6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1008 -
Fault Record#1
11:12 1/222
2
012-07-25
10:48:21.223
Phase AB
OC1, OC2, OC3, OC4
SOTF
–OC
FL 0.0km
0% OB/NC
2012-07-25
10:48:22.421
ARC-S1
2012-07-25
10:48:22.835
OC1
2012-07-25
10:48:23.208
ARC-S2
2012-07-25
10:48:23.649
OC1, FT
Fault values
Ia
1234.56kVa 123.4deg
Ib
1234.56kVa 123.4deg
Ic
1234.56kVa 123.4deg
PreFault values
Ia
1234.56kVa 123.4deg
Ib
1234.56kVa 123.4deg
Ic
1234.56kVa 123.4deg
○
a Record Num ber (#1)
○
b Date and Tim e at Fault (YYYY-MM-DD)
○
c Tripped phase inform ation
○
d Mode inform ation
○
f Detail inform ation about evolving faults
○
g Fault quantities
○
h Pre-fault quantities
Screen scroll down
Detail inform ation about evolving faults
ARC Shot#1 issued
E volving fault#1; detection m ade by OC1 relay
ARC Shot#2 issued
○
e FL calculation results
E volving fault#2; abandoning to reclose CB (i.e., Final Trip)
Figure 8.1-2 Screen structure about the information #1.
8.1.3
Setup for the fault recorder
(i)
Operation identifiers (ID1–ID128)
The user can select the operation identifies arbitrarily using the settings [
OP Mode ID1
] etc.
For example, when the operation result with regard to the overcurrent relay element (i.e., OC1
in phase-A) shall be recorded, choose the operated signal ‘OC1-OPT-A (440001 800011B68)”
and set it for the [
OP Mode ID1
]. Remember to program the displaying name about the OC1-
OPT-A using the setting [
OP Mode Name1
] (e.g., “OC1-A relay OP-ed”). Note that the length
of the displaying name should be less than 18 letters. The user should find blanks in the setting
list, because several IDs have been already set.
(ii)
Logical signals (ID201–ID264)
Wishing to record a logical level ‘1 (TRUE)’ or ‘0 (FALSE)’ on the circuits, the user can pick the
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......