6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 136 -
carrier communication, the carrier signal received by the binary input is connected to PLC
connection point (DISCAR-R1). As a result, (External DISCAR-R1) signal will be generated.
In addition, DISCAR has the scheme switch [
DisCAR-CHSEL
]. By this setting, (External
DISCAR-R1) signal generation is as follows.
Single
:
(External DISCAR-R1) signal will be generated by only (DISCAR-R1).
And
:
(External DISCAR-R1) signal will be generated by (DISCAR-R1) and
(DISCAR-R1-2) for fail safe.
Guard
:
(External DISCAR-R1) signal will be generated by (DISCAR-R1) and non
(DISCAR-R1-2) for fail safe.
In the integral carrier communication, the received carrier signals transmitted by the
DIF_COMM function are connected to PLC connection point (INT.DISCAR-R1-*). As a result,
(Integral DISCAR-R1-*) signals will be generated.
DISCAR-R1-2
800000EBB2
INT.DISCAR-R1-A
800000EBB5
INT.DISCAR-R1-B
810000EBB6
INT.DISCAR-R1-C
820000EBB7
INT.DISCAR-R1-S
830000EBB8
DISCAR-R1
800000EBB1
Carrier signal
Used for the external carrier communication
(Carrier signal received at binary inputs)
Used for the integral carrier communication
(Carrier signal transmitted by the transmission control function (DIF_COMM))
Carrier signal (for Phase-A)
ase-A)
Carrier signal (for Phase-B)
Carrier signal (for Phase-C)
Carrier signal (for Short)
DisCAR-CHSEL
Guard
And
Single
&
1
&
&
≥1
t 0
5ms
External DISCAR-R1
Integral DISCAR-R1-A
Integral DISCAR-R1-B
Integral DISCAR-R1-C
Integral DISCAR-R1-S
Figure 2.3-13 How to receive carrier signals
How to receive carrier signals from the remote terminal 2 is the same.
Note: When applying UOP or BOP, the user must assign the signal “C1_BIT”
(*)
to the PLC
connection points shown below.
(*)“C1_BIT” is a BIT type signal that always holds 1. The Data ID of the signal
is shown in
Appendix: Signal list for common function
.
- In the external carrier communication, assign
the signal “C1_BIT” to the PLC
connection points (INT.DISCAR-R*-A), (INT.DISCAR-R*-B), (INT.DISCAR-R*-C) and
(INT.DISCAR-R*-S) that are not used in external carrier communication.
- In the integral carrier communication, assign
the signal “C1_BIT” to the PLC
connection point (DISCAR-R*) that is not used in the integral carrier communication.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......