bus Variables EC_BUS 178 E 5 Inter controller Transmission Variables STN_DATA 180 ...

Страница 174: ...IO1 Variables used to access built in I Os of the LC53 EC bus Variables EC_BUS Variables equivalent to that of the conventional single loop controllers EC series Data of other single loop controllers connected to EC bus can be accessed by using EC bus variables Inter controller Transmission Variables STN_DATA Variables used to refer to send and receive data of inter controller transmissions They a...

Страница 175: ... write in the area for read only areas Using these areas may cause malfunction of the LC53 Prohibited TableE 1 General data read only data ZW Use F E D C B A 9 8 7 6 5 4 3 2 1 0 0 Calendar date Greenwich Mean Time Year 10 1 Month 10 1 Day 10 1 Hour 10 1 Minute 10 1 Second 10 1 6 Engineering switch 7 6 5 4 3 2 1 0 state Eng SW 0 SW1 Memory clear selection with ON 1 SW2 Reserved 2 SW3 Reserved 3 SW4...

Страница 176: ...cess cycle at power on or RUN startup 53 Instruction error representative status 1 Any of the following errors has occurred Yes 0 No EX 54 Detailed data for above 0 Illegal instruction 1 POU undefined error 2 Stack overflow 3 Real number calculation error 4 Boundary overflow executed 5 Variable reference address boundary error 6 7 8 Division error 9 BCD data error 10 Table operation error 11 12 13...

Страница 177: ...n F 00H 0 03H 3F 474 Major classification 1 Medium classification 0 00H 0 SW 03H 3F to to 534 Medium classification F 00H 0 03H 3F Minor fault error map Minor classification F E D C B A 9 8 7 6 5 4 3 2 1 0 538 Major classification 0 Medium classification 0 00H 0 HW 03H FF to to 598 Medium classification F 00H 0 03H 3F 602 Major classification 1 Medium classification 0 00H 0 SW 03H 3F to to 662 Med...

Страница 178: ... be checked The upper 1 byte of the displayed and selected loop indicates the loop number currently displayed The lower 1 byte is the command register to switch the displayed loop Loop display can be switched by writing a loop number 1 8 When writing a loop number write it as 1W data The upper byte doesn t have to be masked When 0 is written nothing will be changed Table E 6 Ethernet status ZW Use...

Страница 179: ...abled disabled 931 enabled enabled disabled disabled 932 enabled enabled disabled disabled 933 enabled enabled enabled disabled ZW 930 ZW 932 is compatible with the error status of the expansion I O data area EA10 bitD and bit0 3 However the error status of the EA10 but you can choose a minor fault major fault without the error mask of expansion I O parameter area EA11 the ZW area indicates the pr...

Страница 180: ...s setting or input condition Only the one that satisfies all conditions can be input indicates the state display or data display OIS indicates it is writable from the OIS indicates a change notification is made to the OIS when it is rewritten from the Engineering Tool side keyboard or user application indicates it is write protected indicates that it is a parameter data displayed in the OIS indica...

Страница 181: ...eering unit section RL RH Engineering unit EU Set the engineering unit character of the PV value Up to 8 one byte characters Decimal point position DCML Set the decimal point position for displaying the PV value and range 0 6 Signal type code SIG Select the type of input signal from the following refer to Supplementary explanation Unused Standard processing for this instrument will not be performe...

Страница 182: ... the standard process for analog input is performed Sensor error PVI occurrence conditions Other than mV AI input 4480 AI input 32767 mV AI input DCH AI input DCL For pulse contact and pulse voltage the standard process for pulse input is performed 2 The relation between the signal type SIG and input count is as follows 4 20mA 6400 32000 1 5V 6400 32000 Resistance temperature detector 6400 to 3200...

Страница 183: ...antaneous value is a bar graph and the display for integration value is a counter Instantaneous value Integration value Integration PV No SPV When Integration value is selected for Integration specification PV indicates an integrated value The instantaneous value to be used as integration value can be selected from other PV as well as the signal assigned to its own To use other PV as the target si...

