HX7+ ASD Installation and Operation Manual
151
RX Gain Adjust
Program
Frequency Setting
Speed Reference Setpoints
RX
This parameter is used to fine tune the gain of the
RX
input terminal when this
terminal is used as the control input while operating in the
Speed Control
or
the
Torque Control
mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and either increasing
or decreasing this setting to provide an output of 100% from the ASD.
Direct Access Number — F475
Parameter Type —
Numerical
Factory Default —
141
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 255
RX2 Bias Adjust
Program
Frequency Setting
Speed Reference Setpoints
RX2
This parameter is used to fine tune the bias of the
RX2
input terminal when this
terminal is used as the control input while operating in the
Speed Control
or
the
Torque Control
mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and either increasing or
decreasing this setting to provide a zero output from the ASD.
Direct Access Number — F476
Parameter Type —
Numerical
Factory Default —
99
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 255
RX2 Gain Adjust
Program
Frequency Setting
Speed Reference Setpoints
RX2
This parameter is used to fine tune the gain of the
RX2
input terminal when this
terminal is used as the control input while operating in the
Speed Control
or
the
Torque Control
mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and either increasing
or decreasing this setting to provide an output of 100% from the ASD.
Direct Access Number — F477
Parameter Type —
Numerical
Factory Default —
141
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 255
Exciting Strengthening Coefficient
Program
Special Control
Special Parameters
This parameter determines the rate at which the excitation current is allowed to
go from zero to saturation and is enabled at
Direct Access Number — F480
Parameter Type —
Numerical
Factory Default —
64
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Over-Exciting Cooperation
Program
Special Control
Special Parameters
This parameter determines the method used to control the rate that the
excitation current is allowed to reach saturation. If
Effective
is selected, the
preset
Torqu
e
Control
or
Speed
Control
settings will determine the rate that
the motor reaches excitation saturation.
Settings:
0 — Effective
1 — Applied by
Direct Access Number — F481
Parameter Type —
Selection List
Factory Default —
Effective
Changeable During Run —
Yes
Содержание HX7+ ASD
Страница 1: ...HX7 ASD Install Op Manual TOSHIBA HX7 ASD INSTALLATION OPERATION MANUAL DN 67017 001 February 2014 ...
Страница 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Страница 219: ...210 HX7 ASD Installation and Operation Manual Figure 27 66 200 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 220: ...HX7 ASD Installation and Operation Manual 211 Figure 28 260 518 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 221: ...212 HX7 ASD Installation and Operation Manual Figure 29 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 222: ...HX7 ASD Installation and Operation Manual 213 Figure 30 1200 1500 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 223: ...214 HX7 ASD Installation and Operation Manual Figure 31 66 200 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 224: ...HX7 ASD Installation and Operation Manual 215 Figure 32 260 518 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 225: ...216 HX7 ASD Installation and Operation Manual Figure 33 518 1000 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 226: ...HX7 ASD Installation and Operation Manual 217 Figure 34 1200 1500 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Страница 228: ...HX7 ASD Installation and Operation Manual 219 Figure 36 260 518 kVA Sine Wave NEMA 1 Enclosure ...
Страница 229: ...220 HX7 ASD Installation and Operation Manual Figure 37 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 230: ...HX7 ASD Installation and Operation Manual 221 Figure 38 932 1500 kVA Sine Wave NEMA 1 Enclosure ...
Страница 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Страница 232: ...HX7 ASD Installation and Operation Manual 223 Figure 40 260 518 kVA Sine Wave NEMA 3R Enclosure ...
Страница 233: ...224 HX7 ASD Installation and Operation Manual Figure 41 518 1000 kVA Sine Wave NEMA 3R Enclosure ...
Страница 234: ...HX7 ASD Installation and Operation Manual 225 Figure 42 932 1500 kVA Sine Wave NEMA 3R Enclosure ...
Страница 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Страница 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Страница 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Страница 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...