For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-
2192
17
7
Three Wire Control
Introduction
The G3 can be programmed to allow three-wire start/stop functionality without the use of an external relay.
Notice: that the pushbuttons utilized are momentary. The switch ‘S3” determines direction. Remember to cycle
power when finished with any super user programming.
Connections For the g3 three wire control
Programming
Group
Parameter
New Value
UTILITY PARAMETERS
Command Mode Selection
*
1
UTILITY PARAMETERS
Frequency Mode Selection
*
2
UTILITY PARAMETERS
Blind Function Selection
1
UTILITY PARAMETERS
Terminal Selection Parameters Blind
1
TERMINAL SELECTION PARAMETERS
Input Terminal Selection
1
TERMINAL SELECTION PARAMETERS
“S1” Input Terminal Selection
37
TERMINAL SELECTION PARAMETERS
“S2” Input Terminal Selection
38
TERMINAL SELECTION PARAMETERS
“S3” Input Terminal Selection
40
Notes
*1 – Command Mode Selection controls how the run command is given to the drive. The following
settings are useable with 3 wire control .
1 – Terminal Input Valid.
4 – Local/Remote control. Local/Remote light must be off.