Страница 184: ...correction PV No PM When process value is such as an air flow rate signal and correction calculation by pressure is needed PV No to show measurement pressure should be registered 0 Unused 1 to 128 Correction specified Temperature correction design temperature C TDG When process value is such as an air flow rate signal and correction calculation by temperature is needed design temperature for refer...

Страница 185: ...tor works as a conversion factor in the same way as the unit conversion factor 0 D Note PU T K and D values are used to obtain the following process value PV Analog integrated value Integrated value Previous integrated value Instantaneous value this time D K Scan cycle T Pulse integrated value Integrated value Previous count value Pulse count this time PU D K Pulse instantaneous value Instantaneou...

Страница 186: ...haracters Up to 16 characters A two byte character is counted as two characters PV pointer position EU PVPT Set the initial value for the pointer indicating the PV position of the bar graph displayed by the OIS Logging LOG Set whether to perform logging No Yes Related graphic file name PICT Simulation method SIMM Indicator value PV of indicator registered by Controller variable is used loop back s...

Страница 187: ...ize the integration value OFF ON When ON RST 1 is set the integration value of the integrator TTL is zeroed Device error PDE I O module error An ADC error or module down is generated Sensor error PVI Input signal error Broken wire or an error of sensor out of range occurred For condition of PVI generation refer to Signal type code SIG PV processing error PRE Either a device error PDE or a sensor e...

Страница 188: ... as a master loop in cascade control 4 20mA 4 20mA is selected with actual output signal Slow pulse width output is selected with pulse width slow actual signal Pulse width slow Slow pulse width output is selected with actual output signal Pulse width fast Fast pulse width output is selected with actual output signal Pulse train slow Slow pulse train output is selected with actual output signal Pu...

Страница 189: ...oefficient factor GAM 2 degree of freedom derivative coefficient 0 GAM 2 Deviation gap width EU GP In the case of CTL Ratio setter at the time of PID or SPI operation gain can be modified within the gap near the deviation SV PV Here its gap width can be set 0 GP 100 Ratio bias Note In the case of CTL Ratio setter this is defined as BIAS Deviation gap gain factor GG In the case of CTL Ratio setter ...

Страница 190: ... its alarm is as follows Suppose absolute value is ABS a deviation alarm DVE is generated when ABS SV PV DL is established and the alarm is restored when ABS SV PV DL DVB is established MV high alarm value MHA MV high alarm value is set MLA MHA MV low alarm value MLA MV low alarm value is set MLA MHA MV high low alarm dead band MVB Dead band for MV high low alarm is set 0 MVB Valve position PV No ...

Страница 191: ...his setting is used for new instrumentation FB library This cannot be used in standard output processing For details refer to New Instrumentation FB Library User s Manual Type of cascade value FS1 MV pointer position MVPT The position of operation pointer placed on the MV bar graph is set ML MVPT MH SV decimal point position DCSV When Ratio Setter is selected the decimal point position for SV valu...

Страница 192: ...output of MV stops Alarm suppression LSP Alarm suppression is set Note The following alarms will be reset when LSP ON MVH MVL and DVE Mode M M This is a BOOL type variable of the above control mode Either of M A C or RM turns on and the rest stays off depending on the condition of the control mode Note Read only data Does not affect the control mode MODE even if this variable is written Mode A A M...

Страница 193: ... for user application CMP intervening CMP Used for user application SEQ intervening SEQ Used for user application Cascade connection CC Used for user application Pulse output request flag For future use POR When Pulse is selected for Output signal type MSIG this flag is used to indicate the timing to send pulse output OFF ON Pulse output is executed when ON MV error unconfirmed MEU Unconfirmed bit...

Страница 194: ...icator light character NAM1 NAM2 NAM3 Name and comment data to be attached to Indicator light 1 to 3 is set 8 characters or less PB use flag USE This flag is used to register whether the corresponding instrument is used or not Used Not used Input point variable name IA1 IA2 IA3 Register the input points for input signals 1 3 For the registration method refer to Chapter 4 Registration and Setting U...

