6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 687 -
Permission signal “SYNC01_SLD_VCS”
†
The “SYNC01_SLD_VCS” signal is transferred to the DPSY01 select-logic. For example,
suppose the DPSY01 function is given permission to operate when any voltage-condition is
satisfied, then the user should set
On
for the scheme switches [
SYNCHK01-LRDIEN
],
[
SYNCHK01-DRLIEN
], and [
SYNCHK01-DRDIEN
].
For example, if the DPSY01 function is required to operate when the voltage condition
“LRDI” is confirmed (Table 4.6-4.(4)), just set
On
for the scheme switch [
SYNCHK01-LRDIEN
].
User programmable pick-up delay timers are available for the conditions “LRDI” and
“DRLI” (Table 4.6-4.(1 and 4)); hence the user can set a desired value for the setting
[
SYNC01_TLRDIDRLI
]; similarly, a desired value can be applied for the setting
[
SYNC01_TDRDI
] for the condition “DRDI” (Table 4.6-4.(3)).
†Note: This signal is required for CB closing in the select logic. For more information, see
separate section
DPSY: Control logics.
Permission signal “SYNC01_SYN_CLC”
‡
The “SYNC01_SYN_CLC” signal is input to the DPSY01 operate-closing-logic as a permissive
signal. The DPSY01 function is allowed to operate when any voltage-conditions except “LRLI”
is satisfied in the DPSY01 operation.
‡Note: This signal is required only for CB closing in the operate-closing logic. For more
information, see separate section
DPSY: Operate logics.
(iii)
Adding other voltage-conditions using PLC signals
The user can add a user-preferred condition to the logic signal using PLC connection points.
In the SYNCHK1 logic, points “SYNC01_LLV_CL_ECP, _LDV_CL_ECP, _DLV_CL_ECP, and
_DDV_CL_ECP” are provided†. Similarly, points “SYNC02_LLV_CL_ECP, _LDV_CL_ECP,
_DLV_CL_ECP, and _DDV_CL_ECP” are provided in the SYNCHK2 function.
†Note: For more information on PLC programing, see chapter
PLC function, separately.
(iv)
Relay selection using PLC signals
Either SYNCHK_Ry1 or SYNCHK_Ry2 function can be chosen for SYNCHK1 operation. On
this account, points “SYNC01_RY1_USE_STS and _RY2_USE_STS” are provided and the user
can choose either for use in conjunction with SYNCHK1 operation; similarly,
“SYNC02_RY1_USE_STS and _RY2_USE_STS” are provided for SYNCHK2 operation. The
purpose of the choice is discussed in section 4.6.5.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......