6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 734 -
(viii)
Signal name and number
Note: The user should note the following descriptions shown in the column “M/O” for
each table:
“O” indicated that the signal is provided for optional use.
“M” indicates that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings are
used.
“N/A” indicates that the user cannot change the state of the signal.
Table 4.8-2 PLC Connection points (Input points for Command ‘On’)
Signal Number
Signal Name
Description
M/O
512001 800301EE32
DEV01_CL_COMMAND
DPOS01 PLC On-control checking with interlock(PLC#1)
O
512001 800302EE32
DEV02_CL_COMMAND
DPOS02 PLC On-control checking with interlock(PLC#1)
O
512001 800303EE32
DEV03_CL_COMMAND
DPOS03 PLC On-control checking with interlock(PLC#1)
O
….
….
….
512001 800348EE32
DEV72_CL_COMMAND
DPOS72 PLC On-control checking with interlock(PLC#1)
O
512001 800301EE33
DEV01_CL_INTERLOCK DPOS01 PLC On-control without checking(PLC#2)
O
512001 800302EE33
DEV02_CL_INTERLOCK DPOS02 PLC On-control without checking(PLC#2)
O
512001 800303EE33
DEV03_CL_INTERLOCK DPOS03 PLC On-control without checking(PLC#2)
O
….
….
….
512001 800348EE33
DEV72_CL_INTERLOCK DPOS72 PLC On-control without checking(PLC#2)
O
Table 4.8-3 PLC Connection points (Input points for Command ‘Off’)
Signal Number
Signal Name
Description
M/O
512001 800301EE30
DEV01_OP_COMMAND
DPOS01 PLC Off-control checking with interlock(PLC#1)
O
512001 800302EE30
DEV02_OP_COMMAND
DPOS02 PLC Off-control checking with interlock(PLC#1)
O
512001 800303EE30
DEV03_OP_COMMAND
DPOS03 PLC Off-control checking with interlock(PLC#1)
O
….
….
….
512001 800348EE30
DEV72_OP_COMMAND
DPOS72 PLC Off-control checking with interlock(PLC#1)
O
512001 800301EE31
DEV01_OP_INTERLOCK
DPOS01 PLC Off-control without checking(PLC#2)
O
512001 800302EE31
DEV02_OP_INTERLOCK
DPOS02 PLC Off-control without checking(PLC#2)
O
512001 800303EE31
DEV03_OP_INTERLOCK
DPOS03 PLC Off-control without checking(PLC#2)
O
….
….
….
512001 800348EE31
DEV72_OP_INTERLOCK
DPOS72 PLC Off-control without checking(PLC#2)
O
Table 4.8-4 PLC Connection points (Interlock for Command ‘On/Off’)
Signal Number
Signal Name
Description
M/O
570001 3103021DA2
DPOS01-Close
DPOS01 interlock condition for On control.
N/A
570001 3103031DA2
DPOS02-Close
DPOS02 interlock condition for On control.
N/A
570001 3103041DA2
DPOS03-Close
DPOS03 interlock condition for On control.
N/A
…
…
…
570001 3103481DA2
DPOS72-Close
DPOS72 interlock condition for On control.
N/A
570001 3103011DA0
DPOS01-Open
DPOS01 interlock condition for Off control.
N/A
570001 3103021DA0
DPOS02-Open
DPOS02 interlock condition for Off control.
N/A
570001 3103031DA0
DPOS03-Open
DPOS03 interlock condition for Off control.
N/A
….
….
….
570001 3103481DA0
DPOS72-Open
DPOS72 interlock condition for Off control.
N/A
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......