Страница 195: ...le Button 1 pressed output DA11 DA12 DA13 The operation for output of each point when Button 1 is pressed can be selected from the following None Set Reset Toggle Button 2 pressed output DA21 DA22 DA23 The operation for output of each point when Button 2 is pressed can be selected from the following None Set Reset Toggle Button 3 pressed output DA31 DA32 DA33 The operation for output of each point...

Страница 196: ... MOD is M DIO error For future use IOE Displays the error state of the I O module I O module error status is displayed Normal 0 alarm 1 Lamp FI1 FI2 FI3 Data entered from I O specified by the input hardware address IA1 to IA3 is displayed OFF 0 ON 1 Operation mode MODE Control mode is displayed A FO to be changed by application will be sent to DO output RM Mode when operated by button operation fr...

Страница 197: ...DI2 Digital input 2 BOOL 1 1 DI3 Digital input 3 BOOL 1 2 RM Remote input LC532 only BOOL 1 8 Analog input AI1 Analog input 1 UINT 2 AI2 Analog input 2 UINT 3 AI3 Analog input 3 UINT 4 AI4 Analog input 4 UINT 5 AI5 Analog input 5 UINT 6 AI6 Analog input 6 UINT 7 RB1 MV read back count 1 LC531 only UINT 8 RB2 MV read back count 2 LC531 only UINT 9 Digital output DO1 Digital output 1 BOOL 17 0 DO2 D...

Страница 198: ... DP00 System constant default value 0 REAL 272 DP01 System constant default value 1 REAL 274 DP02 System constant default value 2 REAL 276 DP03 System constant default value 3 REAL 278 DP04 Temperature and pressure correction constant default value 273 15 REAL 280 DP05 Temperature and pressure correction constant default value 459 4 REAL 282 DP06 Temperature and pressure correction constant defaul...

Страница 199: ... 0 No update 1 Update BOOL 671 15 External variable transmission error V01E External variable transmission error 1 0 Normal 1 Error BOOL 672 0 V02E External variable transmission error 2 0 Normal 1 Error BOOL 672 1 V03E External variable transmission error 3 0 Normal 1 Error BOOL 672 2 V04E External variable transmission error 4 0 Normal 1 Error BOOL 672 3 V32E External variable transmission error...

Страница 200: ...ss of Station No Receive area Station 1 AW 0 to AW 63 64 Receive area for data sent from Station 1 Receive area Station 2 AW 64 AW 127 128 Receive area for data sent from Station 2 Receive area Station i AW i 64 AW i 1 64 1 i 64 Note If the own station is Station i this area is not used Receive area Station 31 AW 1920 AW 1983 1984 Receive area for data sent from Station 31 Receive area Station 32 ...

Страница 201: ... Details of Module Parameters This chapter describes the module parameters of the LC53 that can be set and displayed from the nv Engineering Tool F 1 Module Parameter Setting 182 F 2 Module Parameter Data Display 183 ...

Страница 202: ...ask Set a subnet mask corresponding to the class up to 20 characters Example 255 255 255 0 Alarm restoration method Select whether to perform auto restoration of alarm or to require a confirmation before restoration Auto Confirm Default Auto Side display language Set the language type of the side display English Japanese Default English Side display contrast setting Set the contrast of the side di...

Страница 203: ... size Memory remaining size for program 0 to 6144 Total size Used size Code memory used step size Used memory size for program 0 to 6144 Data memory total step size Local variable total size 4096 fixed Data memory remaining step size Local variable remaining size 0 to 4096 Total size Used size Data memory used step size Used size of local variable 0 to 4096 Date time Current clock data YYYY MM DD ...

Страница 204: ...Appendix F Details of Module Parameters 6F8C1388 184 F ...

Страница 205: ...185 Appendix G Execution Performance of the LC531 LC532 G 1 Execution Performance of the LC531 LC532 186 G 2 Main Scan and Free Time 187 ...

Страница 206: ...uction word Execution time μs Remark LD 26 ST 163 A contact input 53 Coil output 61 Addition 131 Real type Subtraction 123 Real type Multiplication 131 Real type Division 125 Real type PID 786 Table G 2 Tag processing time TYP Tag type No of points Processing time ms Indicator tag PV 1 0 35 Controller tag LP 1 1 50 Pushbutton tag PB 1 0 47 CAUTION The performance value changes depending on the use...

