6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 167 -
2.5.7
Setting
OC (Function ID: 440001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
OC1-EN
Off / On
- OC1 protection scheme switch
Off
OC2-EN
Off / On
- OC2 protection scheme switch
Off
OC3-EN
Off / On
- OC3 protection scheme switch
Off
OC4-EN
Off / On
- OC4 protection scheme switch
Off
OC1
OC1-Dir
NonDir / Forward /
Reverse
- OC1 directional characteristic
NonDir
OC1-Angle
0 - 180
deg OC1 directional characteristic angle
45
OC1-Timer
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
IEEE-EI / US-CO2 /
US-CO8 / Original
- OC1 delay type
DT
DT
OC1
0.02 -
50.00
0.10 -
250.00
A OC1 threshold (in DT mode)
1.00
5.00
OC1-DPR
10 - 100
% OC1 drop-out/pick-up ratio
100
TOC1
0.00 - 300.00
s OC1 operating delay time (in DT mode)
1.00
IEC
OC1
0.02 -
5.00
0.10 -
25.00
A OC1 threshold (in IDMT mode)
1.00
5.00
OC1-DPR
10 - 100
% OC1 drop-out/pick-up ratio
100
OC1-TMS-IEC
0.010 - 50.000
- OC1 time multiplier of IEC inverse curve
1.000
TOC1R
0.00 - 300.00
s OC1 definite time reset delay
0.00
UK
OC1
0.02 -
5.00
0.10 -
25.00
A OC1 threshold (in IDMT mode)
1.00
5.00
OC1-DPR
10 - 100
% OC1 drop-out/pick-up ratio
100
OC1-TMS-UK
0.010 - 50.000
- OC1 time multiplier of UK inverse curve
1.000
TOC1R
0.00 - 300.00
s OC1 definite time reset delay
0.00
IEEE
OC1
0.02 -
5.00
0.10 -
25.00
A OC1 threshold (in IDMT mode)
1.00
5.00
OC1-DPR
10 - 100
% OC1 drop-out/pick-up ratio
100
OC1-TMS-
IEEE
0.010 - 50.000
- OC1 time multiplier of IEEE inverse curve
1.000
OC1-Rtimer
DEF / DEP
- OC1 reset delay type of IEEE
DEF
TOC1R
0.00 - 300.00
s OC1 definite time reset delay
0.00
OC1-RTMS-
IEEE
0.010 - 50.000
-
OC1 dependent reset time multiplier of IEEE
inverse curve
1.000
US
OC1
0.02 -
5.00
0.10 -
25.00
A OC1 threshold (in IDMT mode)
1.00
5.00
OC1-DPR
10 - 100
% OC1 drop-out/pick-up ratio
100
OC1-TMS-US
0.010 - 50.000
- OC1 time multiplier of US inverse curve
1.000
OC1-Rtimer
DEF / DEP
- OC1 reset delay type of US
DEF
TOC1R
0.00 - 300.00
s OC1 definite time reset delay
0.00
OC1-RTMS-US
0.010 - 50.000
-
OC1 dependent reset time multiplier of US
inverse curve
1.000
ORG
OC1
0.02 -
5.00
0.10 -
25.00
A OC1 threshold (in IDMT mode)
1.00
5.00
OC1-DPR
10 - 100
% OC1 drop-out/pick-up ratio
100
OC1-TMS-ORG
0.010 - 50.000
- OC1 time multiplier of ORG inverse curve
1.000
OC1-Rtimer
DEF / DEP
- OC1 reset delay type of US
DEF
TOC1R
0.00 - 300.00
s OC1 definite time reset delay
0.00
OC1-RTMS-
ORG
0.010 - 50.000
-
OC1 dependent reset time multiplier of ORG
inverse curve
1.000
OC1-k
0.00000 - 500.00000 - OC1 user original curve coefficient
0.00000
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......