G2020 Series UPS Installation and Operation Manual
– 94861-004
43
Table 5-6 Crimp Type Compression Lug
WIRE
SIZE
WIRE
STRAND
RECOMMENDATION
CRIMP TOOL REQUIRED
BURNDY TYPE Y35 OR Y46
(CODE)
CLASS
VENDOR
CAT. NO.
COLOR KEY
DIE INDEX
1
B
I
BURNDY
ILSCO
BURNDY
YA1C
CRA-1L
YA25-LB
GREEN
GREEN
---
11 / 375
11 / 375
1019
1/0
B
I
BURNDY
ILSCO
BURNDY
YA25
CRA-1/OL
YA25-LB
PINK
PINK
---
12 / 348
12 / 348
1020
2/0
B
I
BURNDY
ILSCO
BURNDY
YA26
CRA-2/OL
YA27-LB
BLACK
BLACK
---
13
13
1021
3/0
B
I
BURNDY
ILSCO
BURNDY
YA27
CRB-3/OL
YA28-LB
ORANGE
ORANGE
---
14 / 101
14 / 101
1022
4/0
B
I
BURNDY
ILSCO
BURNDY
YA28
CRB-4/OL
YA29-LB
PURPLE
PURPLE
---
15
15
1023
250 MCM
B
I
BURNDY
ILSCO
BURNDY
YA29
CRA-250L
YA30-LB
YELLOW
YELLOW
---
16
16
1024
300 MCM
B
I
BURNDY
ILSCO
BURNDY
YA30
CRA-300L
YA32-LB
WHITE
WHITE
---
17 / 298
17 / 298
1026
350 MCM
B
I
BURNDY
ILSCO
BURNDY
YA31
CRA-350L
YA34-LB
RED
RED
---
18 / 324
18 / 324
1027
400 MCM
B
I
BURNDY
ILSCO
BURNDY
YA32
CRA-400L
YA36-LB
BLUE
BLUE
---
19 / 470
19 / 470
1027
500 MCM
B
I
BURNDY
ILSCO
BURNDY
YA34
CRA-500L
YA38-LB
BROWN
BROWN
---
20 / 299
20 / 299
1029
600 MCM
B
I
BURNDY
ILSCO
BURNDY
YA36
CRA-600L
YA39-LB
GREEN
GREEN
---
22 / 472
22 / 472
1030
750 MCM
B
BURNDY
ILSCO
YA39
CRA-750L
BLACK
BLACK
24
24
NOTE:
When using crimp type lugs, the lugs should be crimped to the specifications given in the
manufacturer's instructions for both crimp tool and lug
.
/ CHA
Static Transfer
Switch
Bypass
Input
Terminals
A40
B40
C40
AC
Input
Terminals
A
B
C
CB1
Terminals
BP
BN
External
Battery
CB2
Converter
/Charger
Inverter
Terminals
A50
B50
C50
AC
Output
52C
CB3
52S
Figure 5-1 UPS Terminal Designation