Страница 207: ... make sure that the application functions normally in the LC53 set the main scan cycle time so that free time is 30 or more at least 30ms or create the application taking into account the execution time of main scan tasks For reference the calculation formula for obtaining execution time per loop is shown below CAUTION When the main scan cycle time is short sufficient free time may not be reserved...

Страница 208: ...Appendix G Execution Performance of the LC531 LC532 6F8C1388 G 188 ...

Страница 209: ...rate Side Keyboard 194 H 2 1 Change the Side Display Indication to English 195 H 2 2 Display the Alarm Currently Generated 195 H 2 3 Change the Operation Mode 196 H 2 4 Change the Tag 196 H 2 5 Change the General Variables 197 H 2 6 Change the Data of Polynomial Line Variable 198 H 2 7 Display the Version 199 H 2 8 Change the Controller Control Cycle MS task scan cycle 199 H 2 9 Restore the MV Err...

Страница 210: ... contact our service department CPU カンレン イジョウ MEM Memory related Memory related error Memory fault occurred or memory data may be destructed Perform Memory clear and Batch DL or contact our service department メモリ カンレン イジョウ IO1 External I O related Expansion I O related error For future use Expansion I O module is erroneous カクチョウ I O イジョウ IO2 Internal I O related Built in I O related error For f...

Страница 211: ...53 again to restart If no recovery occurs replace the LC53 システム プログラム テイシ BAT Battery Fault Battery error Battery error is detected Replace the battery with a new one バッテリ イジョウ WDT WDT OFF of Program Application WDT OFF WDT signal is turned off by user program Check the user program ZW 800 is other than 0 アプリケーション WDT OFF Table H 2 Types of process alarms 1 2 Tag Abbr Display contents Descrip...

Страница 212: ...L Deviation alarm value Check the user application program so that MV stays above MLA Check the user application program and PV signal source so that DV stays below DL Memo If M A manipulator or Ratio setter is selected for CTL alarm does not occur If the Mode is M or RM alarm does not occur MV ジョウゲン ケイホウ DVE Deviation Alarm Deviation alarm MV is lower than MLA MLA MV low alarm value Sensor erro...

Страница 213: ...tored by pressing any key to turn ON Batch download RUN start ダウンロードマチ DL シテクダサイ Key operation lock Key Hold Esc release Key operation locked Key operation is locked Press longer 2 seconds or more キー ソウサ ムコウ Esc カイジョ Key input error Limit Over Error Check Input Data Data limit over Input data has exceeded the defined range Display can be restored by pressing any key to turn ON Enter correct nu...

Страница 214: ...ral times Main Menu 0 Alarm Inf The operation methods are described for each of the following operation items Change the Side display indication to English Display the alarm currently generated Change the operation mode Change the tag Change the general variables Change the data of polynomial line variable P Check the version Change the controller control cycle MS task scan cycle Restore the MV er...

Страница 215: ...he auto lock Operation Display 6 5 2 Setting Enter Enter Screen SYSTEM HOLD ON SYSTEM HOLD OFF H 2 2 Display the Alarm Currently Generated Example Display the system alarm Operation System alarm display 0 0 Next alarm Screen System HRD Miscellaneous Hardware related System BAT Battery fault Example Display the process alarm Operation I O alarm display 0 2 Next alarm Screen LP 000 PDE Device Error ...

Страница 216: ... value after the decimal point is not always the same as the input data Example Input data 95 6 Display data 95 59999 If the input data has fewer digits than the display data delete unnecessary digits with Example When Current value 95 59999 Input value 50 4 Unnecessary digits 9999 the key input is as follows 5 0 4 DEL DEL DEL DEL Example Change the value of PV 004 PH to 150 Operation Display 2 0 ...

Страница 217: ...d in binary max 16 points For example internal flags of EC_US S1 S16 are displayed in binary 16 points The left end indicates the most significant bit S16 and the right end indicates the least significant bit S1 Example Display W 0000 in UNIT single integer without sign and change the value to 65535 Operation Display 4 1 Setting Enter 65535 Enter Screen W 0000 Unit 0 W 0000 Unit 65535 Remark For a...

