Inrush current detection function (ICD)
When a current transformer (CT) is first energized, an inrush current flows into the CT
transiently to establish the magnetic field. The magnitude of the inrush current can greater
than the full load current so much; thus, the protection function can issue trip signals falsely.
That is, the inrush current is required to detected and the protection functions shall not
operate during CT energizing. Inrush current detection (ICD) function is designed to detect a
second harmonic inrush current. This is because, the inrush current has all order of harmonics,
but the second harmonics is the greatest†. Signals generated in the ICD function are
transferred to other protection functions to block their operations.
†Note: The second harmonic current is present all inrush currents in three-phases. The
proportion of the second harmonic current varies with the degree of the
energizing, but the ratio of the second harmonic current to the fundamental
current can be about 20% or greater during energizing.
─────────────────────────────────────────────────────────────────
Note:
The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the “G&T position” whilst
referring to the comparison table below. For more information, see
Appendix: Ordering
.
Table 2.19-1 Comparative table in respective ordering numbers
Sec.
Feature
Ordering No. at “G&T”
31
32
–
Main features
✓
✓
✓
: Applicable NA: Not applicable
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......