6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 215 -
2.8.4
Setting
THM (Function ID: 451001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
THM-EN
Off / On
- Thermal protection scheme switch
Off
THM
0.40 -
2.00
2.00 -
10.00
A Thermal overload current
1.00
5.00
TTHM
0.5 - 500.0
min
Thermal time constant
10.0
Type
THM-Itype
Max phase/
Equivalent
- Selection of THM equations
Equivalent
THM-q
0 - 10
- Factor when Equivalent selected
0
SW
THMT-EN
Off / On
- Thermal protection
Off
THM-UseFor
Trip / Alarm
- THM used for trip or alarm
Trip
ALM
THMA-EN
Off / On
- Thermal alarm switch
Off
THM-Alarm
50 - 100
% Thermal alarm level multiplier
80
Test tool(Function ID: 451001)
Items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Function test
THM-Test
Off / On
- Thermal protection scheme switch
Off
THM-IP
0.00 -
1.00
0.00 -
5.00
A Thermal overload current
0.00
0.00
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......