Страница 218: ...99 P 02 04Y 94 8 P 02 04Y 94 80000 Polygonal line parameters of Polygonal line No 3 Coordinate X Coordinate Y 0 10 7 0 1 25 2 15 2 32 1 35 5 46 2 3 82 6 73 6 4 126 2 95 6 94 8 5 167 4 143 8 6 300 250 7 0 0 8 9 10 11 Remark For polygonal line parameters successive data input is available Press after data input to proceed to the next coordinate You can enter coordinate data successively by repeating...

Страница 219: ...basic software version OS kernel OS and TEST test pro version To switch version display press H 2 8 Change the Controller Control Cycle MS task scan cycle Example Change the control MS task scan cycle Operation Display 6 4 Enter Screen SYSTEM CT 1000 Example Check the scan time and free time Operation Display 6 4 Enter Display next Free time Screen SYSTEM MNOW 330 SYSTEM FNOW 1170 Remark For MS sc...

Страница 220: ...is displayed Example When LP 000 MVE is generated Operation Process alarm display 0 2 Check Enter Screen LP 000 MVE MV error Process Alarm None Remark For process alarms recovery confirm operation can be done only for MVE alarm Other process alarms will be restored automatically when the error is removed When multiple alarms exist the next alarm is displayed when is pressed after the alarm display...

Страница 221: ...ed to install the USB serial port driver for the LC53 to the PC for the nv Engineering Tool This chapter describes how to install the USB serial port driver I 1 Making USB Connection for the First Time 201 I 2 USB Driver Installation 203 I 3 Setting the nv Engineering Tool and Communication Parameters 206 ...

Страница 222: ...C automatically detects the USB connection and the New Hardware Wizard starts up as shown below Follow the instructions of the New Hardware Wizard and install the USB serial port driver for the LC53 Remark Before installation check that the LC53 install configuration file LC53_USB INF is stored in the folder C Program Files VEngTool of the nv Engineering Tool ...

Страница 223: ...Welcome to the Found New Hardware Wizard select Install from a list or specific location Advanced and click Next In Please choose your search and installation options select Search for the best driver in these locations select the Include this location in the search check box and enter the location C Program Files VEng Tool where the LC53 install configuration file LC53 _USB INF is stored Click Ne...

Страница 224: ...SB Driver Installation 6F8C1388 204 I Installation of the USB serial port driver starts and the following dialog is displayed If the following warning dialog is displayed click Continue to continue the installation ...

Страница 225: ...hen the installation of the USB serial port driver is complete the following dialog is displayed Click Finish to end installation The installation of the USB serial port driver is now complete From now on it will be automatically recognized when the USB cable is connected and USB connection will be ready for use ...

Страница 226: ...n check the COM port allocation state COM number with the device manager of the Windows system To use the nv Engineering Tool you need to set this COM number to the RS 232C port of the communication parameter of the nv Engineering Tool in advance From the menu bar of the main screen of the nv Engineering Tool the communication parameter setting screen is displayed by selecting Tools T Communicatio...

Страница 227: ...BUS reference Specifications The MODBUS reference specification for accessing from an ECBUS or MODBUS master is shown below J 1 How to take a reference number 208 J 2 Reference number list 208 J 3 Raw data structure 217 ...

Страница 228: ... relative number to a reference number Table J 1 The classification of a reference number Item Reference number Relative number Function Code Coil 0 Reference 1 1 5 15 Input relay 1 Reference 10001 2 Input register 3 Reference 30001 4 Holding register 4 Reference 40001 3 6 16 J 2 Reference number list The list of the reference numbers to which LC53 corresponds is shown ...

Страница 229: ...RA 3 GP 40017 40018 40019 40020 GG1 GG2 GG3 GG4 Gain within gap R W 0 000 1 000 LP_PARA 0 GG LP_PARA 1 GG LP_PARA 2 GG LP_PARA 3 GG 40021 40022 40023 40024 RT1 RT2 RT3 RT4 Ratio R W 327 68 327 67 without 0 00 LP_PARA 0 GG LP_PARA 1 GG LP_PARA 2 GG LP_PARA 3 GG It is effective when Ratio setter CTL 4 40025 40026 40027 40028 BS1 BS2 BS3 BS4 Bias R W 327 68 327 67 LP_PARA 0 GP LP_PARA 1 GP LP_PARA 2 ...

Страница 230: ...40062 40063 40064 BL1 BL2 BL3 BL4 Backlash pulse count or time s R W 0 HT 32767 LP_PARA 0 BL LP_PARA 1 BL LP_PARA 2 BL LP_PARA 3 BL 40065 40066 40067 40068 PB1 PB2 PB3 PB4 Pulse band R W 0 01 PB 327 67 LP_PARA 0 PLB LP_PARA 1 PLB LP_PARA 2 PLB LP_PARA 3 PLB 40069 40070 40071 40072 40073 40074 40075 40076 40077 40078 40079 40080 RH10 RL10 RH11 RL11 RH12 RL12 RH13 RL13 RH14 RL14 RH15 RL15 PV range u...

Страница 231: ... RH45 RL45 PV range upper and lower limits low three digit R W RL 32 767 32 768 RH PV_PARA 0 RH PV_PARA 0 RL PV_PARA 1 RH PV_PARA 1 RL PV_PARA 2 RH PV_PARA 2 RL PV_PARA 3 RH PV_PARA 3 RL PV_PARA 4 RH PV_PARA 4 RL PV_PARA 5 RH PV_PARA 5 RL 40117 40118 40119 40120 40121 40122 40123 40124 40125 40126 40127 40128 RH50 RL50 RH51 RL51 RH52 RL52 RH53 RL53 RH54 RL54 RH55 RL55 PV range upper and lower limi...

Страница 232: ...T6 Digital filter coefficient R W 0 0000 0 9999 PV_PARA 0 FT PV_PARA 1 FT PV_PARA 2 FT PV_PARA 3 FT PV_PARA 4 FT PV_PARA 5 FT 40159 40160 40161 40162 40163 40164 LC1 LC2 LC3 LC4 LC5 LC6 Low cut R W 0 00 100 00 PV_PARA 0 LC PV_PARA 1 LC PV_PARA 2 LC PV_PARA 3 LC PV_PARA 4 LC PV_PARA 5 LC 40165 40166 40167 40168 REQSV1 REQSV2 REQSV3 REQSV4 Remote operation SV setting demand value R W 3276 8 3276 7 L...

Страница 233: ...0008 GAMMA1 GAMMA2 GAMMA3 GAMMA4 Gamma R 3276 8 3276 7 LP_PARA 0 GAM LP_PARA 1 GAM LP_PARA 2 GAM LP_PARA 3 GAM 30009 30010 30011 30012 30013 30014 PV1 PV2 PV3 PV4 PV5 PV6 PV R 327 68 327 67 PV_DATA 0 PV PV_DATA 1 PV PV_DATA 2 PV PV_DATA 3 PV PV_DATA 4 PV PV_DATA 5 PV 30015 30016 30017 30018 SV1 SV2 SV3 SV4 SV R 327 68 327 67 LP_DATA 0 SV LP_DATA 1 SV LP_DATA 2 SV LP_DATA 3 SV 30019 30020 30021 300...

Страница 234: ...20 HC1 HC2 HC3 HC4 HC5 HC6 Sensor upper limit check execution flag R W PV_PARA 0 UIH PV_PARA 1 UIH PV_PARA 2 UIH PV_PARA 3 UIH PV_PARA 4 UIH PV_PARA 5 UIH 00021 00022 00023 00024 00025 00026 LC1 LC2 LC3 LC4 LC5 LC6 Sensor lower limit check execution flag R W PV_PARA 0 UIL PV_PARA 1 UIL PV_PARA 2 UIL PV_PARA 3 UIL PV_PARA 4 UIL PV_PARA 5 UIL 00027 00028 00029 00030 DO1 DO2 DO3 DO4 Digital output R ...

Страница 235: ... 10074 DOMODE1 DOMODE2 DOMODE3 DOMODE4 Digital output mode R PB_DATA 0 MODE PB_DATA 1 MODE PB_DATA 2 MODE PB_DATA 3 MODE 10075 10076 10077 10078 10079 10080 10081 10082 S1 S2 S3 S4 S5 S6 S7 S8 S flag data R S1 S2 S3 S4 S5 S6 S7 S8 10083 10084 10085 DI1 DI2 DI3 DI digital input data R DI1 DI2 DI3 10086 10087 10088 10089 10090 10091 PVI1 PVI2 PVI3 PVI4 PVI5 PVI6 PV inactive error flag R PV_DATA 0 PV...

Страница 236: ...10111 A1 A2 A3 A4 A mode flag R LP_DATA 0 A LP_DATA 1 A LP_DATA 2 A LP_DATA 3 A 10112 10113 10114 10115 M1 M2 M3 M4 M mode flag R LP_DATA 0 M LP_DATA 1 M LP_DATA 2 M LP_DATA 3 M M or RM 10120 10121 10122 10123 DVE1 DVE2 DVE3 DVE4 Deviation alarm R LP_DATA 0 DVE LP_DATA 1 DVE LP_DATA 2 DVE LP_DATA 3 DVE 10124 10125 10126 10127 CLI1 CLI2 CLI3 CLI4 Control inactive R LP_DATA 0 CLI LP_DATA 1 CLI LP_DA...

Страница 237: ...fter processing necessary data into the raw data structure automatically EC329 Transmit a message of the raw data transmission area The raw data transmission area of EC329 uses expand I O input and output data MIO EXT By defining variable to MIO EXT as below it prepares the transmit data Figure J 1 EC329 Defining variable to MIO EXT The list of the raw data structures EC300 EC329 are shown in the ...

Страница 238: ...O_DATA ADE 0 Reserve 2 1 AdTune state 1 Not applicable 2 Maximum station number 4 Module parameter EC bus maximum station number 2 S flag S1 S16 2 S1 S16 4 DI state bit0 DI1 bit1 DI2 bit2 DI3 bit3 DI4 bit4 DO5 bit5 DO6 bit6 M A5 bit7 M A6 1 SIO_DATA DI1 SIO_DATA DI2 SIO_DATA DI3 SIO_DATA DO5 PB_DATA 4 A 5 DO モード DO state bit0 DO1 bit1 DO2 bit2 DO3 bit3 DO4 bit4 M A1 bit5 M A2 bit6 M A3 bit7 M A4 1...

Страница 239: ...CLE bit9 M bit10 A bit11 C bit12 MVL bit13 MVH bit14 SLPE bit15 CMP 2 Not applicable Not applicable Not applicable LP_DATA 0 MVE LP_DATA 0 CLI LP_DATA 0 DVE Not applicable LP_DATA 0 M LP_DATA 0 A LP_DATA 0 C LP_DATA 0 MVL LP_DATA 0 MVH bit6 8 12 13 の OR LP_DATA 0 CMP 10 LOOP2 LOOP4 Structure is same as LOOP1 6 11 13 PV INT AI1 AI6 12 PV_DATA 0 PV PV_DATA 5 PV 14 19 SV INT LOOP1 LOOP4 8 LP_DATA 0 S...

Страница 240: ...C329 1 40h 0 Station abnormality information bit0 SM bit1 ADC 1 Not applicable SIO_DATA ADE 0 Reserve 3 1 Maximum station number 4 Module parameter EC bus maximum station number 3 X FLT X01 X60 240 MIO_EXT 0 MIO_EXT 118 5 123 1 LC53 correspondence internal variable when transmitting a message to other station 2 External variable setting VSET nn DADR when receiving a message from other station ...

Страница 241: ...2016 6rth Edition Infrastructure Systems Solutions Company Industrial Systems Division 72 34 Horikawa cho Saiwai ku Kawasaki 212 8585 Japan Toshiba Corporation 2013 2016 All Right Reserved No part of this document may be reproduced without the prior written consent of Toshiba ...

Страница 242: ...1388 6 1609 ...